Plan Review Details - Permit 12060388
Plan Review Stops For Permit 12060388
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2012-09-06 Cont ID  
Sent By rmcdouga Date 2012-09-06 Time 16:22 Rev Time 0.00
Received By rmcdouga Date 2012-09-06 Time 11:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2012-09-04 Cont ID  
Sent By rmcdouga Date 2012-09-04 Time 15:07 Rev Time 0.00
Received By rmcdouga Date 2012-09-04 Time 11:35 Sent To  
Notes
2012-09-04 15:36:262010 FBC
  
 1) THE PRODUCT APPROVALS SUBMITTED DO NOT MATCH THE
 PRODUCT APPROVAL NUMBERS LISTED IN THE WINDOW AND DOOR
 SCHEDULES FOR THE FIXED WINDOWS, HORIZONTAL SLIDING
 WINDOWS OR THE ENTRY DOOR. PLEASE CORRECT. DCA RULE
 9N-3
  
 2) THE PRODUCT APPROVALS FOR THE LINTELS AND TRUSS
 ANCHORS HAVE NOT BEEN UPLOADED. DCA RULE 9N-3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-07-25 Cont ID  
Sent By rmcdouga Date 2012-07-25 Time 14:07 Rev Time 0.00
Received By rmcdouga Date 2012-07-25 Time 14:06 Sent To  
Notes
2012-07-25 13:29:182010 FBC
  
 DENIED BY BUILDING
  
 1) CORRECTED.
  
 2) CORRECTED.
  
 3) CORRECTED. HOWEVER, THE DOOR SCHEDULE LISTS TWO
 STATE PRODUCT APPROVAL NUMBERS FOR THE AMARR GARAGE
 DOOR. THE PRODUCT APPROVAL PRESSURES (-52.1, +45.9 PSF)
 LISTED IN THE SCHEDULE ARE FOR FL #7170-R3. ACCORDING
 TO THE PRODUCT EVALUATION, FL #6243 HAS PRESSURES OF
 (-41.0, +37.0 PSF) WHICH ARE LESS THAN THE REQUIRED
 OPENING PRESSURES SPECIFIED IN THE DOOR SCHEDULE.
 PLEASE CORRECT. CITY AMENDMENTS 107.2.1 AND R301.2.1
  
 4) CORRECTED.
  
 5) CORRECTED.
  
 6) CORRECTED.
  
 7) CORRECTED.
  
 8) SUBMIT CURRENT PRODUCT APPROVALS FOR THE EXTERIOR
 DOORS, WINDOWS, ROOFING MATERIAL, LINTELS AND OTHER
 COMPONENTS AND CLADDING REQUIRED BY DCA RULE 9N-3.
 PRODUCT APPROVALS FOR THE ROOFING MATERIAL, LINTELS AND
 TRUSS ANCHORS HAVE NOT BEEN SUBMITTED. ALSO, PLEASE
 SUBMIT THE FL COVERSHEET AND EVALUATION REPORT FOR THE
 FIBERGLASS ENTRY DOOR.
  
 9) SUBMIT MANUFACTURER'S SPECIFICATIONS AND/OR
 EVALUATIONS FOR THE SPRAY FOAM INSULATION, FIRE
 RETARDANT COATING AND HUBER ROOF SHEATHING.
  
 10) CORRECTED.
  
 11) THE WINDLOADS SPECIFIED IN THE TABLE ON SHEET S-3
 NEEDS TO MATCH THE OPENING PRESSURES SPECIFIED IN THE
 WINDOW AND DOOR SCHEDULES ON THE ARCHITECTURAL
 DRAWINGS. CITY AMENDMENTS 107.2.1 AND FBC R301.2.1 THE
 SLIDING GLASS DOOR AND OVERHEAD GARAGE DOOR PRESSURES
 DO NOT MATCH. ALSO, IN THE DOOR SCHEDULE THE POSITIVE
 PRESSURE IS MORE THAN THE NEGATIVE PRESSURE FOR THE
 SLIDING GLASS DOOR. THE NEGATIVE PRESSURE IS ALWAYS
 HIGHER. PLEASE CORRECT.
  
 12) THE FLOOR PLAN, ROOF PLAN AND ELEVATIONS THAT WERE
 SUBMITTED ARE ALL FOR A 6 UNIT BUILDING. IF YOU WISH TO
 USE THIS MASTER FOR BUILDINGS WITH OTHER THAN SIX UNITS
 YOU WILL NEED TO SUBMIT FLOOR PLANS, ROOF PLANS AND
 ELEVATIONS FOR EACH OF THE DIFFERENT CONFIGURATIONS.
 CITY AMENDMENTS 107.2.1
  
 13) NEW COMMENT. ON SHEET S-3 THE INTERIOR AND CORNER
 ZONE PRESSURES FOR THE ENTRY DOOR ARE THE SAME. THE
 CORNER ZONE PRESSURES SHOULD BE HIGHER. PLEASE CORRECT.
 FBC R301.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-06-29 Cont ID  
Sent By rmcdouga Date 2012-06-29 Time 13:45 Rev Time 0.00
Received By rmcdouga Date 2012-07-25 Time 11:48 Sent To  
Notes
2012-06-29 12:29:462010 FBC
  
 DENIED BY BUILDING
  
 1) ON PLAN SHEET T-1, THE STRUCTURAL NOTES SPECIFY ASCE
 7-05 AND A WINDSPEED OF 175 MPH. THE 2010 FBC
 REFERENCES ASCE 7-10 AND THE WINDSPEED FOR RISK
 CATEGORY II IS 170 MPH. FBC CHAPTER 43 AND FBC
 R301.2.1.1
  
 2) PLEASE UPDATE THE FOLLOWING STANDARDS SPECIFIED ON
 T-1 TO THE 2008 EDITIONS. ACI 318, ACI 530, ASCE 5, AND
 TMS 402. FBCR CHAPTER 43
  
 3) THE PRODUCT APPROVAL INFORMATION IN THE DOOR AND
 WINDOW SCHEDULE NEED TO BE BROUGHT CURRENT. ALL OF THEM
 HAVE EXPIRED, BEEN SUPERSEDED OR BEEN REVISED. DCA RULE
 9N-3
  
 4) THE REQUIRED OPENING PRESSURES LISTED IN THE
 SCHEDULE FOR DOOR NUMBER 2 ARE HIGHER THAN THE ONES
 INDICATED FROM THE PRODUCT APPROVAL. PLEASE CORRECT.
 FBC R301.2.1
  
 5) PLEASE REVIEW ALL NEW PRODUCT APPROVAL DESIGN
 PRESSURES AGAINST THE REQUIRED OPENING PRESSURES TO
 VERIFY COMPLIANCE WITH FBC R301.2.1
  
 6) IN THE DOOR SCHEDULE ON SHEET TU-1.0 THE REMARKS FOR
 DOOR 2 HAVE BEEN PRINTED OVER AND ARE NOT LEGIBLE.
 PLEASE CORRECT. CITY AMENDMENTS 107.2.1
  
 7) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD. CITY AMENDMENTS
 107.3.4.1
  
 8) SUBMIT CURRENT PRODUCT APPROVALS FOR THE EXTERIOR
 DOORS, WINDOWS, ROOFING MATERIAL, LINTELS AND OTHER
 COMPONENTS AND CLADDING REQUIRED BY DCA RULE 9N-3.
  
 9) SUBMIT MANUFACTURER'S SPECIFICATIONS AND/OR
 EVALUATIONS FOR THE SPRAY FOAM INSULATION, FIRE
 RETARDANT COATING AND HUBER ROOF SHEATHING.
  
 10) ON SHEET S-1 IN THE DESIGN PARAMETERS AND
 ASSUMPTION TABLE UNDER BUILDING HEIGHT ASCE 7-05 IS
 SPECIFIED. PLEASE UPDATE TO ASCE 7-10. FBCR CHAPTER 43
  
 11) THE WINDLOADS SPECIFIED IN THE TABLE ON SHEET S-3
 NEEDS TO MATCH THE OPENING PRESSURES SPECIFIED IN THE
 WINDOW AND DOOR SCHEDULES ON THE ARCHITECTURAL
 DRAWINGS. CITY AMENDMENTS 107.2.1 AND FBC R301.2.1
  
 12) THE FLOOR PLAN, ROOF PLAN AND ELEVATIONS THAT WERE
 SUBMITTED ARE ALL FOR A 6 UNIT BUILDING. IF YOU WISH TO
 USE THIS MASTER FOR BUILDINGS WITH OTHER THAN SIX UNITS
 YOU WILL NEED TO SUBMIT FLOOR PLANS, ROOF PLANS AND
 ELEVATIONS FOR EACH OF THE DIFFERENT CONFIGURATIONS.
 CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2012-09-06 Cont ID  
Sent By rmcdouga Date 2012-09-06 Time 16:22 Rev Time 0.00
Received By rmcdouga Date 2012-09-06 Time 16:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2012-09-04 Cont ID  
Sent By rmcdouga Date 2012-09-04 Time 11:32 Rev Time 0.00
Received By rmcdouga Date 2012-09-04 Time 11:32 Sent To  
Notes
2012-09-04 11:33:46COMMENTS FROM FIRST AND SECOND REVIEWS HAVE NOT BEEN
 ADDRESSED.
  
 2010 FBC & 2008 NEC
  
 DENIED BY ELECTRIC
  
 1) ON SHEET E-1 0 THROUGH E-1 3 NOTE 1 UNDER ELECTRICAL
 SPECIFICATIONS REFERENCES THE 2007 FBC W/2009
 REVISIONS. PLEASE UPDATE TO THE 2010 FBC. CITY
 AMENDMENTS 107.2.1
  
 2) THE NOTE BELOW THE LOAD CALCULATIONS ON THE
 ELECTRICAL PLAN SHEETS SPECIFIES THE 2005 NEC. PLEASE
 UPDATE TO THE 2008 NEC. CITY AMENDMENTS 107.2.1
  
 3) THE RECEPTACLE ON THE CEILING FOR THE OVERHEAD
 GARAGE DOOR OPENER IS REQUIRED TO BE GFCI PROTECTED PER
 2008 NEC ART.210.8 (A).
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2012-07-25 Cont ID  
Sent By rmcdouga Date 2012-07-25 Time 11:21 Rev Time 0.00
Received By rmcdouga Date 2012-07-25 Time 11:21 Sent To  
Notes
2012-07-25 11:22:35COMMENTS FROM FIRST REVIEW HAVE NOT BEEN ADDRESSED.
  
 2010 FBC & 2008 NEC
  
 DENIED BY ELECTRIC
  
 1) ON SHEET E-1 0 THROUGH E-1 3 NOTE 1 UNDER ELECTRICAL
 SPECIFICATIONS REFERENCES THE 2007 FBC W/2009
 REVISIONS. PLEASE UPDATE TO THE 2010 FBC. CITY
 AMENDMENTS 107.2.1
  
 2) THE NOTE BELOW THE LOAD CALCULATIONS ON THE
 ELECTRICAL PLAN SHEETS SPECIFIES THE 2005 NEC. PLEASE
 UPDATE TO THE 2008 NEC. CITY AMENDMENTS 107.2.1
  
 3) THE RECEPTACLE ON THE CEILING FOR THE OVERHEAD
 GARAGE DOOR OPENER IS REQUIRED TO BE GFCI PROTECTED PER
 2008 NEC ART.210.8 (A).
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-06-29 Cont ID  
Sent By rmcdouga Date 2012-06-29 Time 09:17 Rev Time 0.00
Received By rmcdouga Date 2012-06-29 Time 08:31 Sent To  
Notes
2012-06-29 09:08:202010 FBC & 2008 NEC
  
 DENIED BY ELECTRIC
  
 1) ON SHEET E-1 0 THROUGH E-1 3 NOTE 1 UNDER ELECTRICAL
 SPECIFICATIONS REFERENCES THE 2007 FBC W/2009
 REVISIONS. PLEASE UPDATE TO THE 2010 FBC. CITY
 AMENDMENTS 107.2.1
  
 2) THE NOTE BELOW THE LOAD CALCULATIONS ON THE
 ELECTRICAL PLAN SHEETS SPECIFIES THE 2005 NEC. PLEASE
 UPDATE TO THE 2008 NEC. CITY AMENDMENTS 107.2.1
  
 3) THE RECEPTACLE ON THE CEILING FOR THE OVERHEAD
 GARAGE DOOR OPENER IS REQUIRED TO BE GFCI PROTECTED PER
 2008 NEC ART.210.8 (A).
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date 2012-07-19 Cont ID  
Sent By wjolin Date 2012-07-19 Time 08:45 Rev Time 0.00
Received By wjolin Date 2012-07-19 Time 08:42 Sent To  
Notes
2012-07-19 08:45:34THE FLORIDA FIRE CODE INTERPRETATIONS COMMITTEE (FCIC)
 HAS RULED THAT FEE SIMPLE TOWNHOMES WITH A TWO-HOUR
 FIRE BARRIER BETWEEN UNITS ARE CONSIDERED TO BE A ONE
 OR TWO FAMILY DWELLING; THEREFORE, NO FIRE SPRINKLERS,
 FIRE PLAN REVIEW OR FIRE INSPECTIONS ARE REQUIRED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-06-23 Cont ID  
Sent By wjolin Date 2012-06-23 Time 17:15 Rev Time 0.00
Received By wjolin Date 2012-06-23 Time 17:00 Sent To  
Notes
2012-06-23 17:15:368321 OKEECHOBEE BOULEVARD
 PERMIT #12060388
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE FLORIDA
 FIRE PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF
 BOTH NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS.
  
 ALL NEW APARTMENTS AND TOWNHOUSES SHALL BE PROTECTED
 THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM PER SECTION 30.3.5.1 (NFPA 101 -
 FLORIDA EDITION 2009).
  
 FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION
 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES
 SEALED (BY DESIGN PROFESSIONAL) FIRE PROTECTION
 CONSTRUCTION DOCUMENTS FOR THE DESIGN OF 50 OR MORE
 AUTOMATIC FIRE SPRINKLERS.
  
 FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED
 SUPERVISING STATION IN ACCORDANCE WITH NFPA 72.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-06-29 Cont ID  
Sent By rmcdouga Date 2012-06-29 Time 13:46 Rev Time 0.00
Received By rmcdouga Date 2012-06-25 Time 11:02 Sent To  
Notes
2012-06-14 10:33:03MASTER PERMIT APPLICATION SENT TO RON FOR ELECTRONIC
 PLANS PROCESSING. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-07-25 Cont ID  
Sent By rmcdouga Date 2012-07-25 Time 11:45 Rev Time 0.00
Received By rmcdouga Date 2012-07-25 Time 11:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-06-28 Cont ID  
Sent By rmcdouga Date 2012-06-28 Time 10:34 Rev Time 0.00
Received By rmcdouga Date 2012-06-28 Time 10:34 Sent To  
Notes
2012-06-28 11:00:242010 FBC
  
 MECHANICAL DENIED
  
 1) THIS SUBMITTAL IS FOR A MASTER PLAN. THE ENERGY
 CALCULATIONS THAT WERE SUBMITTED UNDER ENERGY BUILDING
 7 RHEEM ARE WORSE CASE CALCULATIONS FOR SPECIFIC UNITS
 WITH ADDRESS AND LOT NUMBER. ONLY ONE ENERGY
 CALCULATION IS REQUIRED FOR EACH OF THE DIFFERENT TYPES
 OF UNITS THAT WILL BE IN THE DIFFERENT BUILDINGS. FOR
 EXAMPLE: INTERIOR WITH GARAGE LEFT AND GARAGE RIGHT AND
 END UNITS WITH GARAGE LEFT AND GARAGE RIGHT. 2010 FBC
 ENERGY CONSERVATION SECTION 405
  
 2) THE ENERGY CALCS UNDER END UNIT 2 AND END UNIT 1 ARE
 FOR INTERIOR UNITS. PLEASE CORRECT. 2010 FBC ENERGY
 CONSERVATION SECTION 405
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-06-28 Cont ID  
Sent By rmcdouga Date 2012-06-28 Time 09:12 Rev Time 0.00
Received By rmcdouga Date 2012-06-28 Time 09:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2013-01-28 Cont ID  
Sent By rregueir Date 2012-09-07 Time 15:38 Rev Time 0.00
Received By rregueir Date 2012-09-07 Time 15:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2012-09-07 Cont ID  
Sent By eschneid Date 2012-09-07 Time 12:56 Rev Time 3.00
Received By eschneid Date 2012-09-07 Time 12:56 Sent To  
Notes
2012-09-07 13:08:32PASSED W/PROVISOS
  
 1) THE SCREEN ENCLOSURES REQUIRE SEPARATE PERMITS AND
 ARE NOT APPROVED AS PART OF THE MASTER.
  
 2) THE INCLUSION OF THE PRIVACY WALL AS A DESIGN OPTION
 REQUIRES THE APPROVAL OF A MINOR PLANNED DEVELOPMENT
 AMENDMENT PRIOR TO IT BEING INCLUDED ON ANY BUILDING
 PERMITS. THE PRIVACY WALL IN NOT PART OF THIS APPROVAL.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 1 Status F Date 2012-06-26 Cont ID  
Sent By eschneid Date 2012-06-26 Time 11:40 Rev Time 1.00
Received By eschneid Date 2012-06-26 Time 11:40 Sent To  
Notes
2012-06-26 11:42:39FAILED
  
 1) THE EXTENDED PATIO PLANS WERE NOT PROVIDED WITH THE
 BUILDING MASTER.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.