Plan Review Details - Permit 12060142
Plan Review Stops For Permit 12060142 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2012-08-09 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2012-08-09 |
Time |
11:33 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2012-08-09 |
Time |
11:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2012-06-27 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2012-06-27 |
Time |
17:16 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2012-06-27 |
Time |
17:16 |
Sent To |
|
|
Notes |
2012-06-27 17:21:23 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2010 | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | 1. REVISE PLAN TO INCLUDE WIND DESIGN CRITERIA, FBC | | 1603.4.1. SPECIFY TOTAL NUMBER OF FASTENERS PROPOSED; | | CALCULATIONS OR ENGINEERING MAY BE REQUIRED. | | | | 2. PROVIDE A DETAIL FOR PROPOSED SIGN CONSTRUCTION | | WHICH SHOWS ALL CONNECTIONS. SPEC OF 2X2 WITH 1X1 IN | | THE MIDDLE NOT CLEAR. | | | | 3. WHEN RESUBMITTING, PROVIDE TWO COMPLETE SETS OF | | PLANS FOR PERMIT ISSUANCE, FBC 107. | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2012-08-09 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2012-08-09 |
Time |
11:33 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2012-07-18 |
Time |
14:16 |
Sent To |
|
|
Notes |
2012-07-18 14:17:26 | INCOMING SENT TO ZONING BOX (ERIC SCHNIEDER) . JW |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2012-06-27 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2012-06-27 |
Time |
17:21 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2012-06-06 |
Time |
11:38 |
Sent To |
|
|
Notes |
2012-06-07 11:38:37 | SENT TO ZONING SHELF FOR REVIEW. JG. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2012-07-31 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2012-07-31 |
Time |
16:19 |
Rev Time |
0.50 |
Received By |
eschneid |
Date |
2012-07-31 |
Time |
16:19 |
Sent To |
B |
|
Notes |
2012-07-31 16:28:59 | SIGN IS MOUNTED ON A PROTION OF THE WALL MEASURING 30 | | FEET WIDE BY 25 FEET HIGH = 750 SQ. FT. | | SIGN ALLOWED FOR THIS SIZE AREA = 80.5 SQ. FT. | | APPROVED SIGN IN THIS AREA = 80 SQ. FT. | | | | THIS IS SIGN #2 ON THIS BUILDING. - IMECA LUMBER SIGN | | #2 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2012-06-18 |
|
|
Cont ID |
|
Sent By |
eschneid |
Date |
2012-06-18 |
Time |
12:35 |
Rev Time |
0.25 |
Received By |
eschneid |
Date |
2012-06-08 |
Time |
15:27 |
Sent To |
B |
|
Notes |
2012-06-18 13:03:37 | FAILED | | | | 1) THE LISTED FACADE DIMENSIONS WOULD NOT ALLOW THE | | PROPOSED SIGN TO BE CONSTRUCTED. 750 SQUARE FEET ONLY | | ALLOWS AN 80 SQ. FT. SIGN. PLEASE NOTE THAT THE FRONT | | FACADE IS WIDE THEN WHAT IS LISTED. | | | | 2) THE SIGN SIZE DIMENSIONS ARE NOT ACCURATELY | | PROVIDED. IN ORDER FOR THE PROPOSAL NOT TO COUNT AS 3 | | SEPARATE SIGNS, WHICH EXCEEDS THE AMOUNT OF ALLOWED | | SIGNS, THE AREA BETWEEN THE 3 SIGNS NEEDS TO BE | | PROVIDED IN THE OVERALL SIGN SIZE DIMENSION. | | | | 3) THE BUSINESS, "IMCEA LUMBER & HARDWARE" DOES NOT | | HAVE A BUSINESS TAX RECEIPT/CERTIFICATE OF USE. THIS IS | | REQUIRED PRIOR TO OPENING THE BUSINESS. | | | | 4) 2 COPIES OF THE PLANS ARE REQUIRED. | | | | 5) HOW FAR WILL THE FRAME EXTNED FROM THE WALL? | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | 2012-06-08 15:27:55 | GIVEN TO ES |
|
|
|