2012-05-04 15:19:26 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2010 |
| FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| |
| 1. STEEL SUBSTRATE IS NOT AN OPTION IN THE PRODUCT |
| APPROVAL, PLEASE PROVIDE SITE SPECIFIC ENGINEERING. |
| |
| 2. A 1" EDGE DISTANCE IS NOT PERMITTED FOR CONCRETE. |
| ALTHOUGH IT'S A TRAPPED OPENING, EDGE DISTANCE MUST BE |
| MAINTAINED SO THE CONCRETE SUBSTRATE IS NOT |
| COMPROMISED, SEE SHEET 7. A 1 3/4" MINIMUM EDGE |
| DISTANCE IS REQUIRED, SEE "FACTOR" TABLE ON SHEET 13. |
| APPLICABLE FACTOR TO BE APPLIED TO ANCHOR SPACING IN |
| THE CHART. |
| |
| 3. WHEN RESUBMITTING, PLEASE PROVIDE TWO SETS OF THE |
| INSTALLATION SCHEDULE. FAILURE TO PROVIDE TWO SETS MAY |
| RESULT IN PERMIT ISSUANCE DELAYS DUE TO TIME |
| CONSTRAINTS. A PHOTOCOPY MACHINE IS IN THE LOBBY FOR |
| YOUR CONVENIENCE. |
| |
| 4. PLEASE ADVISE AS TO WHICH OPTION IS TO BE USED, |
| SYMMETRICAL CENTERMATES OR OPPOSING CENTERMATES, AND |
| REVISE SHUTTER TO GLASS SEPARATION IF NECESSARY, SEE |
| SHEET 11. |
| |
| 5. PLEASE ADVISE AS TO HOW YOU HAVE DETERMINED DESIGN |
| PRESSURES. THE BUILDING MRH APPEARS TO BE HIGHER THAN |
| 40' AS IT IS FOUR STORIES, PITCHED ROOF. 81.2/-108.7 |
| ULT = 48.72/-65.22 ASD. PRESSURES PROPOSED RANGE FROM |
| -47.99 TO 50.4, APPEAR TOO LOW BASED ON ENGINEERING |
| PROVIDED. |
| |
| |