Plan Review Details - Permit 12050436
Plan Review Stops For Permit 12050436
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-06-01 Cont ID  
Sent By rferguso Date 2012-06-01 Time 15:38 Rev Time 0.00
Received By rferguso Date 2012-06-01 Time 15:36 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-05-16 Cont ID  
Sent By ddaniels Date 2012-05-16 Time 09:31 Rev Time 0.00
Received By ddaniels Date 2012-05-16 Time 09:29 Sent To M
Notes
2012-05-16 09:41:17FIRE DEPARTMENT REVIEW ***DENIED****
  
 ADDRESS: 315 SOUTH FLAGLER DRIVE
 PERMIT # 12050436
 CONTRACTOR: FRED MCGILVRAY INC.
 PHONE: 561 471-3349
  
  
 1. THE SCOPE OF WORK SHALL BE INDICATED ON PLANS.
 2. DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE
 FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA
 EDITION OF NFPA 1 AND NFPA 101.
 3. ALL DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY.
 4. FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
 5. FOR SYSTEM PRESSURES EXCEEDING 100 PSI, PENDENT
 SPRINKLERS SHALL BE PROTECTED FROM UPWARD MOVEMENT.
 HANGERS SHALL BE LOCATED WITHIN 12-INCHES OF THE DROP
 ELBOW. INDICATE THE HANGER TYPE OR METHOD TO BE USED
 FOR RESTRAINING UPWARD MOVEMENT.
 6. FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION
 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES
 SEALED FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE
 DESIGN OR ALTERATION OF 50 OR MORE AUTOMATIC FIRE
 SPRINKLERS.
  
  
  
 DERRICK L. DANIELS, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL
 (561) 805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-06-04 Cont ID  
Sent By hmoser Date 2012-06-04 Time 13:19 Rev Time 0.00
Received By hmoser Date 2012-06-01 Time 11:35 Sent To  
Notes
2012-06-01 11:35:10TO FIRE
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-17 Cont ID  
Sent By hmoser Date 2012-05-17 Time 14:15 Rev Time 0.00
Received By hmoser Date 2012-05-15 Time 13:53 Sent To  
Notes
2012-05-15 13:53:27TO FIRE
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-06-04 Cont ID  
Sent By hmoser Date 2012-06-04 Time 13:19 Rev Time 0.00
Received By hmoser Date 2012-06-04 Time 13:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-05-17 Cont ID  
Sent By hmoser Date 2012-05-17 Time 13:33 Rev Time 0.00
Received By hmoser Date 2012-05-17 Time 14:05 Sent To  
Notes
2012-05-17 14:15:18ON THE 1ST PAGE OF THE PLANS IT SHOWS 15 NEW PIPE AND
 SPRINKLERS
 AND 16 RELOCATED PIPE AND SPRINKLERS . PAGE 3 OF PLANS
 SHOW A LOT MORE.
 PLEASE CLARIFY.
 REFER TO SECTION 633.021 (S) (E) FLORIDA STATUTES 49
 HEADS OR MORE PLANS
 MUST BE ENGINEERED.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]