Plan Review Details - Permit 12050072
Plan Review Stops For Permit 12050072
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-06-22 Cont ID  
Sent By shill Date 2012-06-22 Time 15:32 Rev Time 0.00
Received By shill Date 2012-06-22 Time 15:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-08 Cont ID  
Sent By shill Date 2012-05-08 Time 07:43 Rev Time 0.00
Received By shill Date 2012-05-07 Time 16:53 Sent To  
Notes
2012-05-08 07:46:05****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. SHEET T, PROJECT DATA, STATES THAT THE 2ND FLOOR IS
 A SINGLE TENANT. OUR RECORDS SHOW THAT THERE ARE MORE
 THAN ONE TENANT ON THIS FLOOR, PLEASE EITHER EXPLAIN OR
 REVISE NOTE, FBC 709.1(6).
  
 2. GOVERNING CODE CHANGED ON 3/15/2012 TO FBC 2010;
 PLEASE REVISE PROJECT DATA AND REFERENCE STANDARDS AND
 ANY OTHER NOTES AS APPLICABLE; FS 553.73.
  
 3. A2, TENANT SEPARATION WALL DOES NOT APPEAR CONTINOUS
 AT OFFICE 101, SHOWS FIRE RATED WALLS TERMINATING AT
 WHAT APPEARS TO BE A COLUMN. PROVIDE A DETAIL TO SHOW
 HOW FIRE RESISTANCE WILL BE MAINTAINED AT THIS
 LOCATION, FBC 709.1(6).
  
 4. SPECIFY HEAD OF WALL DETAIL FOR THE NEW FIRE RATED
 WALLS, FBC 709.4.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-05-07 Cont ID  
Sent By rlecky Date 2012-05-07 Time 10:09 Rev Time 0.00
Received By rlecky Date 2012-05-07 Time 10:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-06-15 Cont ID  
Sent By wjolin Date 2012-06-15 Time 10:58 Rev Time 0.00
Received By wjolin Date 2012-06-15 Time 10:41 Sent To  
Notes
2012-06-15 10:50:52701 NORTHPOINT PARKWAY - SUITE #209
 PERMIT #12050072
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 EACH SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-05-10 Cont ID  
Sent By ddaniels Date 2012-05-10 Time 12:23 Rev Time 0.00
Received By ddaniels Date 2012-05-10 Time 12:23 Sent To  
Notes
2012-05-10 12:33:35FIRE DEPARTMENT REVIEW ** DENIED**
  
 1. THE SCOPE OF WORK SHALL BE INDICATED ON PLANS.
 2. DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE
 FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA
 EDITION OF NFPA 1 AND NFPA 101.
 3. ALL DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY.
 4. FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
 5.PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
  
  
  
 DERRICK L. DANIELS, BATTALION CHIEF / FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL
 (561) 805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-06-25 Cont ID  
Sent By shill Date 2012-06-25 Time 16:41 Rev Time 0.00
Received By shill Date 2012-06-12 Time 08:40 Sent To  
Notes
2012-06-12 08:47:24B17
2012-06-12 08:44:57B17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-15 Cont ID  
Sent By lmartine Date 2012-05-10 Time 16:55 Rev Time 0.00
Received By lmartine Date 2012-05-02 Time 11:20 Sent To  
Notes
2012-05-03 11:20:51B04

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-06-25 Cont ID  
Sent By hmoser Date 2012-06-25 Time 16:41 Rev Time 0.00
Received By hmoser Date 2012-06-25 Time 16:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-05-04 Cont ID  
Sent By hmoser Date 2012-05-04 Time 09:06 Rev Time 0.00
Received By hmoser Date 2012-05-04 Time 08:57 Sent To  
Notes
2012-05-04 09:06:33PLANS DENIED
 REFER TO SECTION 607.5.1 FIRE WALLS.2010 FBC (M)
 MISSING FIRE DAMPERS IN EXISTING 1 HR. RATED WALL WHERE
 EXISTING DUCT PENETRATES WALLS.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2012-05-08 Cont ID  
Sent By lwagner Date 2012-05-08 Time 10:47 Rev Time 0.00
Received By lwagner Date 2012-05-08 Time 10:42 Sent To  
Notes
2012-05-08 10:47:38NO PLUMBING SHOWN AT THIS TIME.

Review Stop Z ZONING
Rev No 1 Status N Date 2012-05-04 Cont ID  
Sent By eschneid Date 2012-05-04 Time 15:21 Rev Time 0.25
Received By eschneid Date 2012-05-04 Time 15:21 Sent To  
Notes
2012-05-04 15:22:04INTERIOR WORK ONLY - VALUE LESS THAN 50%.