2012-04-24 10:23:36 | BUILDING PLAN REVIEW |
| PERMIT: 12040421- UNIT 910 |
| 12040586- UNIT 912 |
| ADD:319 CLEMATIS ST |
| CONT: RIELLY CONSTRCUCTION |
| TEL: (561)262-6876 |
| |
| 2010 FLORIDA BUILDING CODE W/ |
| * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| NOTE: PLANS INDICATE A NEW TENANT SEPERATION WALL, 2 |
| PERMITS WERE CREATED FOR UNITS ON EACH SIDE OF THE WALL |
| FOR HISTORY OF THE UNIT (INDICATION OF WHEN THIS UNIT |
| WAS CREATED) AND LOGGING IN OF INSPECTION RESULTS. |
| |
| 1) NEITHER THE LS NOR A-1.0 SHEET PROVIDE WALL |
| IDENTIFICATION TAGS IDENTIFYING THE WALL TYPE TO BE |
| INSTALLED. SHEET A-3.0 DETAIL-A PARTITION DETAILS DO |
| NOT INDENTIFY WHERE THESE WALLS TYPES WILL BE |
| INSTALLED? 106.3.5.1.1(4) FIRE SEPERATION WALLS, |
| 709.6(1) ALSO SEE EXCEEPTION #1? |
| |
| 2) PROVIDE COMPLIANCE WITH: 2010 FBC-B 712.6 FIRE |
| WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS |
| AND SMOKE PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE |
| PROTECTED OPENINGS SHALL BE EFFECTIVELY AND PERMANENTLY |
| IDENTIFIED WITH SIGNS OR STENCILING IN A MANNER |
| ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. SUCH |
| IDENTIFICATION SHALL BE ABOVE ANY DECORATIVE CEILING |
| AND IN CONCEALED SPACES. SUGGESTED WORDING FOR FIRE AND |
| SMOKE BARRIERS: "FIRE AND SMOKE BARRIER - PROTECT ALL |
| OPENINGS." |
| |