Plan Review Details - Permit 12050811
Plan Review Stops For Permit 12050811
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-06-01 Cont ID  
Sent By jgomez Date 2012-06-01 Time 14:39 Rev Time 0.00
Received By jgomez Date 2012-06-01 Time 14:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-29 Cont ID  
Sent By jgomez Date 2012-05-29 Time 16:29 Rev Time 0.00
Received By jgomez Date 2012-05-29 Time 16:28 Sent To  
Notes
2012-05-29 16:42:11RE-ROOF BUILDING REVIEW COMMENTS.
 2010 FBC.
  
 1- ENGINEER TO PROVIDE THE RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7. FLAT ROOF BASE SHEET
 FASTENING INFORMATION SUBMITTED BY THE ENGINEER IS THE
 SAME AS SPECIFIED ON THE NOA 11-0425.07 SUBMITTED. THIS
 NAILING IS GOOD ONLY FOR ROOF ZONE #1. THAT'S WHY RAS
 117 CALCULATIONS FOR PERIMETER AND CORNER AREAS ARE
 REQUIRED TO PROVIDE THE ENHANCED NAIL FASTENING TO MEET
 THE DESIGN PRESSURES REQUIRED BY SEC. 1609 OF FBC.
  
 2- ENGINEER TO REVISE THE DESIGN PRESSURES. ACCORDING
 TO SEC. 1609.4.3 THIS BUILDING IS LOCATED ON EXPOSURE
 "C" NOT "B". REVISE AS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-06-01 Cont ID  
Sent By jgomez Date 2012-06-01 Time 14:29 Rev Time 0.00
Received By jgomez Date 2012-06-01 Time 14:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-29 Cont ID  
Sent By jgomez Date 2012-05-29 Time 16:29 Rev Time 0.00
Received By jgomez Date 2012-05-29 Time 16:29 Sent To  
Notes
***NONE***