Plan Review Details - Permit 12040024
Plan Review Stops For Permit 12040024
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-06-12 Cont ID  
Sent By rmcdouga Date 2012-06-12 Time 15:38 Rev Time 0.00
Received By rmcdouga Date 2012-06-11 Time 16:38 Sent To  
Notes
2012-06-12 16:04:53BUILDING PROVISO
  
 SUBMIT A LETTER FROM THE DESIGNER OF RECORD LISTING THE
 PRODUCT APPROVALS FOR THE PROJECT AND STATING THAT THEY
 HAVE BEEN REVIEWED AND APPROVED BY HIM AS REQUIRED BY
 CITY AMENDMENT 107.3.4.1
  
 PROVIDE AN EMERGENCY ESCAPE AND RESCUE OPENING IN THE
 SECOND FLOOR BEDROOM THAT COMPLIES WITH FBC R310.1.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-07 Cont ID  
Sent By rmcdouga Date 2012-05-07 Time 16:14 Rev Time 0.00
Received By rmcdouga Date 2012-05-03 Time 14:54 Sent To  
Notes
2012-05-07 16:57:412010 FBC
  
 DENIED BY BUILDING
  
 1) THE EXPOSURE CATEGORY SPECIFIED ON SHEET S100 IS
 INCORRECT. THE STRUCTURE IS LOCATED APPROXIMATELY 656
 FEET FROM THE INTRA-COASTAL WATERWAY. THEREFORE, THE
 SURFACE ROUGHNESS B DOES NOT PREVAIL IN THE UPWIND
 DIRECTION FOR AT LEAST 1,500 FEET. BASED ON FBC
 R301.2.1.4.3 THE EXPOSURE CATEGORY FOR THIS STRUCTURE
 IS C. PLEASE REVISE THE PLANS.
  
 2) PLEASE REVIEW THE DESIGN PRESSURES IN TABLES ON
 SHEET S100 AND REVISE AS NECESSARY TO COMPLY WITH FBC
 R301.2.1.
  
 3) ONLY ONE SET OF PRODUCT APPROVALS WERE SUBMITTED.
 CITY AMENDMENTS 107.1 REQUIRES A MINIMUM OF TWO SETS.
 PLEASE SUBMIT AN ADDITIONAL SET OF PRODUCT APPROVALS.
  
 4) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 5) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE ROOF
 TILE AND SPECIFY THE ATTACHMENT METHOD FROM THE PRODUCT
 APPROVAL THAT WILL BE USED TO INSTALL IT. DCA RULE 9N-3
  
 6) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR ALL
 EXTERIOR DOORS (EXTERIOR LOUVER DOORS, FRENCH DOOR,
 REFURBISHED DOOR FROM MAIN HOUSE) AS REQUIRED BY DCA
 RULE 9N-3. THE PRODUCT APPROVAL SUBMITTED FOR THE
 FRENCH DOOR (CGI 450) IS EXPIRED. IF THE REFURBISHED
 DOOR DOES NOT HAVE A PRODUCT APPROVAL, THEN IT WILL BE
 REQUIRED TO BE ENGINEERED IN ACCORDANCE WITH ACCEPTABLE
 ENGINEERING PRACTICES PER FBC R612.8.3.
  
 7) THE PLANS SPECIFY THAT THE SINGLE HUNG WINDOWS ARE
 TO BE PGT. PRODUCT APPROVALS WERE SUBMITTED FOR BOTH
 PGT AND CGI SINGLE HUNG WINDOWS. PLEASE CLARIFY.
  
 8) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE CGI
 CASEMENT WINDOW IS FOR A SINGLE WINDOW. THE PLANS
 INDICATE DOUBLE CASEMENT WINDOWS AT THE BEDROOM. BASED
 ON THE PRODUCT APPROVAL SUBMITTED TWO SINGLE WINDOWS
 WOULD NEED TO BE JOINED TOGETHER WITH A MULLION WHICH
 WOULD NOT COMPLY WITH THE REQUIRED MINIMUM OPENING
 WIDTH OF FBC R310.1.3. PLEASE SHOW COMPLIANCE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-04-30 Cont ID  
Sent By rlecky Date 2012-04-30 Time 12:21 Rev Time 0.00
Received By rlecky Date 2012-04-30 Time 11:53 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2012-06-05 Cont ID  
Sent By fmittner Date 2012-06-05 Time 14:04 Rev Time 0.00
Received By fmittner Date 2012-06-05 Time 14:04 Sent To B
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2012-04-13 Cont ID  
Sent By fmittner Date 2012-04-13 Time 16:33 Rev Time 0.00
Received By fmittner Date 2012-04-12 Time 15:03 Sent To  
Notes
2012-04-13 16:34:56PUT BACK IN R-10.
  
 APPROVED FOR HP. FRIEDERIKE SPOKE TO ARCHITECT AND
 CONTRACTOR REGARDING ZONING CONCERN. WILL REVISE PLANS
 AND REMOVE COOKTOP.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-06-12 Cont ID  
Sent By rmcdouga Date 2012-06-12 Time 16:05 Rev Time 0.00
Received By rmcdouga Date 2012-05-23 Time 15:48 Sent To  
Notes
2012-06-06 11:36:356/6 TO RM DESK
  
2012-05-23 15:48:51IN ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-08 Cont ID  
Sent By rmcdouga Date 2012-05-08 Time 09:27 Rev Time 0.00
Received By rmcdouga Date 2012-04-02 Time 10:49 Sent To  
Notes
2012-04-04 10:50:07SENT TO R10 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2012-05-04 Cont ID  
Sent By rmcdouga Date 2012-05-04 Time 15:20 Rev Time 0.00
Received By rmcdouga Date 2012-05-04 Time 15:20 Sent To  
Notes
2012-05-04 15:21:58NO MECHANICAL PLANS SUBMITTED. SEPARATE APPLICATION,
 REVIEW AND PERMIT WILL BE REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-06-12 Cont ID  
Sent By rmcdouga Date 2012-06-11 Time 16:35 Rev Time 0.00
Received By rmcdouga Date 2012-06-11 Time 16:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-05-04 Cont ID  
Sent By rmcdouga Date 2012-05-04 Time 14:35 Rev Time 0.00
Received By rmcdouga Date 2012-05-04 Time 14:35 Sent To  
Notes
2012-05-04 15:10:532010 FBC
  
 DENIED BY PLUMBING
  
 1) SUBMIT TWO SETS OF A SANITARY ISOMETRIC RISER
 DIAGRAM THAT INCLUDE THE NEW OUTSIDE SHOWER. CITY
 AMENDMENTS 107.3.5.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2012-06-04 Cont ID  
Sent By jroach Date 2012-06-04 Time 18:35 Rev Time 0.00
Received By jroach Date 2012-05-29 Time 17:48 Sent To HIST
Notes
2012-06-04 18:35:59ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 06.04.2012
 PERMIT NO.: 12040024
 ADDRESS: 290 GRANADA
 CONTRACTOR/CONTACT: JEFF GOMERSALL
 TELEPHONE NO.: 561.659.6696
 SCOPE OF REVIEW: RENOVATIONS TO EXISTING ACCESSORY
 STRUCTURE/APARTMENT AND ADDITION OF NEW STEPS TO REAR
 OF PRIMARY RESIDENCE.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. PLEASE NOTE THAT THE SCOPE OF THIS APPROVAL APPLIES
 ONLY TO THE RENOVATIONS TO THE ACCESSORY STRUCTURE AND
 THE CONSTRUCTION OF NEW STEPS ON THE REAR OF THE
 PRIMARY STRUCTURE. ALL OTHER IMPROVEMENTS SHOWN ON THE
 APPROVED PLANS SHALL BE DONE UNDER SEPARATE PERMITS!
  
 2. PLEASE NOTE THAT SYNTHETIC OR ARTIFICIAL TURF/LAWN
 IS NOT PERMITTED WITHIN THE CITY OF WEST PALM BEACH.
 WHILE NOT A PART OF THE SCOPE OF THIS PERMIT, PLEASE
 MAKE ADJUSTMENTS ACCORDINGLY AS RENOVATIONS PROGRESS.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
2012-05-29 17:48:17GIVEN TO JR

Review Stop Z ZONING
Rev No 1 Status F Date 2012-04-12 Cont ID  
Sent By jroach Date 2012-04-12 Time 14:59 Rev Time 0.00
Received By jroach Date 2012-04-04 Time 16:21 Sent To HIST
Notes
2012-04-12 15:03:41ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 4/12/12
 PERMIT NO.: 12040024
 ADDRESS: 290 GRANADA ROAD
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: RENOVATION TO ACCESSORY STRUCTURE.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO THE CITY'S ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDRS), THE SUBJECT PROPERTY IS ONLY
 PERMITTED ONE (1) SINGLE FAMILY RESIDENCE. IN ORDER TO
 PERMIT AN ACCESSORY APARTMENT, THE LOT WIDTH SHALL BE A
 MINIMUM OF 60 FEET IN WIDTH. IT IS UNDERSTOOD THAT THE
 APARTMENT IS EXISTING AND WAS LEGALLY CONSTRUCTED,
 HOWEVER, SECTION 94-513(B)(1)(D) OF THE ZLDRS INDICATES
 THAT SUCH NONCONFORMITIES MAY ONLY BE RENOVATED
 PROVIDED THAT THE COSTS INCURRED DO NOT EXCEED 50
 PERCENT OF THE VALUE OF THE STRUCTURE. ACCORDING TO THE
 PALM BEACH COUNTY PROPERTY APPRAISER, THE VALUE OF THE
 STRUCTURE IS $56,451. EITHER THE VALUE OF THE
 RENOVATIONS SHALL BE REDUCED TO BELOW 50 PERCENT OF THE
 VALUE OF THE STRUCTURE; OR THE APARTMENT SHALL BE
 REMOVED AND NOT CONSIDERED A DWELLING UNIT; OR THE
 PROPERTY OWNER MAY APPLY FOR A CLASS B SPECIAL USE
 PERMIT FROM THE CITY'S HISTORIC PRESERVATION BOARD
 REQUESTING THE ALLOWANCE OF AN ACCESSORY APARTMENT ON A
 50 FOOT WIDE LOT.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  