Plan Review Details - Permit 12040588
Plan Review Stops For Permit 12040588
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2012-10-10 Cont ID  
Sent By jwitmer Date 2012-10-10 Time 13:41 Rev Time 0.00
Received By jwitmer Date 2012-10-10 Time 13:40 Sent To  
Notes
2012-10-10 14:01:38BUILDING PLAN REVIEW
 PERMIT: 12040588
 ADD:2700 BROADWAY
 CONT: PKS CONSTRUCTION
 TEL: (561)704-2394
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 4TH REVIEW
 OCT .10/2012
 ENGINEER JOHN HOLT PE # 15252
  
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 A SEPERATE ROOFING PERMIT IS REQUIRED. PRODUCT
 APPROVALS WERE GIVEN BACK TO THE CGC TO BE SUBMITTED BY
 ROOFING CONTRACTOR.
 PRODUCT APPROVALS WERE SUBMITTED:
 1) SANTAFE TILE, MISSION BARREL ROOFING TILE NOA
 07-0626.04.
 RUBBER STAMP REVIEWED AND APPROVED BY JOHN HOLT PE BUT
 NO SIGNATURE
 TYPE OF ATTACHMENT FOR ROOF TILE NOT IDENTIFIED
  
 2) POLYGLASS SELF-ADHERED ROOF SYSTEM OVER WOOD DECK
 NOA 11-0425.07
 SUB-SYSTEMS NOT IDENTIFIED AS TO WHICH SUB-SYSTEM WOULD
 BE INSTALLED, ALL SUB-SYSTEMS WITH LIMITATION # 7
 WILL NEED ENHANCED FASTENING RAS 117 SCHEDULE BY EITHER
 AN ENGINEER, ARCHITECT
  
 3) FLAT DECK BASE SHEET NAILING SCHEDULE SUBMITTED NO
 DESIGN PROFESSIONAL SIGNATURE NOR SEAL AS PER NOA
 REQUIREMENT LIMITATION # 7.
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2012-09-14 Cont ID  
Sent By jwitmer Date 2012-09-14 Time 16:15 Rev Time 0.00
Received By jwitmer Date 2012-09-14 Time 15:46 Sent To  
Notes
2012-09-14 16:12:47BUILDING PLAN REVIEW
 PERMIT: 12040588
 ADD:2700 BROADWAY
 CONT: PKS CONSTRUCTION
 TEL: (561)704-2394
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 3RD REVIEW
 SEPT. 14/2012
 ENGINEER JOHN HOLT PE # 15252
  
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-1:
 1A) SHEET A-1 & A-2 SIGNED AND SEALED DATED 8/29/12,
 PLANS ARE DESIGNED UNDER THE 2007 FBC-B. MARCH 15/ 2012
 IS THE ADOPTION DATE STATEWIDE FOR THE 2010 FBC-B,
 PLANS SUBMITTED ON THAT DATE AND LATER FOR FIRST REVIEW
 ARE TO BE DESIGNED TO THE 2010 FBC. SINCE THIS IS AN
 ADDITION THE PLANS WILL ALSO BE REVIEWED TO THE 2010
 EXISTING BUILDING CODE CHAPTER 10 FOR ADDITIONS AND
 CHAPTER 11 FOR HISTORIC BUILDINGS.
  
  
 1B) 2010 EXIST BUILDING CODE 1002.2 PLEASE PROVIDE CODE
 ANALYSIS FOR BUILDING, MINIMUM BUILDING TYPE, SQUARE
 FOOTAGE OF EXISTING BUILDING, SPRINKLERED OR NOT AND
 TYPE OF OCCUPANCY FOR AREA LIMITATIONS. 106.3.5.1.1*
 MINIMUM COMMERCIAL PLAN REVIEW CRITERIA.
 THE PROPERTY APPRAISERS OFFICE AND CITY LIST THIS
 BUILDING AS A RESTROOM (I-1). PLANS INDICATE THIS AS A
 A-2 OCCUPANCY?
 SHEET A1 ALSO INDICATES THE MINIMUM BLDG TYPE AS A TYPE
 5 CLASS 1 THIS IS NOT TERMINOLOGY FOUND IN TABLE 503
 EITHER VA OR VB.
  
 1C) SHEET A-1 INDICATES THE PLANS ARE DESIGNED TO THE
 2010 FBC FOR WIND DESIGN BUT STILL REFERENECES ASCE
 7-05 AND A IMPORTANCE FACTOR OF 1.15 WHAT IS REQUIRING
 THE IMPORTANCE FACTOR OF 1.15, THE 2010 WIND TABLE HAVE
 THIS DESIGNED INTO WHICH WIND SPEED MAP THAT IS USED,
 THE 170 MPH WIND ZONE MAP WILL BE A BUILDING CATEGORY
 OF II, THE THE EXPOSURE ZONE AND HEIGHT FACTOR ARE NOT
 PROVIDED WITHIN THE WIND DESIGN CRITERIA 2010 FBC-B T
 1609.7.(2). PLEASE SHOW PRESSURES IN VULT.
 OLD COMMENT: WIND DESIGN CRITERIA IS FOR THE 2007 FBC
 NOT THE 2010 FBC-B PLEASE REVIEW 1609.1.1.
  
 2-3) COMPLIED.
  
 NEW COMMENTS:
  
 4) PRODUCT APPROVALS SUBMITTED POLYGLASS NOA
 11-0425.07, & GAF MODIFIED NOA 11-0425.07 ARE STAMPED
 REVIEWED BY LUIS LOPEZ NOT REVIEWED BY PE JOHN HOLT,
 NEITHER HAS THE PRODUCT APPROVAL SANTAFE TILE, MISSION
 BARREL ROOFING TILE NOA 07-0626.04.
  
 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-07-24 Cont ID  
Sent By jwitmer Date 2012-07-24 Time 11:32 Rev Time 0.00
Received By jwitmer Date 2012-07-24 Time 11:32 Sent To  
Notes
2012-07-24 11:34:56BUILDING PLAN REVIEW
 PERMIT: 12040588
 ADD:2700 BROADWAY
 CONT: PKS CONSTRUCTION
 TEL: (561)704-2394
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2ND REVIEW
  
 ENGINEER LUIS LOPEZ PE # 59805 VOLUNTARY RELINGUISHMENT
 4/27/2012. JW
  
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-1:
 1A) SHEET A-1 & A-2 SIGNED AND SEALED DATED 4/19/2012,
 PLANS ARE DESIGNED UNDER THE 2007 FBC-B. MARCH 15/ 2012
 IS THE ADOPTION DATE STATEWIDE FOR THE 2010 FBC-B,
 PLANS SUBMITTED ON THAT DATE AND LATER FOR FIRST REVIEW
 ARE TO BE DESIGNED TO THE 2010 FBC. SINCE THIS IS AN
 ADDITION THE PLANS WILL ALSO BE REVIEWED TO THE 2010
 EXISTING BUILDING CODE CHAPTER 10 FOR ADDITIONS AND
 CHAPTER 11 FOR HISTORIC BUILDINGS.
  
 1B) 2010 EXIST BUILDING CODE 1002.2 PLEASE PROVIDE CODE
 ANALYSIS FOR BUILDING, MINIMUM BUILDING TYPE, SQUARE
 FOOTAGE OF EXISTING BUILDING, SPRINKLERED OR NOT AND
 TYPE OF OCCUPANCY FOR AREA LIMITATIONS. 106.3.5.1.1*
 MINIMUM COMMERCIAL PLAN REVIEW CRITERIA.
  
 1C) WIND DESIGN CRITERIA IS FOR THE 2007 FBC NOT THE
 2010 FBC-B PLEASE REVIEW 1609.1.1.
  
 2) FRONT PORCH ADDITION;
 2A) SHEET A2 ROOF FRAMING PLAN FAILS TO IDENTIFY BOTH
 B-1 CARRYING BEAM ATTACHMENTS TO THE EXISTING
 STRUCTURE, PART OF THE MWFRS (MAIN WIND FORCE RESITING
 SYSTEM) PLEASE PROVIDE TYPE OF BUCKET AND ATTACHMENT.
 106.1.2* ADTIONAL INFORMATION REQUIRED /
 106.3.5.1.1.(8)*.
  
 2B) SHEET A1 FRONT PORCH DETAIL INDICATES THE ROOF
 JOIST ANCHORING TO BEAM B1 BUT THIS DETAIL NOR THE
 DETAIL ON A2 PROVIDE THE CANTILVERED ROOF JOIST
 ATTACHMENT TO BEAM B-1 NOR THE COMMON JOIST THEY ATTACH
 TOO? PART OF THE MWFRS, 106.3.5.1.1(8)*.
  
 2C) THE SAME DETAIL INDICATES THE ATTACHMENT OF LEDGER
 TO THE WALL WITH 1/2" BOLTS @ 4'-0" O.C.? PLANS LACK
 THE TYPE OF ANCHOR TO BE INSTALLED, LENGTH OF ANCHOR,
 IS THIS ANCHOR GOING TO BE INSTALLED INTO A CONCRETE
 BEAM, FILLED MASONRY BLOCK BEAM OR EMPTY CONCRETE BLOCK
 UNITS.
  
 2D) SHEET A-1 FRONT PORCH DETAIL INDICATES THE ROOFING
 MATERIALS TO BE MODIFIED PEEL AND STICK ROOFING WHERE
 AS THE ACTUAL PRODUCT APPROVAL IS A GAF RUBEROID
 MODIFIED BITUMEN ROOF SYSTEM FOR ROOF DECKS WHICH IS
 CORRECT? IF THE PEEL AND STICK NOTE IS DELETED AND THIS
 APPROVAL WILL BE INSTALLED THEN PLEASE IDENTIFY WHICH
 OF THE SUB-SYSTEMS WILL BE APPLIED, PLEASE NOTE THAT IN
 ROOF ZONES 2 & 3 ENHANCED FASTENING WILL BE REQUIRED
 WHEN LIMITATION NOTE # 7 APPEARS LIMITATION NOTE # 9
 DOES NOT ALLOW FOR ENHANCED FASTENING.
  
 3) BACK PORCH ADDITION, ALL OF THE CONDITIONS LISTED
 ABOVE ARE THE SAME CONDITIONS FOR THE BACK PORCH
 ADDITION.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-22 Cont ID  
Sent By jwitmer Date 2012-05-22 Time 10:10 Rev Time 0.00
Received By jwitmer Date 2012-05-22 Time 09:56 Sent To  
Notes
2012-05-22 10:59:31BUILDING PLAN REVIEW
 PERMIT: 12040588
 ADD:2700 BROADWAY
 CONT: PKS CONSTRUCTION
 TEL: (561)704-2394
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET A-1:
 1A) SHEET A-1 & A-2 SIGNED AND SEALED DATED 4/19/2012,
 PLANS ARE DESIGNED UNDER THE 2007 FBC-B. MARCH 15/ 2012
 IS THE ADOPTION DATE STATEWIDE FOR THE 2010 FBC-B,
 PLANS SUBMITTED ON THAT DATE AND LATER FOR FIRST REVIEW
 ARE TO BE DESIGNED TO THE 2010 FBC. SINCE THIS IS AN
 ADDITION THE PLANS WILL ALSO BE REVIEWED TO THE 2010
 EXISTING BUILDING CODE CHAPTER 10 FOR ADDITIONS AND
 CHAPTER 11 FOR HISTORIC BUILDINGS.
  
 1B) 2010 EXIST BUILDING CODE 1002.2 PLEASE PROVIDE CODE
 ANALYSIS FOR BUILDING, MINIMUM BUILDING TYPE, SQUARE
 FOOTAGE OF EXISTING BUILDING, SPRINKLERED OR NOT AND
 TYPE OF OCCUPANCY FOR AREA LIMITATIONS. 106.3.5.1.1*
 MINIMUM COMMERCIAL PLAN REVIEW CRITERIA.
  
 1C) WIND DESIGN CRITERIA IS FOR THE 2007 FBC NOT THE
 2010 FBC-B PLEASE REVIEW 1609.1.1.
  
 2) FRONT PORCH ADDITION;
 2A) SHEET A2 ROOF FRAMING PLAN FAILS TO IDENTIFY BOTH
 B-1 CARRYING BEAM ATTACHMENTS TO THE EXISTING
 STRUCTURE, PART OF THE MWFRS (MAIN WIND FORCE RESITING
 SYSTEM) PLEASE PROVIDE TYPE OF BUCKET AND ATTACHMENT.
 106.1.2* ADTIONAL INFORMATION REQUIRED /
 106.3.5.1.1.(8)*.
  
 2B) SHEET A1 FRONT PORCH DETAIL INDICATES THE ROOF
 JOIST ANCHORING TO BEAM B1 BUT THIS DETAIL NOR THE
 DETAIL ON A2 PROVIDE THE CANTILVERED ROOF JOIST
 ATTACHMENT TO BEAM B-1 NOR THE COMMON JOIST THEY ATTACH
 TOO? PART OF THE MWFRS, 106.3.5.1.1(8)*.
  
 2C) THE SAME DETAIL INDICATES THE ATTACHMENT OF LEDGER
 TO THE WALL WITH 1/2" BOLTS @ 4'-0" O.C.? PLANS LACK
 THE TYPE OF ANCHOR TO BE INSTALLED, LENGTH OF ANCHOR,
 IS THIS ANCHOR GOING TO BE INSTALLED INTO A CONCRETE
 BEAM, FILLED MASONRY BLOCK BEAM OR EMPTY CONCRETE BLOCK
 UNITS.
  
 2D) SHEET A-1 FRONT PORCH DETAIL INDICATES THE ROOFING
 MATERIALS TO BE MODIFIED PEEL AND STICK ROOFING WHERE
 AS THE ACTUAL PRODUCT APPROVAL IS A GAF RUBEROID
 MODIFIED BITUMEN ROOF SYSTEM FOR ROOF DECKS WHICH IS
 CORRECT? IF THE PEEL AND STICK NOTE IS DELETED AND THIS
 APPROVAL WILL BE INSTALLED THEN PLEASE IDENTIFY WHICH
 OF THE SUB-SYSTEMS WILL BE APPLIED, PLEASE NOTE THAT IN
 ROOF ZONES 2 & 3 ENHANCED FASTENING WILL BE REQUIRED
 WHEN LIMITATION NOTE # 7 APPEARS LIMITATION NOTE # 9
 DOES NOT ALLOW FOR ENHANCED FASTENING.
  
 3) BACK PORCH ADDITION, ALL OF THE CONDITIONS LISTED
 ABOVE ARE THE SAME CONDITIONS FOR THE BACK PORCH
 ADDITION.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-04-30 Cont ID  
Sent By wjolin Date 2012-04-30 Time 12:52 Rev Time 0.00
Received By wjolin Date 2012-04-30 Time 11:52 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2012-09-10 Cont ID  
Sent By fmittner Date 2012-09-10 Time 11:06 Rev Time 0.00
Received By fmittner Date 2012-09-10 Time 11:06 Sent To  
Notes
2012-09-10 11:06:37MUST USE 6X6 COLUMN FOR SUPPORT

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2012-07-20 Cont ID  
Sent By fmittner Date 2012-07-20 Time 12:29 Rev Time 0.00
Received By fmittner Date 2012-07-20 Time 12:29 Sent To  
Notes
2012-07-20 12:30:31APPLICATION REQUIRES FILING OF A COA (CERTIFICATE OF
 APPROPRIATENESS). ADDTION DOES NOT APPEAR TO BE
 ARCHITECTURALLY COMPATIBLE. SAME CONCERNS AS FROM FIRST
 SUBMITTAL. QUESTIONS CONTACT FRIEDERIKE AT 822-1457.

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2012-05-10 Cont ID  
Sent By fmittner Date 2012-05-10 Time 11:48 Rev Time 0.00
Received By fmittner Date 2012-05-10 Time 11:48 Sent To  
Notes
2012-05-10 11:51:44REQUIRES A CERTIFICATE OF APPROPRIATENESS
 (COA)....OVERHANGS NOT ARCHITECTURALLY COMPATIBLE.
 SLOPED WITH BARREL TILE. QUESTIONS, CONTACT FRIEDERIKE
 MITTNER 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2012-10-10 Cont ID  
Sent By jwitmer Date 2012-10-10 Time 14:22 Rev Time 0.00
Received By jwitmer Date 2012-10-09 Time 10:59 Sent To  
Notes
2012-10-10 11:00:11SENT TO JIM'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-09-14 Cont ID  
Sent By jwitmer Date 2012-09-14 Time 16:16 Rev Time 0.00
Received By jwitmer Date 2012-09-10 Time 16:49 Sent To  
Notes
2012-09-13 16:50:01SENT TO JIM'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-09-13 Cont ID  
Sent By jgomez Date 2012-07-24 Time 16:48 Rev Time 0.00
Received By jgomez Date 2012-07-03 Time 08:50 Sent To  
Notes
2012-09-13 16:48:54LAST REVIEW WAS DONE ON 7/24/12. JG.
2012-07-03 08:49:49INCOMING SENT TO ZONING/ HISTORIC BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-22 Cont ID  
Sent By jwitmer Date 2012-05-22 Time 10:59 Rev Time 0.00
Received By jwitmer Date 2012-04-25 Time 14:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status N Date 2012-07-23 Cont ID  
Sent By lmartine Date 2012-07-23 Time 17:15 Rev Time 0.00
Received By lmartine Date 2012-07-09 Time 13:58 Sent To B
Notes
2012-07-23 17:16:34SEE FREDERIEK'S HISTORICAL APPROVAL.
2012-07-09 13:59:24HISTORIC PROPERTY - GIVEN TO FM FOR REVIEW.

Review Stop Z ZONING
Rev No 1 Status P Date 2012-05-10 Cont ID  
Sent By fmittner Date 2012-05-10 Time 11:52 Rev Time 0.00
Received By fmittner Date 2012-05-10 Time 11:52 Sent To  
Notes
***NONE***