Plan Review Details - Permit 12050030
Plan Review Stops For Permit 12050030
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-05-02 Cont ID  
Sent By ddaniels Date 2012-05-02 Time 11:40 Rev Time 0.00
Received By ddaniels Date 2012-05-02 Time 11:35 Sent To  
Notes
2012-05-02 11:45:18PLANS REVIEWED BY FIRE **APPROVED**
  
 1.) PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 2.) TENT SHALL BE OF THE OPEN AREA/NO SIDES TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 3.) POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS. PROVIDE NONCOMBUSTIBLE FLAME CERTIFICATE FOR
 THE CANOPY MATERIAL.
  
  
  
 DERRICK L. DANIELS, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-02 Cont ID  
Sent By ddaniels Date 2012-05-02 Time 11:40 Rev Time 0.00
Received By ddaniels Date 2012-05-01 Time 14:30 Sent To  
Notes
2012-05-01 14:30:45SENT TO FIRE TEMPORARY TENT SHELF FOR REVIEW. JG.