Plan Review Details - Permit 12060062
Plan Review Stops For Permit 12060062
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2012-08-03 Cont ID  
Sent By shill Date 2012-08-03 Time 19:25 Rev Time 0.00
Received By shill Date 2012-08-03 Time 19:25 Sent To FIRE
Notes
2012-08-03 19:29:20****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. OK.
  
 2. THE LIFE SAFETY PLAN DOES NOT SHOW WHICH OPENINGS
 YOU PROPOSE TO COVER. PLEASE CORRELATE WITH
 INSTALLATION SCHEDULE OR YOUR PREVIOUSLY SUBMITTED
 FLOOR PLAN. IT IS NOT CLEAR WHICH DOORS ARE TO BE
 BLOCKED, FBC 1003.6.
  
 REVISED PLAN SHOWS REQUIRED EXIT DOORS IN ASSEMBLY
 OCCUPANCY PROPOSED TO BE COVERED BY HURRICANE SHUTTERS.
 THERE IS NO PROVISION ALLOWING THIS USE OF SHUTTERS.
 PLEASE FEEL FREE TO CONTACT ME TO DISCUSS.
  
 IF YOU WISH TO PROVIDE RATIONALE FOR BLOCKING REQUIRED
 EXITS IN AN ASSEMBLY OCCUPANCY, PLEASE SUBMIT A LETTER
 ADDRESSED TO ROBERT BROWN, ABO (VIA EMAIL), AND IT WILL
 BE FORWARDED TO HIM.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-07-14 Cont ID  
Sent By shill Date 2012-07-14 Time 11:37 Rev Time 0.00
Received By shill Date 2012-07-14 Time 11:37 Sent To  
Notes
2012-07-14 11:40:34****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. THE INSTALLATION SCHEDULE WAS SUBMITTED BLANK EXCEPT
 FOR THE SHUTTER TO GLASS SEPARATION COLUMN. PLEASE
 PROVIDE ALL INFORMATION ON THE INSTALLATION SCHEDULE
 AND PROVIDE TWO SETS.
  
 2. THE LIFE SAFETY PLAN DOES NOT SHOW WHICH OPENINGS
 YOU PROPOSE TO COVER. PLEASE CORRELATE WITH
 INSTALLATION SCHEDULE OR YOUR PREVIOUSLY SUBMITTED
 FLOOR PLAN. IT IS NOT CLEAR WHICH DOORS ARE TO BE
 BLOCKED, FBC 1003.6.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-06-12 Cont ID  
Sent By shill Date 2012-06-12 Time 13:50 Rev Time 0.00
Received By shill Date 2012-06-12 Time 13:50 Sent To  
Notes
2012-06-12 13:52:22****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
  
 1. FBC RESIDENTIAL 301.1, SEE PRODUCT APPROVAL SECTION
 DETAILS FOR REQUIRED SHUTTER TO GLASS SEPARATION.
  
 2. REVISE PLAN TO SHOW TYPE OF OPENING; WINDOW OR DOOR.
 MORE INFORMATION MAY BE REQUIRED, SEE FBC 1003.6, MEANS
 OF EGRESS CONTINUITY.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-08-04 Cont ID  
Sent By wjolin Date 2012-08-04 Time 22:31 Rev Time 0.00
Received By wjolin Date 2012-08-04 Time 22:24 Sent To B
Notes
2012-08-04 22:31:25807 NORTH FLAGLER DRIVE
 PERMIT #12060062
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 HURRICANE PROTECTION DEVICES COVERING REQUIRED EXIT
 DOORS ARE NOT PERMITTED ON COMMERCIAL BUILDINGS PER
 LIFE SAFETY CODE SECTION 7.3.4.1.1 OF NFPA 101.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-08-06 Cont ID  
Sent By shill Date 2012-08-06 Time 08:29 Rev Time 0.00
Received By shill Date 2012-07-26 Time 15:05 Sent To  
Notes
2012-08-03 19:29:408/3/12 TO FIRE
  
2012-07-26 15:06:05SENT TO SAMANTHA'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-07-14 Cont ID  
Sent By shill Date 2012-07-14 Time 11:40 Rev Time 0.00
Received By shill Date 2012-07-09 Time 09:02 Sent To  
Notes
2012-07-09 09:03:05TO SH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-06-12 Cont ID  
Sent By shill Date 2012-06-12 Time 13:52 Rev Time 0.00
Received By shill Date 2012-06-05 Time 08:08 Sent To  
Notes
2012-06-05 08:09:09INCOMING SENT TO MISC BOX # 1. JW