Plan Review Details - Permit 12040044
Plan Review Stops For Permit 12040044
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-06-14 Cont ID  
Sent By jwitmer Date 2012-06-14 Time 11:08 Rev Time 0.00
Received By jwitmer Date 2012-06-14 Time 11:06 Sent To  
Notes
2012-06-14 11:08:16COVER SHEETS NEED TO BE REVERSED IN PROJECT DOCS BEFORE
 BATCH STAMPING OCCURS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-05-29 Cont ID  
Sent By jwitmer Date 2012-05-29 Time 15:33 Rev Time 1.50
Received By jwitmer Date 2012-05-29 Time 14:33 Sent To  
Notes
2012-05-29 15:53:31BUILDING PLAN REVIEW
 PERMIT: 12040044
 ADD: 1711 WORTHINGTON BLDG PHASE I BLDG 100 SUITE 108
 BUSINESS
 CONT: ONICX LLC
 TEL: (813)964-0666
  
 2010 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 MAY 28/2012
 ACTION: DENIED
  
 1) THE CONTRACTOR IS TO COME IN AND CHANGE THE PERMIT
 APPLICATION UNDER THE HEADING DESCRIPTION OF WORK. THE
 PERMIT APPLICATION AND PLANS NEED TO USE THE SAME
 NOMENCLATURE THE PLANS INDICATE THIS PORTION OF WORK AS
 PHASE I BLDG 100 BUSINESS L/ CHANGE IN OCCUPANCY.
  
 2) SHEET A-0.0 COVER SHEET & INDEX;
 2A) COMPLIED.
  
 2B) COMPLIED.
  
 2C) SEMI-COMPLIED. THE HEADING OF CODE INFORMATION
 FBC-B 803.5 INDICATES, CLASS E FOR EXITS &
 CORRIDORSCORRECT OCCUPANCY TYPE FOR OFFICES.
  
  
 2D) PRODUCT APPROVAL ARE LOADED UPSIDE DOWN.
 THE COVER SHEET ALSO INDICATES THE USE OF YKK YES40F1
 WINDOW PRODUCT APPROVALS FL 7606.1 PLEASE NOTE THIS
 REPORT IS FOR NON- MISSILE RATED GLAZING WHICH WILL
 REQUIRE PRODUCT TESTING REPORT FOR STORM PANELS.
  
 THE OTHER ISSUE WITH THE SUBMITTED FL 7606.1 REPORT
 ONLY THE COVER SHEETS WERE UPLOADED, THE ACTUAL
 EVALUATION REPORT WITH PRESSURES WAS NOT INCLUDED NOR
 WAS THE INSTALATION INSTRUCTIONS THAT TIE TO THE
 FLORIDA COVER SHEET.
  
 PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.4.
  
 FL BLD CODE 2004 SECTION 106.3.3,
 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION SCHEDULE
 SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS,
 UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR
 REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 2E) THE SECOND PRODUCT APPROVAL THE COVER SHEET LISTED
 IS FOR EXTERIOR OUTSWING YKK DOOR FL 9967.1 NO REPORT
 WAS FOUND UNDER THIS PRODUCT NUMBER.
  
 2F) PLEASE CORRECT THE TITLE SHEET FOR THE BUSINESS
 OFFICES PERMIT BY REMOVING ALL REFREENCES TO THE
 EDUCATIONAL OCCUPANCY, NOT PART OF THE SCOPE OF WORK
 UNDER THIS PERMIT.
  
 3) SHEET A-1.0:
 3A) PLEASE PROVIDE THE DISTANCE BETWEEN THE TWO
 BUILDINGS AND PROVIDE COMPLIANCE WITH FBC-B TABLE 602
 OR ARE THEY CONSIDERED BUILDINGS ON SAME LOT UNDER
 FBC-B 503.1.2.
  
 3B) COMPLIED.
  
 4COMPLIED.
  
 5)BUSINESS OCCUPANCY / NOT A CHANGE OF OCCUPANCY ,
 COMPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-04-10 Cont ID  
Sent By jwitmer Date 2012-04-10 Time 16:22 Rev Time 0.00
Received By jwitmer Date 2012-04-10 Time 16:14 Sent To  
Notes
2012-04-10 16:21:20BUILDING PLAN REVIEW
 PERMIT: 12040044
 ADD: 1711 WORTHINGTON BLDG PHASE I BLDG 100 SUITE 108
 BUSINESS
 CONT: ONICX LLC
 TEL: (813)964-0666
  
 2010 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE CONTRACTOR IS TO COME IN AND CHANGE THE PERMIT
 APPLICATION UNDER THE HEADING DESCRIPTION OF WORK. THE
 PERMIT APPLICATION AND PLANS NEED TO USE THE SAME
 NOMENCLATURE THE PLANS INDICATE THIS PORTION OF WORK AS
 PHASE I BLDG 100 BUSINESS L/ CHANGE IN OCCUPANCY.
  
 2) SHEET A-0.0 COVER SHEET & INDEX;
 2A) CODE INFORMATION, THE MINIMUM BUILDING TYPE IS NOT
 PROVIDED ONLY A "B" TYPE 2010 FBC-B WPB ADMINISTRATIVE
 CODE 106.3.5.1.1(3) MINIMUM TYPE OF CONSTRUCTION &
 TABLE 503.
  
 BUILDING 200 PHASE II THE EDUCATIONAL OCCUPANCY
 INDICATES AN AREA OF 11,410 SQ FT, PLEASE PROVIDE THE
 MINIMUM BUILDING TYPE IF AREA INCREASES WERE CONSIDERED
 FOR FRONTAGE OR FIRE SPRINKLERS FBC-B 506.2 AND OR
 506.3.
  
 2B) THE PLANS DO NOT PROVIDE DOCUMENTATION IF THIS
 BUILDING IS PROTECTED BY NFPA 13 FIRE SPRIKLER SYSTEM
 OR NOT? INDEX DOES NOT INDICATE ANY FIRE SPINKLER OR
 FIRE PROTECTION PLANS WITHIN THE SET? 106.3.5.1.1(5)
 SCHEMATIC FIRE SPRINKLERS.
  
 2C) THE HEADING OF CODE INFORMATION FBC-B 803.5
 INDICATES, CLASS B FOR EXITS & CORRIDORS/ CLASS C FOR
 ROOMS AND ENCLOSED SPACES THESE RATINGS ARE FOR FIRE
 SPRINKLERED BUILDINGS.
  
 2D) THE COVER SHEET ALSO INDICATES THE USE OF YKK
 YES40F1 WINDOW PRODUCT APPROVALS FL 7606.1 PLEASE NOTE
 THIS REPORT IS FOR NON- MISSILE RATED GLAZING WHICH
 WILL REQUIRE PRODUCT TESTING REPORT FOR STORM PANELS.
  
 THE OTHER ISSUE WITH THE SUBMITTED FL 7606.1 REPORT
 ONLY THE COVER SHEETS WERE UPLOADED, THE ACTUAL
 EVALUATION REPORT WITH PRESSURES WAS NOT INCLUDED NOR
 WAS THE INSTALATION INSTRUCTIONS THAT TIE TO THE
 FLORIDA COVER SHEET.
  
 PROVIDE STORM PANEL INFORMATION WITH INSTALLATION
 SCHEDULE AND KEY PLAN WITH SPECIFIC ANCHORS AND
 MOUNTING TO BE USED FOR ALL NON-IMPACT GLAZING. FBC
 1609.1.4.
  
 FL BLD CODE 2004 SECTION 106.3.3,
 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION SCHEDULE
 SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS,
 UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR
 REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 2E) THE SECOND PRODUCT APPROVAL THE COVER SHEET LISTED
 IS FOR EXTERIOR OUTSWING YKK DOOR FL 9967.1 NO REPORT
 WAS FOUND UNDER THIS PRODUCT NUMBER.
  
 3) SHEET A-1.0:
 3A) PLEASE PROVIDE THE DISTANCE BETWEEN THE TWO
 BUILDINGS AND PROVIDE COMPLIANCE WITH FBC-B TABLE 602
 OR ARE THEY CONSIDERED BUILDINGS ON SAME LOT UNDER
 FBC-B 503.1.2.
  
 3B) THE PLANS DO NOT COMMENT ON THE TENANT SEPERATION
 WALL BETWEEN THE BUSINESS OCCUPANCY AND THE NEXT TENANT
 SPCACE, OR IS THIS ALSO A OCCUPANCY SEPERATION WALL?
 FBC-B 709.6 / TABLE 508.4?
  
 4) SHEET A-2.0 FILE ROOM 104 WALL TYPE 4 INDICATES A 2
 HR WALL BUT THE WALL DOES NOT GO TO THE ROOF DECK
 ABOVE. THE DESIGNER HAS ELECTED TO PROVIDE A FIRE RATED
 CEILING BUT NO ASSEMBLY HAS BEEN PROVIDED FOR THE RATED
 CEILING AS THE WALL. FBC-B TABLE 508.4 & 707.3.9.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-06-04 Cont ID  
Sent By rlecky Date 2012-06-04 Time 09:42 Rev Time 0.00
Received By rlecky Date 2012-06-01 Time 14:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-04-23 Cont ID  
Sent By rlecky Date 2012-04-23 Time 17:21 Rev Time 0.00
Received By rlecky Date 2012-04-23 Time 16:12 Sent To  
Notes
2012-04-23 17:22:3412040044 & 12040042
 1700 WORTHINGTON ROAD
 BLDG. A & B
  
 PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.5
 VERIFY COMPLIANCE WITH LIGHTING AND GLARE REQUIREMENTS
 FOR CLASS ROOMS. FBC 443.3.7
 PROVIDE A RISER PLAN SHOWING THE NEW AND EXISTING
 ELECTRIC SERVICE COMPONENTS WITH MAIN DISCONNECT,
 SERVICE GROUNDING, CONDUIT SIZE AND TYPE, CONDUCTOR
 SIZE AND TYPE ALL LOCATED ON THE PLAN. INCLUDE A
 SUMMARY LOAD CALCULATION SHOWING EXISTING ELECTRIC
 SERVICE CAN HANDLE THE NEW LOADS; VERIFY SAFETY
 CLEARANCES AND ACCESS. NEC 110.26, 215.5
 PROVIDE AN INTERSYSTEM BONDING TERMINAL. NEC 250.94
 PROVIDE FOR GFCI PROTECTION AT THE VENDING MACHINES.
 NEC 422.51
  
 NOTE:
 SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE
 ALARM SYSTEM, VOICE AND DATA.
  
 ROBERT LECKY, CBO
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-06-04 Cont ID  
Sent By wjolin Date 2012-06-04 Time 14:32 Rev Time 0.00
Received By wjolin Date 2012-06-04 Time 14:08 Sent To  
Notes
2012-06-04 14:31:001711 WORTHINGTON ROAD - BUILDING A & B
 PERMIT #12040042 & #12040044
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL PLAN REVIEW COMMENTS ADDRESSED ON PLANS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-04-09 Cont ID  
Sent By wjolin Date 2012-04-09 Time 15:00 Rev Time 0.00
Received By wjolin Date 2012-04-09 Time 11:35 Sent To  
Notes
2012-04-09 15:00:251711 WORTHINGTON ROAD - BUILDING A & B
 PERMIT #12040042 & #12040044
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE SCOPE OF WORK APPEARS TO INCLUDE A CHANGE OF
 OCCUPANCY. SUBMIT DEMOLITION DRAWINGS. ALL DEMOLITION
 WORK SHALL CONFORM TO THE REQUIREMENTS OF NFPA 241.
 TRASH AND CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE
 SITE DAILY. POST "NO SMOKING" SIGNS THROUGHOUT
 BUILDING.
  
 PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET.
 NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT
 LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL
 CONTRAST THE BACKGROUND.
  
 INDICATE THE OCCUPANCY TYPE AND FIRE RATED SEPARATION
 BETWEEN SUITE #108 AND THE AREA TO THE WEST OF THIS
 SUITE. EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION
 SHALL BE PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING READING FIRE/SMOKE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
  
 INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE
 EITHER CLASS A OR CLASS B PER SECTION 14.3.3.2 OF NFPA
 101 (FLORIDA).
  
 CONFIRM THE LARGE MOTIVATIONAL POSTERS/SIGNS IN THE
 EGRESS CORRIDORS MEET THE REQUIREMENTS FOR CLASS A OR
 CLASS B INTERIOR WALL FINISHES.
  
 RETRACTABLE BELT BARRIER OBSTRUCTS PATH OF EGRESS TO
 EXIT DOORS.
  
 THE CURRENT SHELL SPACE (FUTURE CLASSROOMS #7 & #8)
 WILL BE TREATED AS A STORAGE ROOM UNTIL THIS SPACE IS
 OCCUPIED. THE STORAGE ROOM WILL NEED TO BE SEPARATED
 FROM THE REST OF THE BUILDING WITH A ONE-HOUR FIRE
 BARRIER HAVING PROTECTED OPENINGS AND PENETRATIONS.
  
 FUTURE CLASSROOM #8 SHOWS FURNITURE OBSTRUCTING THE
 EXTERIOR EXIT DOOR.
  
 ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS
 SHALL NOT EXCEED 20 PERCENT OF THE INDIVIDUAL WALL
 AREA.
  
 AN EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN
 BUILDING PRIOR TO OCCUPANCY.
  
 EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY. ALL
 DRILLS SHALL BE SOUNDED ON THE FIRE ALARM SYSTEM.
  
 FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED MONTHLY
 BY A TRAINED SENIOR MEMBER OF THE STAFF, AFTER WHICH A
 COPY OF THE LATEST INSPECTION REPORT SHALL BE POSTED IN
 A CONSPICUOUS PLACE IN THE DAY-CARE FACILITY. IT SHALL
 BE THE DUTY OF THE STAFF TO INSPECT ALL EXITS DAILY TO
 ENSURE THAT ALL DOORS AND EXIT PATHS ARE MAINTAINED
 CLEAR OF OBSTRUCTIONS.
  
 FIRE ALARM: PROVIDE NOTIFICATION APPLIANCES IN ALL
 PUBLIC AND COMMON USE SPACES SUCH AS READING #123,
 BREAK #129, ETC.
  
 FIRE ALARM: A CERTIFICATE OF COMPLETION AND A THIRD
 PARTY MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE
 SHALL BE PROVIDED AT TIME OF FINAL FIRE ALARM
 INSPECTION.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-06-14 Cont ID  
Sent By jwitmer Date 2012-06-14 Time 11:21 Rev Time 0.00
Received By jwitmer Date 2012-06-12 Time 12:26 Sent To  
Notes
2012-06-12 12:27:05DIGITAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2012-06-06 Time   Rev Time 0.00
Received By rregueir Date 2012-05-24 Time 11:36 Sent To  
Notes
2012-05-24 11:37:10DIGITAL - 2ND ROUND

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-07 Cont ID  
Sent By rregueir Date 2012-05-07 Time 10:51 Rev Time 0.00
Received By rregueir Date 2012-04-06 Time 10:51 Sent To  
Notes
2012-05-07 10:51:40DIGITAL

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-06-06 Cont ID  
Sent By rregueir Date 2012-06-06 Time 17:48 Rev Time 0.00
Received By rregueir Date 2012-06-06 Time 17:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-05-07 Cont ID  
Sent By rregueir Date 2012-05-07 Time 10:51 Rev Time 0.00
Received By rregueir Date 2012-05-07 Time 10:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2012-06-14 Cont ID  
Sent By lwagner Date 2012-06-14 Time 09:18 Rev Time 0.00
Received By lwagner Date 2012-06-14 Time 09:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-06-01 Cont ID  
Sent By lwagner Date 2012-06-01 Time 10:50 Rev Time 0.00
Received By lwagner Date   Time   Sent To  
Notes
2012-06-01 10:54:11EXISTING RESTROOMS.
 DRINKING FOUNTAIN FOR BUSINESS IS IN BUILDING 200

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-04-25 Cont ID  
Sent By lwagner Date 2012-04-25 Time 09:17 Rev Time 0.00
Received By lwagner Date 2012-04-24 Time 13:57 Sent To  
Notes
2012-04-24 14:45:27FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. BUILDING 100 DOES NOT INCLUDE THE REQUIRED DRINKING
 FOUNTIAN. PLUMBING 403.1 MINIMUM PLUMBING FIXTURES. PER
 ACCESSIBILITY CODE 2010 - 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 2. THE LAVS IN ROOMS 107 & 108 APPEAR TO BE IN THE 5'
 CLEAR SPACE FOR THE WATER CLOSET. THE TOTAL FOR THE
 RESTROOM WOULD BE 5' + 2'-1" = 7'-1"
 FBC 2010 FLORIDA ACCESSIBILITY CODE 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL. 604.3.2 OVERLAP. THE
 REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE
 PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB
 BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT
 HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE
 AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE
 TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL
 BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE.
  
 3. A SANITARY RISER DIAGRAM IS REQUIRED PER FBC 106.3.3
 PLUMBING (13)
  
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2012-06-14 Cont ID  
Sent By jwitmer Date 2012-06-14 Time 14:32 Rev Time 0.00
Received By jwitmer Date 2012-06-14 Time 14:32 Sent To  
Notes
2012-06-14 14:33:42LEFT SIGNATURE SHEETS ON RON REGUEIRO'S CHAIR
 YESTERDAY. JW

Review Stop Z ZONING
Rev No 1 Status N Date 2012-04-30 Cont ID  
Sent By ajones Date 2012-04-30 Time 10:45 Rev Time 0.00
Received By ajones Date 2012-04-30 Time 10:45 Sent To  
Notes
***NONE***