Plan Review Details - Permit 12040402
Plan Review Stops For Permit 12040402
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-05-02 Cont ID  
Sent By rlecky Date 2012-05-02 Time 08:54 Rev Time 0.00
Received By rlecky Date 2012-05-01 Time 17:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2012-05-02 Cont ID  
Sent By hmoser Date 2012-04-20 Time 09:35 Rev Time 0.00
Received By lmartine Date 2012-04-16 Time 09:50 Sent To  
Notes
2012-05-02 09:10:12WAITING FOR MECHANICAL AND ELECTRICAL CONTRACTORS TO
 APPLY.
2012-04-19 09:52:37GAVE TO HAROLD
2012-04-19 09:51:584/18/12 ADDED 'EXPEDITED' REQUEST
2012-04-17 13:39:04SENT TO MECHANICAL SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-05-01 Cont ID  
Sent By hmoser Date 2012-05-01 Time 10:46 Rev Time 0.00
Received By hmoser Date 2012-05-01 Time 10:09 Sent To  
Notes
2012-05-01 10:45:51PROVISO
 1) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS.
 2010 FLORIDA ENERGY CODE.
 2) REFER TO SECTION 301.4 GENERAL. PROVIDE
 MANUFACTURERS
 INSTALLATION INSTRUCTIONS FOR SMOKE FIRE DAMPERS AT 1ST
 INSPECTION.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-04-20 Cont ID  
Sent By hmoser Date 2012-04-20 Time 09:06 Rev Time 0.00
Received By hmoser Date 2012-04-20 Time 08:09 Sent To  
Notes
2012-04-20 09:06:31PROVISO
 1) REFER TO SECTION 301.4 GENERAL 2010 FBC (M)
 HAVE THE MANUFACTURERS INSTALLATION INSTRUCTIONS
 FOR THE SMOKE FIRE DAMPERS ON SITE FOR 1ST INSPECTION.
 2) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS
 2010 FLORIDA ENERGY CODE .
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 HMOSER @WPB.ORG