Plan Review Details - Permit 12050415
Plan Review Stops For Permit 12050415
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-06-01 Cont ID  
Sent By jwitmer Date 2012-06-01 Time 13:29 Rev Time 0.00
Received By jwitmer Date 2012-06-01 Time 13:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-05-18 Cont ID  
Sent By rlecky Date 2012-05-18 Time 16:42 Rev Time 0.00
Received By rlecky Date 2012-05-18 Time 10:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-05-29 Cont ID  
Sent By wjolin Date 2012-05-29 Time 13:26 Rev Time 0.00
Received By wjolin Date 2012-05-29 Time 13:21 Sent To  
Notes
2012-05-29 13:25:59303 BANYAN BOULEVARD
 TRACKING #12050415
 PERMIT #12020313
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET E1.1: PROVIDE BI-DIRECTIONAL CHEVRONS ON EXIT
 SIGN AT END OF CORRIDOR #002.
  
 SHEET E1.1: THE FIRE ALARM NOTIFICATION APPLIANCE IN
 CORRIDOR #002 IS OBSTRUCTED BY THE WING WALL.
  
 SHEET E1.1: ONLY ONE FIRE ALARM NOTIFICATION APPLIANCE
 WILL NOT ADEQUATELY COVER THE ENTIRE CORRIDOR #001.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-06-01 Cont ID  
Sent By jwitmer Date 2012-06-01 Time 13:30 Rev Time 0.00
Received By jwitmer Date 2012-05-14 Time 14:28 Sent To  
Notes
2012-05-15 14:28:57B--23

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-05-31 Cont ID  
Sent By hmoser Date 2012-05-31 Time 15:24 Rev Time 0.00
Received By hmoser Date 2012-05-31 Time 14:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-05-16 Cont ID  
Sent By lwagner Date 2012-05-16 Time 12:52 Rev Time 0.00
Received By lwagner Date 2012-05-16 Time 12:23 Sent To  
Notes
***NONE***