Plan Review Details - Permit 12040595
Plan Review Stops For Permit 12040595
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-05-16 Cont ID  
Sent By shill Date 2012-05-16 Time 13:26 Rev Time 0.00
Received By shill Date 2012-05-16 Time 07:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-04-26 Cont ID  
Sent By shill Date 2012-04-26 Time 07:20 Rev Time 0.00
Received By shill Date 2012-04-25 Time 12:40 Sent To  
Notes
2012-04-26 07:41:20****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. SEE FBC 2010 EXISTING BUILDING 404, RECONFIGURATION
 OR ADDITIONAL OF A DOOR IS A LEVEL 2 ALTERATION, PLEASE
 REVISE SHEET A1.
  
 2. FOR THE ENTRY DOOR AND WALL, PLEASE NOTE WHETHER OR
 NOT THIS IS A FIRE RATED WALL AND DOOR, AND IF NOT,
 SHOW EXCEPTION TO FBC 708.14.1, FBC EXISTING BUILDING
 701.3.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-04-30 Cont ID  
Sent By rlecky Date 2012-04-30 Time 08:25 Rev Time 0.00
Received By rlecky Date 2012-04-30 Time 08:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-05-15 Cont ID  
Sent By ddaniels Date 2012-05-15 Time 15:21 Rev Time 0.00
Received By ddaniels Date 2012-05-15 Time 15:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-05-16 Cont ID  
Sent By hmoser Date 2012-05-16 Time 14:38 Rev Time 0.00
Received By hmoser Date 2012-05-08 Time 18:45 Sent To  
Notes
2012-05-08 18:45:50CONTRACTOR RESUBMITTED BEFORE FIRE REVIEW
 ADDED RESUBMITTED PLAN TO PACKAGE
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-16 Cont ID  
Sent By hmoser Date 2012-05-16 Time 14:38 Rev Time 0.00
Received By hmoser Date 2012-04-24 Time 16:42 Sent To  
Notes
2012-04-24 16:43:10EXPEDITED
 B--19

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-05-16 Cont ID  
Sent By hmoser Date 2012-05-16 Time 14:38 Rev Time 0.00
Received By hmoser Date 2012-05-16 Time 14:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-04-26 Cont ID  
Sent By hmoser Date 2012-04-26 Time 15:15 Rev Time 0.00
Received By hmoser Date 2012-04-26 Time 15:06 Sent To  
Notes
2012-04-26 15:15:36PLANS DENIED
 REFER TO SECTION 403.6.1 EQUIPMENT SIZING 2010 FLORIDA
 ENERGY CODE.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-05-02 Cont ID  
Sent By lwagner Date 2012-05-02 Time 13:59 Rev Time 0.00
Received By lwagner Date 2012-05-02 Time 13:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2012-05-01 Cont ID  
Sent By aaponte Date 2012-05-01 Time 10:45 Rev Time 0.00
Received By aaponte Date 2012-05-01 Time 10:44 Sent To  
Notes
2012-05-01 10:45:19INTERIOR REMODEL OF RESIDENTIAL UNIT.