Plan Review Details - Permit 12050711
Plan Review Stops For Permit 12050711
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-08-23 Cont ID  
Sent By jwitmer Date 2012-08-22 Time 15:33 Rev Time 0.00
Received By jwitmer Date 2012-08-22 Time 15:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-07-18 Cont ID  
Sent By jwitmer Date 2012-07-18 Time 16:03 Rev Time 0.00
Received By jwitmer Date 2012-07-18 Time 15:55 Sent To  
Notes
2012-07-18 16:34:11BUILDING PLAN REVIEW
 PERMIT: 12050711
 ADD: 1801 S FLAGLER DR # 204
 CONT: D L PORTER CONSTRUCTORS, INC (TBD)
 TEL: (941)650-3311
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 1)COMPLIED.
  
 2) COMPLIED.
  
 3A)2ND REQUEST, PLANS INDICATE NEW WOOD FLOORS, PLEASE
 PROVIDE COMPLIANCE WITH 2010 FBC-B 1207.3 STRUCTURE
 BORNE SOUND TRANSMITION. THE FLOORING/ CEILING ASSEMBLY
 SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF
 NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN
 ACCORDANCE WITH ASTM E 492 SUBMIT REPORT.
  
 3B) ASH 3/8 INCH HARDWOOD FLOORING PLEASE PROVIDE
 COMPLIANCE WITH SECTION 2010 FBC-B 603.1.2(2)
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
 OR
 805.1.3 INSULATING BOARDS. COMBUSTIBLE INSULATING
 BOARDS NOT MORE THAN 1/2 INCH (12.7 MM) THICK AND
 COVERED WITH APPROVED FINISH FLOORING ARE PERMITTED
 WHERE ATTACHED DIRECTLY TO A NONCOMBUSTIBLE FLOOR
 ASSEMBLY OR TO WOOD SUBFLOORING ATTACHED TO SLEEPERS AS
 PROVIDED FOR IN SECTION 805.1.1.
 OR
 804.3 TESTING AND IDENTIFICATION. INTERIOR FLOOR FINISH
 AND FLOOR COVERING MATERIALS SHALL BE TESTED BY AN
 APPROVED AGENCY IN ACCORDANCE WITH NFPA 253 AND
 IDENTIFIED BY A HANG TAG OR OTHER SUITABLE METHOD SO AS
 TO IDENTIFY THE MANUFACTURER OR SUPPLIER AND STYLE, AND
 SHALL INDICATE THE INTERIOR FLOOR FINISH OR FLOOR
 COVERING CLASSIFICATION ACCORDING TO SECTION 804.2.
 CARPET-TYPE FLOOR COVERINGS SHALL BE TESTED AS PROPOSED
 FOR USE, INCLUDING UNDERLAYMENT. TEST REPORTS
 CONFIRMING THE INFORMATION PROVIDED IN THE
 MANUFACTURER'S PRODUCT IDENTIFICATION SHALL BE
 FURNISHED TO THE BUILDING OFFICIAL UPON REQUEST.
  
 4-6) NOT PART OF SCOPE OF WORK.
  
 7) 2ND REQUEST, SHEET A1.01 NOTE # 8 INDICATES THE
 INSTALATION OF A NEW SOFFIT/ DROPPED CEILING BUT THERE
 IS NO FRAMING INFORMATION, TYPE OF FINISH ON THE
 SOFFIT, LIMITS OF DEFLECTION,
 2010 FBC-B 2506.2, TABLE 2506.2 STEEL STUDS NON-LOAD
 BEARING ASTM C 645.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-31 Cont ID  
Sent By jwitmer Date 2012-05-31 Time 08:32 Rev Time 0.00
Received By jwitmer Date 2012-05-31 Time 07:59 Sent To  
Notes
2012-05-31 08:30:24BUILDING PLAN REVIEW
 PERMIT: 12050711
 ADD: 1801 S FLAGLER DR # 204
 CONT: D L PORTER CONSTRUCTORS, INC (TBD)
 TEL: (941)650-3311
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS DO NOT IDENTIFY TO WHICH CODE THEY ARE
 DESIGNED. MACH 15, 2012 PLANS SUBMITTED FOR
 JURISDICTIONAL REVIEW WILL BE DESSIGNED TO THE 2012
 FBC- FL S 553.73.
  
 2) 2012 FLORIDA EXISTING BUILDING CODE, THE DESIGNER OF
 RECORD HAS NOT INDICATED WHICH COMPLIANCE METHOD THEY
 DESIGNED THIS PLAN TOO UNDER EXIST BLDG CODE 101.5
 COMPLIANCE METHOD.
  
 3A) PLANS INDICATE NEW WOOD FLOORS, PLEASE PROVIDE
 COMPLIANCE WITH 2010 FBC-B 1207.3 STRUCTURE BORNE SOUND
 TRANSMITION. THE FLOORING/ CEILING ASSEMBLY SHALL HAVE
 AN IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS
 THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE
 WITH ASTM E 492.
  
 3B) ASH 3/8 INCH HARDWOOD FLOORING PLEASE PROVIDE
 COMPLIANCE WITH SECTION 2010 FBC-B 603.1.2(2)
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 4) SHEET A1.01 NOTE # 5 INDICATES THE REPLACEMENT OF
 EXTERIOR SLIDING GLASS DOORS, PLEASE PROVIDE THE WIND
 DESIGN CRITERIA:
 1609.6.2 WIND DESIGN PROCEDURES
 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 4.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
 4.5) PREASURES, POSITIVE/ NEGATIVE
  
 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 6) COMPONENTS & CLADDING, FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
  
 7) SHEET A1.01 NOTE # 8 INDICATES THE INSTALATION OF A
 NEW SOFFIT/ DROPPED CEILING BUT THERE IS NO FRAMING
 INFORMATION, TYPE OF FINISH ON THE SOFFIT, LIMITS OF
 DEFLECTION,
 2010 FBC-B 2506.2, TABLE 2506.2 STEEL STUDS NON-LOAD
 BEARING ASTM C 645.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-08-23 Cont ID  
Sent By rlecky Date 2012-08-23 Time 16:37 Rev Time 0.00
Received By rlecky Date 2012-08-23 Time 15:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-05-31 Cont ID  
Sent By rlecky Date 2012-05-31 Time 11:07 Rev Time 0.00
Received By rlecky Date 2012-05-31 Time 11:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-07-19 Cont ID  
Sent By wjolin Date 2012-07-19 Time 10:26 Rev Time 0.00
Received By wjolin Date 2012-07-19 Time 10:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-06-05 Cont ID  
Sent By wjolin Date 2012-06-05 Time 14:41 Rev Time 0.00
Received By wjolin Date 2012-06-05 Time 14:24 Sent To P
Notes
2012-06-05 14:41:011801 SOUTH FLAGLER DRIVE - SUITE #204
 PERMIT #12050711
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SMOKE ALARMS SHALL BE INSTALLED IN EVERY SLEEPING AREA
 AND OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF BEDROOMS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-08-23 Cont ID  
Sent By rlecky Date 2012-08-23 Time 16:37 Rev Time 0.00
Received By rlecky Date 2012-08-22 Time 15:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-07-19 Cont ID  
Sent By wjolin Date 2012-07-19 Time 10:26 Rev Time 0.00
Received By wjolin Date 2012-07-17 Time 15:55 Sent To  
Notes
2012-07-17 15:55:41GAVE TO JIM

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-06-13 Cont ID  
Sent By lwagner Date 2012-06-13 Time 11:10 Rev Time 0.00
Received By lwagner Date 2012-05-23 Time 17:13 Sent To  
Notes
2012-05-23 17:14:06B--12

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-06-13 Cont ID  
Sent By lwagner Date 2012-06-13 Time 11:09 Rev Time 0.00
Received By lwagner Date 2012-06-13 Time 10:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2012-06-05 Cont ID  
Sent By eschneid Date 2012-06-05 Time 19:51 Rev Time 0.25
Received By eschneid Date 2012-06-05 Time 19:51 Sent To  
Notes
2012-06-05 19:52:00INTERIOR ONLY - LESS THAN 50% OF STRUCTURE