Plan Review Details - Permit 12040374
Plan Review Stops For Permit 12040374
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-06-14 Cont ID  
Sent By jwitmer Date 2012-06-14 Time 16:15 Rev Time 0.00
Received By jwitmer Date 2012-06-14 Time 16:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-04-23 Cont ID  
Sent By jwitmer Date 2012-04-23 Time 14:29 Rev Time 0.00
Received By jwitmer Date 2012-04-23 Time 14:29 Sent To  
Notes
2012-04-23 16:17:39 
 BUILDING PLAN REVIEW
 PERMIT:12040374
 ADD: 7750 OKEECHOBEE BLVD, SUITE__?__
 CONT: LTI DEVELOPMENT
 TEL: (561)718-6243
  
 2010 FLORIDA BUILDING CODE W/
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) NEITHER THE PLANS (COVER SHEET) NOR PERMIT
 APPLICATION PROVIDE WHICH SUITE NUMBER WORK IS TO BE
 COMPLETED UNDER THIS PERMIT ?
 2010 FBC-B 106.1.1* INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED
 AND DRAWN UPON SUITABLE MATERIAL. ELECTRONIC MEDIA
 DOCUMENTS ARE PERMITTED TO BE SUBMITTED WHEN APPROVED
 BY THE BUILDING OFFICIAL. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL
 (SEE ALSO SECTION 106.3.5).
  
 2) PLANS INDICATE THE PROJECT LOCATION IS WITHIN THE
 PALM BEACH COUNTY JURISDICTION, PROPERTIES THAT START
 THEIR PCN NUMBERS WITH 74- ARE LOCATED IN THE CITY OF
 WEST PALM BEACH BOUNDRIES, 106.1.1*.
  
 3) SHEET A1 INDICATES A POS/ NEGATIVE PRESSURE OF 60.
 2010 FBC-B WIND DESIGN CRITERIA IS NOT INDICATED ON THE
 PLANS. IS THE PRESSURE INDICATED V(ALT) 2010 OR IS THE
 PRESSURE INDICATED
 V(ASD)? PLEASE PROVIDE WIND DESIGN CRITERIA EXPOSURE,
 HEIGHT OF BUILDING, & BUILDING RISK FACTOR (WIND MAP).
 2010 FBC-B 1609.
  
 4) PROVIDE PRODUCT SPECS FOR THE WALK IN COOLER/
 FREEZER IN ACCORDANCE WITH 2010 FBC-B 2603.4.1.2 (1-4).
  
 5) PLEASE INDICATE THE TYPE OF OCCUPANCY OCCUPIED THIS
 SPACE BEFORE? IS IT A CHANGE OF OCCUPANCY? 2010
 EXISTING BUILDING CODE 901.3.1.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-06-08 Cont ID  
Sent By rlecky Date 2012-06-08 Time 16:36 Rev Time 0.00
Received By rlecky Date 2012-06-08 Time 16:25 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-05-01 Cont ID  
Sent By rlecky Date 2012-05-01 Time 08:48 Rev Time 0.00
Received By rlecky Date 2012-04-30 Time 15:55 Sent To  
Notes
2012-05-01 08:49:1812040374
 7750 OKEECHOBEE BLVD.
 INTERIOR BUILDING OUT FOR JJ
  
 PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE 2010 FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 505.5.3
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES.
 FBC505.1, 505.2
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-06-12 Cont ID  
Sent By wjolin Date 2012-06-12 Time 08:37 Rev Time 0.00
Received By wjolin Date 2012-06-12 Time 08:33 Sent To  
Notes
2012-06-12 08:37:147750 OKEECHOBEE BOULEVARD
 PERMIT #12040374
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR DEMOLITION
 WORK AND THE MODIFICATION OF THE FIRE SPRINKLER SYSTEM
 AND/OR FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-04-24 Cont ID  
Sent By wjolin Date 2012-04-24 Time 14:13 Rev Time 0.00
Received By wjolin Date 2012-04-24 Time 13:09 Sent To  
Notes
2012-04-24 14:13:327750 OKEECHOBEE BOULEVARD
 PERMIT #12040374
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 INDICATE THE ADDRESS SUITE NUMBER OF THIS PROJECT.
  
 PLANS STATE A SHELL BUILDING IS EXISTING; INDICATE IF
 ANY DEMOLITION WORK IS TO BE PERFORMED.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 A NEW EXIT DOOR IS BEING SAW-CUT IN THE CMU WALL.
 INDICATE WHERE THIS EXIT IS DISCHARGING (PARKING LOT,
 SIDEWALK, GRASS, ETC.).
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR DEMOLITION
 WORK AND THE MODIFICATION OF THE FIRE SPRINKLER SYSTEM
 AND/OR FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-06-25 Cont ID  
Sent By lwagner Date 2012-06-25 Time 13:27 Rev Time 0.00
Received By lwagner Date 2012-05-24 Time 10:58 Sent To  
Notes
2012-06-22 15:12:276/22 TO HM DESK
  
2012-05-29 10:57:59INCOMING SENT TO BOX B05. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-03 Cont ID  
Sent By hmoser Date 2012-05-03 Time 09:54 Rev Time 0.00
Received By hmoser Date 2012-04-13 Time 13:09 Sent To  
Notes
2012-04-17 13:10:23SENT TO B1 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-06-25 Cont ID  
Sent By hmoser Date 2012-06-25 Time 10:13 Rev Time 0.00
Received By hmoser Date 2012-06-25 Time 10:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-05-03 Cont ID  
Sent By hmoser Date 2012-05-03 Time 09:38 Rev Time 0.00
Received By hmoser Date 2012-05-03 Time 08:20 Sent To  
Notes
2012-05-03 09:54:25PLANS DENIED
 1) PLANS SHOW DUCT DETECTOR ON RETURN AIR. REFER TO
 SECTION
 606.2.1 SUPPLY AIR SYSTEMS. 2010 FBC (M)
 2) PROVIDE A DETAIL BY THE ENGINEER FOR CONDENSER STAND
 TO ROOF TIEDOWN AND CONDENSER TO STAND TIEDOWN ON THE
 PLANS.
 3) HOODS,COOLERS AND FREEZERS REQUIRE SEPARATE
 APPLICATION
 PLANS AND PERMIT
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-06-25 Cont ID  
Sent By lwagner Date 2012-06-25 Time 13:26 Rev Time 0.00
Received By lwagner Date 2012-06-25 Time 10:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-04-26 Cont ID  
Sent By lwagner Date 2012-04-26 Time 15:33 Rev Time 0.00
Received By lwagner Date 2012-04-26 Time 13:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2012-04-30 Cont ID  
Sent By lfranco Date 2012-04-30 Time 15:09 Rev Time 0.00
Received By lfranco Date 2012-04-30 Time 15:09 Sent To  
Notes
2012-04-30 15:10:12PLANNING: **** *ZONING REVIEW NOT REQUIRED: INTERIOR
 WORK ONLY AND THE VALUE OF PROPOSED WORK DOES NOT
 EXCEED 50% OF THE IMPROVEMENT VALUE. *****


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved