Plan Review Details - Permit 12050683
Plan Review Stops For Permit 12050683
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-05-24 Cont ID  
Sent By jgomez Date 2012-05-24 Time 16:09 Rev Time 0.00
Received By jgomez Date 2012-05-24 Time 16:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-23 Cont ID  
Sent By jgomez Date 2012-05-23 Time 10:59 Rev Time 0.00
Received By jgomez Date 2012-05-23 Time 10:46 Sent To  
Notes
2012-05-23 12:30:15RE-ROOF BUILDING REVIEW COMMENTS.
 2010 FBC.
  
 1- ACCORDING TO SEC. 1609.4.3 THIS BUILDING IS LOCATED
 ON EXPOSURE "D" NOT EXPOSURE "C". NEED TO REVISE THE
 DESIGN PRESSURES CALCULATIONS AND THE RECOMMENDED BASE
 SHEET ATTACHMENT PATTERN TO MEET THE NEW CALCULATED
 DESIGN PRESSURES.
  
 2- FLAT ROOF NOA 09-0820.11 SUBMITTED WAS SUPERSEDED BY
 MIAMI-DADE. NEED TO VISIT THE MIAMI-DADE WEBSITE AND
 DOWNLOAD CURRENT NOA. PROVIDE 2 COPIES. DCA RULE 9N-3.
 NOTE: SUBMIT THE NOA ALONE. FLORIDA PRODUCT APPROVAL
 FL735-R4 WILL NEED TO BE REVISED BY THE FLORIDA
 BUILDING COMMISSION ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-05-24 Cont ID  
Sent By jgomez Date 2012-05-24 Time 16:10 Rev Time 0.00
Received By jgomez Date 2012-05-24 Time 16:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-23 Cont ID  
Sent By jgomez Date 2012-05-23 Time 10:46 Rev Time 0.00
Received By jgomez Date 2012-05-23 Time 10:46 Sent To  
Notes
***NONE***