Plan Review Details - Permit 12060319
Plan Review Stops For Permit 12060319
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-08-20 Cont ID  
Sent By lmartine Date 2012-08-20 Time 17:33 Rev Time 0.00
Received By lmartine Date 2012-08-20 Time 17:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-07-06 Cont ID  
Sent By jwitmer Date 2012-07-06 Time 11:04 Rev Time 0.00
Received By jwitmer Date 2012-07-06 Time 11:04 Sent To  
Notes
2012-07-06 11:18:59BUILDING PLAN REVIEW
 PERMIT: 12060319
 ADD: 7887 OLMPIA DR
 CONT: MCMAHOUN & ASSOCATES
 TEL: (561)313-7832
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A1 INDICATES THE PRESSURES BOTH POSITIVE AND
 NEGATIVE FOR CPMPONENTS AND CLADDING. THE PRODUCT
 APPROVALS SUBMITTED DO NOT MEET THE PRESSURES REQUIRED
 BY THE DESIGN PROFESSIONAL. NOTE THIS SSTRUCTURE IS
 REVIEWED BY THE 2010 FBC-R ONE AND TWO FAMILY
 RESIDENTIAL CODE, TABLE 301.2(2) PROVIDES THE MINIMUM
 PRESSURES THAT ARE REQUIRED BY CODE. THE DESIGNER OF
 RECORD DOES INDICATE PRESSURES THAT ARE DOUBLE WHAT IS
 REQUIRED BY CODE.
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) PLANS ARE DEFICIENT IN PROVIDING OCMPLIANCE WITH
 2010 FBC-R R302.5, R302.5.1 & TABLE R 302.6.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-06-14 Cont ID  
Sent By rlecky Date 2012-06-14 Time 09:22 Rev Time 0.00
Received By rlecky Date 2012-06-14 Time 07:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-08-20 Cont ID  
Sent By lmartine Date 2012-08-20 Time 17:33 Rev Time 0.00
Received By lmartine Date 2012-07-12 Time 06:34 Sent To  
Notes
2012-07-12 06:34:33R13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-07-09 Cont ID  
Sent By jgomez Date 2012-07-09 Time 16:54 Rev Time 0.00
Received By jgomez Date 2012-06-13 Time 09:14 Sent To  
Notes
2012-06-13 09:18:43B03

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-07-25 Cont ID  
Sent By jgomez Date 2012-07-25 Time 11:26 Rev Time 0.00
Received By jgomez Date 2012-07-25 Time 11:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-07-09 Cont ID  
Sent By jgomez Date 2012-07-09 Time 16:24 Rev Time 0.00
Received By jgomez Date 2012-07-09 Time 11:23 Sent To  
Notes
2012-07-09 16:43:37RESIDENTIAL (R3) REPAIRS MECHANICAL REVIEW COMMENTS.
 CODE: 2010 FBC
  
 1- RETURN AIR TRANSFER DUCT SHOWN FOR THE MASTER
 BEDROOM DOESN'T COMPLY WITH SEC. M1602.4 OF 2010
 FBC-RESIDENTIAL:
 A) TRANSFER DUCT SIZE NEEDS TO BE 1-1/2 TIMES THE CROSS
 SECTIONAL AREA OF THE SUPPLY DUCT ENTERING THE BEDROOM
 AND THE CLOSET.
  
 B) THE TRANSFER DUCT NEEDS TO BE LOCATED ON THE FAMILY
 AREA. THERE IS A DOOR IN THE MASTER BEDROOM VESTIBULE.
  
 2- PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY
 SEC. 403.6.1 OF 2010 FBC-ENERGY CONSERVATION.
  
 3- PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE PLANS. SEC. 107.2.1 CITY AMENDMENTS
 TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-06-19 Cont ID  
Sent By lwagner Date 2012-06-19 Time 14:18 Rev Time 0.00
Received By lwagner Date 2012-06-19 Time 13:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2012-07-18 Cont ID  
Sent By eschneid Date 2012-07-18 Time 11:25 Rev Time 0.50
Received By eschneid Date 2012-07-18 Time 11:05 Sent To  
Notes
2012-07-18 11:25:38EXISTING LANDSCAPE MEETS CODE.

Review Stop Z ZONING
Rev No 1 Status F Date 2012-06-25 Cont ID  
Sent By eschneid Date 2012-06-25 Time 17:42 Rev Time 0.50
Received By eschneid Date 2012-06-25 Time 16:04 Sent To  
Notes
2012-06-25 18:01:53FAILED
  
 PROVIDE RESPONSE IN WRITING.
  
 1) THE VALUE OF THE CONSTRUCTION ($120,000) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($186,000) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH THE RIVERWALK RPD
 LANDSCAPE GUIDELINES AND ALL APPLICABLE REGULATIONS
 FOUND IN ARTICLE XIV OF THE ZLDR. IF THE SITE CONFORMS
 TO THE RIVERWALK RPD LANDSCAPE GUIDELINES AND ARTICLE
 XIV, THEN TWO (2) COPIES OF A LANDSCAPE PLAN
 DEMONSTRATING COMPLIANCE SHALL BE INCLUDED WITH THE
 PERMIT RE-SUBMITTAL. IF THE SITE DOES NOT CONFORM TO
 THE RIVERWALK RPD LANDSCAPE GUIDELINES AND ARTICLE XIV,
 THEN PRIOR TO THE ZONING APPROVAL OF THIS PERMIT A
 SEPARATE LANDSCAPE PERMIT AND IRRIGATION PERMIT SHALL
 BE SUBMITTED SHOWING MATERIAL TO BRING THE SITE INTO
 CONFORMITY.
  
 THE RIVERWALK RPD LANDSCAPE GUIDELINES REQUIRE
 A. ONE SHADE TREE (12 FOOT MINIMUM HEIGHT) FOR EACH
 1,500 SQ. FT. OF PLATTED LOT AREA. TWO PALMS (12 FOOT
 MINIMUM HEIGHT) OR ONE MULTI-STEM SPECIMEN PALM MAY BE
 SUBSTITUTED FOR A SHADE TREE.
 B. ONE SHRUB (24 INCHES MINIMUM HEIGHT) FOR EACH 300
 SQ. FT. OF PLATTED LOT AREA.
 C. ONE ACCENT TREE OR PALM FOR EACH PLATTED LOT.
 D. FLORITAM SODDED LAWNS.
  
 2) PROVIDE THE SETBACK DIMENSION OF THE NEW A/C AND
 CURB FROM THE COMMON PROPERTY LINE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.