Plan Review Details - Permit 12060468
Plan Review Stops For Permit 12060468
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-06-19 Cont ID  
Sent By jgomez Date 2012-06-19 Time 10:21 Rev Time 0.00
Received By jgomez Date 2012-06-19 Time 10:20 Sent To  
Notes
2012-06-19 10:29:39BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- ROBERT BROWN MET WITH CONTRACTOR (PHILIP BLAKE) AND
 APPROVED ONE TIME SPECIAL REPAIR PERMIT TO FIX LEAKING
 ROOF. ROBERT ASKED CONTRACTOR TO PROVIDE LETTER STATING
 THE SPECIAL CONDITIONS ON THIS ROOF. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-06-18 Cont ID  
Sent By jgomez Date 2012-06-18 Time 16:41 Rev Time 0.00
Received By jgomez Date 2012-06-18 Time 15:59 Sent To  
Notes
2012-06-18 17:01:41RESIDENTIAL RE-ROOF BUILDING REVIEW COMMENTS.
 2010 FBC.
  
 1- THIS IS A QUADRUPLEX AND ALL FOUR UNITS ARE SHARING
 THE SAME ROOF. NEED TO RE-ROOF ENTIRE ROOF AS REQUIRED
 BY SEC. 611.1.1 OF 2010 FBC-EXISTING BUILDING.
  
 2- NEED SEPARATE PERMIT FOR THE ROOF A/C UNITS REMOVAL
 AND REPLACEMENT TO VERIFY COMPLIANCE WITH THE WIND
 RESISTANCE AS REQUIRED BY SEC. M1307.2.1.
  
 3- CONTRACTOR TO REVISE THE BUILDING MEAN ROOF HEIGHT.
 THIS IS A TWO STORY BUILDING. THEREFORE 12'-0" MRH IS
 INCORRECT. SEC. 107.2.1 OF CITY AMENDMENTS TO FBC.
  
 4- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7 ON NOA 12-0227.18 SUBMITTED. NEED RAS 117
 CALCULATIONS TO MEET THE DESIGN PRESSURES REQUIRED BY
 SEC. R301.2.1.4.3 OF 2010 FLORIDA RESIDENTIAL CODE.
 ***NOTE; TAKE INTO CONSIDERATION THAT THIS BUILDING IS
 LOCATED ON EXPOSURE "C".
  
 5- SPECIFY WHICH BASE SHEET FASTENING OPTION ON PAGE 14
 OF NOA SUBMITTED IS GOING TO BE USED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.2.1.4.3 AND RAS 117 CALCULATIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-06-19 Cont ID  
Sent By jgomez Date 2012-06-19 Time 10:20 Rev Time 0.00
Received By jgomez Date 2012-06-19 Time 10:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-06-18 Cont ID  
Sent By jgomez Date 2012-06-18 Time 16:00 Rev Time 0.00
Received By jgomez Date 2012-06-18 Time 16:00 Sent To  
Notes
***NONE***