Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-04-27 Cont ID  
Sent By lmartine Date 2012-04-27 Time 14:17 Rev Time 0.00
Received By lmartine Date 2012-04-27 Time 14:17 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-04-20 Cont ID  
Sent By shill Date 2012-04-20 Time 14:25 Rev Time 0.00
Received By shill Date 2012-04-20 Time 14:25 Sent To  
Notes
2012-04-20 14:27:27****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
  
 1. DESIGN PRESSURES APPEAR TOO LOW. EXPOSURE C, 15 MRH,
 10 SF OPENING (WORST CASE) ZONE 4, DESIGN PRESSURES
 SHOULD BE +37.9 / -41.1; -36.7 PROPOSED. IT IS NOT
 CLEAR HOW YOU HAVE DETERMINED DESIGN PRESSURES, SEE FBC
 R 301.2(2).
  
 NOTE THAT THE LARGER OPENINGS HAVE HIGHER DESIGN
 PRESSURES, WHICH IS NOT CORRECT. PLEASE FEEL FREE TO
 CONTACT ME IF YOU WISH TO DISCUSS METHODS OF
 DETERMINING DESIGN PRESSURE REQUIREMENTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-04-20 Cont ID  
Sent By shill Date 2012-04-20 Time 14:27 Rev Time 0.00
Received By shill Date 2012-04-12 Time 11:03 Sent To  
Notes
2012-04-13 11:04:16INCOMING SENT TOMISC BOX # 1. JW