Plan Review Details - Permit 12040183
Plan Review Stops For Permit 12040183
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-04-18 Cont ID  
Sent By shill Date 2012-04-18 Time 17:40 Rev Time 0.00
Received By shill Date 2012-04-18 Time 17:40 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-04-10 Cont ID  
Sent By shill Date 2012-04-10 Time 14:39 Rev Time 0.00
Received By shill Date 2012-04-10 Time 14:38 Sent To  
Notes
2012-04-10 15:00:14****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. BLOCK SUBSTRATE, 58.6 PSF, REQUIRES 8" ANCHOR
 SPACING, SEE CHART ON SHEET 11.
  
 PLEASE SEE INSTALLATION SHEDULE AND ENGINEERING. ZONE 4
 10SF PRESSURE OF -47.4 WAS CIRCLED, AND ZONE 5 10SF
 PRESSURE OF -58.6 WAS CIRCLED. FOR DESIGN PRESSURE ON
 THE INSTALLATION SCHEDULE, +47.4/-58.6 WAS PROPOSED.
 NOT CLEAR WHAT INTENT WAS; PLEASE FEEL FREE TO CONTACT
 ME IF YOU NEED ASSISTANCE.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-04-18 Cont ID  
Sent By shill Date 2012-04-18 Time 17:39 Rev Time 0.00
Received By shill Date 2012-04-12 Time 13:45 Sent To  
Notes
2012-04-13 13:45:33INCOMING SENT TO S HILL DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-04-10 Cont ID  
Sent By shill Date 2012-04-10 Time 15:00 Rev Time 0.00
Received By shill Date 2012-04-06 Time 15:27 Sent To  
Notes
2012-04-06 15:27:32MISC 1