Plan Review Details - Permit 12040332
Plan Review Stops For Permit 12040332
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-04-17 Cont ID  
Sent By jgomez Date 2012-04-17 Time 14:46 Rev Time 0.00
Received By jgomez Date 2012-04-17 Time 14:46 Sent To  
Notes
2012-04-17 14:53:02BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PER AGREEMENT BETWEEN ROBERT BROWN AND HARRY WICKS:
 "A FIELD PULL TEST ON THE POLYISO BOARD ATTACHMENT TO
 THE STEEL DECK" WILL BE PERFORMED AND RESULTS SUBMITTED
 FOR REVIEW.
  
 2- ANY RETROFIT ROOF DRAINS WILL REQUIRE PLUMBING
 REVIEW.
  
 3- ANY ROOF EQUIPMENT REMOVAL REQUIRES SEPARATE PERMITS
 AND REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-04-16 Cont ID  
Sent By rbrown Date 2012-04-16 Time 19:31 Rev Time 0.00
Received By rbrown Date 2012-04-13 Time 10:37 Sent To  
Notes
2012-04-16 19:31:16RESPONSE TO REQUEST FOR CONSIDERATION UNDER 2010 FBC
 SECTION 104.11 ALTERNATIVE MATERIAL, DESIGN AND METHODS
 OF CONSTRUCTION AND EQUIPMENT.
  
 THIS REVIEW IS TO GIVE CONSIDERATION TO THE PROPOSED
 USE OF OLYBOND 500 ADHESIVE FOR ATTACHMENT OF POLYISO
 INSULATION PANELS TO STEEL DECK IN LIEU OF MECHANICAL
 FASTENING USING DRILL-TEC FASTENERS AND 3 INCH DIA.
 DRILL-TEC STEEL PLATES AS SPECIFIED IN MIAMI-DADE NOA#
 10-0125.05:
  
 ** EITHER PROVIDE A LETTER FROM CAMPANY ROOFING
 AGREEING TO PROVIDE PULL TESTS SHOWING RESISTANCE TO A
 DESIGN UPLIFT OF -115 PSF OR PROVIDE THE FOLLOWING
 DOCUMENTATION:
  
 IF ABOVE-MENTIONED SITE SPECIFIC PULL TESTS WILL NOT BE
 PERFORMED PLEASE PROVIDE A LETTER FROM OMG, INC., AS
 MANUFACTURER OF OLYBOND 500, TO ADDRESS THE FOLLOWING:
  
 1) COMPATIBILITY - PAGE 2 OF MIAMI-DADE NOA#
 07-1120.05, UNDER SCOPE STATES THAT THE NOA IS LIMITED
 ONLY TO THOSE ROOF ASSEMBLIES WHERE OLYBOND 500 IS
 SPECIFICALLY LISTED AS AN ACCEPTED COMPONENT. PLEASE
 PROVIDE A LETTER FROM OMG, INC., AS MANUFACTURER OF
 OLYBOND 500 STATING THAT IT IS SUITABLE FOR USE WITH
 ENERGYGUARD RA POLYISO INSULATION PANELS.
  
 2) ADHESION - RIZA ALTAN, P.E., LETTER DATED 4/2/12,
 STATES THAT THE TENSILE RESISTANCE OF OLYBOND 500
 ADHESIVE "ON STEEL SURFACES IS 9 PSI". HOWEVER PAGE 2
 OF MIAMI-DADE NOA# 07-1120.05, UNDER PRODUCT
 DESCRIPTION SIMPLY STATES THAT THE TENSILE STRENGTH OF
 OLYBOND 500 IS 9 PSI, WITH NO REFERENCE TO ADHESION TO
 STEEL. THE TENSILE STRENGTH OF THE MATERIAL IS A
 MEASURE OF ITS ABILITY TO RESIST FORCE IN TENSION, IT
 IS NOT A STATEMENT OF ITS ABILITY TO ADHERE TO STEEL OR
 ANY OTHER SUBSTRATE. THE ABILITY OF OLYBOND 500 TO
 ADHERE TO STEEL IS NOT SPECIFICALLY MENTIONED IN THE
 NOA. PLEASE PROVIDE A LETTER/REPORT FROM OMG, INC., AS
 MANUFACTURER OF OLYBOND 500 GIVING RESULTS OF PULL
 TESTS WITH STEEL USED AS THE SUBSTRATE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 TELEPHONE: (561) 805 6652 ROBERT BROWN
 E-MAIL: [email protected]
  
  
  
  
  
2012-04-13 10:38:09SENT TO ROBERT BROWN'S DESK FOR LOCAL PRODUCT APPROVAL
 REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-04-17 Cont ID  
Sent By jgomez Date 2012-04-17 Time 14:45 Rev Time 0.00
Received By jgomez Date 2012-04-17 Time 14:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-04-13 Cont ID  
Sent By jgomez Date 2012-04-13 Time 09:23 Rev Time 0.00
Received By jgomez Date 2012-04-13 Time 09:23 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved