Plan Review Details - Permit 12050338
Plan Review Stops For Permit 12050338
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-14 Cont ID  
Sent By jwitmer Date 2012-05-14 Time 12:12 Rev Time 0.00
Received By jwitmer Date 2012-05-14 Time 11:28 Sent To  
Notes
2012-05-14 12:54:16BUILDING PLAN REVIEW
 PERMIT: 12010646
 REVISION: 12050338
 ADD: 315 S FLAGLER DR.
 CONT: WHITING-TURNER CO
 TEL: (954)275-0643
  
 2007 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THRESHOLD BUILDING: (3) SOILS REPORTS REQUIRED.
 ORIGINAL SIGNED AND SEALED REPORTS.
  
 NOTE: BUILDING IS NOT LOCATED IN A FLOOD ZONE A FLOOD
 ZONE BUT IS LOCATED IN A "C" FLOOD ZONE NO FLOOD ZONE
 CERTIFICATE IS REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2012-05-29 Cont ID  
Sent By jwitmer Date 2012-05-29 Time 13:18 Rev Time 0.00
Received By jwitmer Date 2012-05-23 Time 16:03 Sent To  
Notes
2012-05-29 13:20:08REVISION: SIGNED & SEALED ORIGINAL SOILS REPORTS FROM
 DUNKLEBERGER ENGINEERING & TESTING. JW
2012-05-23 16:04:05TO JW DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-14 Cont ID  
Sent By jwitmer Date 2012-05-14 Time 12:12 Rev Time 0.00
Received By jwitmer Date 2012-05-10 Time 08:54 Sent To  
Notes
2012-05-11 08:55:36GAVE TO JIM