Plan Review Details - Permit 12040001
Plan Review Stops For Permit 12040001
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-05-09 Cont ID  
Sent By lmartine Date 2012-05-09 Time 09:13 Rev Time 0.00
Received By lmartine Date 2012-05-09 Time 09:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-04-11 Cont ID  
Sent By JWITMER Date 2012-04-11 Time 15:21 Rev Time 0.00
Received By jwitmer Date 2012-04-11 Time 11:29 Sent To  
Notes
2012-04-11 15:20:47BUILDING PROVISO:
 1) SHEET A1.1 GUARDRAIL AT SOFA AND STOOLS TO COMPLY
 WITH :
 2007/09 FBC-B 1013. 2 HEIGHT. GUARDS SHALL FORM A
 PROTECTIVE
 BARRIER NOT LESS THAN 42" MEASURED VERTICALLY ABOVE THE
 LEADING
 EDGE OF THE TREAD, ADJACENT WALKING SURFACE OR ADJACENT
 SEATBOARD AND MEET THE STRENGTH REQUIREMENTS OF 1607.1
 FOR GUARDRAILS!!!
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-04-23 Cont ID  
Sent By RLECKY Date 2012-04-23 Time 09:52 Rev Time 0.00
Received By rlecky Date 2012-04-23 Time 09:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-04-10 Cont ID  
Sent By WJOLIN Date 2012-04-10 Time 14:37 Rev Time 0.00
Received By wjolin Date 2012-04-10 Time 13:38 Sent To  
Notes
2012-04-10 14:15:01200 CLEMATIS STREET
 REV. TRACKING #12040001
 PERMIT #11120544
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - THE USE OF THE EXISTING NON-CONFORMING
 OPEN STAIR BETWEEN THE 1ST AND 2ND FLOOR IS CONSIDERED
 TO BE APPROVED; HOWEVER, THE FOLLOWING FIRE PROTECTION
 FEATURES SHALL BE INSTALLED:
  
 PER NFPA 13, CLOSELY SPACED SPRINKLERS (6'-0" SPACING)
 AND 18" TALL NON-COMBUSTIBLE DRAFT CURTAINS WILL BE
 REQUIRED AROUND THE PERIMETER OF THE FLOOR/CEILING
 OPENING BETWEEN THE 1ST AND 2ND FLOOR.
  
 REPLACE ANY STANDARD-RESPONSE TYPE SPRINKLERS WITH
 QUICK-RESPONSE TYPE SPRINKLERS.
  
 PROVIDE A COMPLETE SMOKE DETECTION SYSTEM (EXCLUDING
 KITCHEN AREA), COMPLIANT WITH NFPA 72, FOR THE
 BASEMENT, 1ST FLOOR AND 2ND FLOOR.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-05-09 Cont ID  
Sent By lmartine Date 2012-05-09 Time 09:13 Rev Time 0.00
Received By lmartine Date 2012-05-01 Time 17:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-04-23 Cont ID  
Sent By rlecky Date 2012-04-23 Time 09:52 Rev Time 0.00
Received By rlecky Date 2012-04-02 Time 11:29 Sent To  
Notes
2012-04-10 11:19:41EXPEDITED REQUEST SUBMITTED 4/10/12
2012-04-04 11:31:49SENT TO C1 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-05-02 Cont ID  
Sent By hmoser Date 2012-05-02 Time 14:49 Rev Time 0.00
Received By hmoser Date 2012-05-02 Time 13:58 Sent To  
Notes
2012-05-02 14:48:54MECHANICAL PLANS OK
 NEED SEPARATE APPLICATION FOR COOLER AND FREEZER.
 NEED SEPARATE APPLICATION FOR FIRE SUPPRESSION FOR
 HOOD.
 NEED SEPARATE APPLICATION FOR HOOD . THERE IS NO
 DUCTWORK
 FOR HOOD SUBMITTED WITH THE PLANS.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-04-13 Cont ID  
Sent By HMOSER Date 2012-04-13 Time 10:17 Rev Time 0.00
Received By hmoser Date 2012-04-12 Time 13:29 Sent To  
Notes
2012-04-13 10:17:25PLANS DENIED
 1) SEPARATE APPLICATION,PLANS AND PERMIT REQUIRED FOR
 HOOD AND COOLERS
 2) PROVIDE FLOOR GRILLE SIZE AND DUCT SIZE ON THE PLANS
 3) PROVIDE GRILLE SIZE FOR SIDE WALLS ON THE PLANS.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-04-16 Cont ID  
Sent By LWAGNER Date 2012-04-16 Time 14:18 Rev Time 0.00
Received By lwagner Date 2012-04-16 Time 09:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2012-05-07 Cont ID  
Sent By aaponte Date 2012-05-07 Time 16:04 Rev Time 0.00
Received By aaponte Date 2012-05-07 Time 16:04 Sent To  
Notes
2012-05-07 16:19:29PROVISO: SOUTH WINDOW ON EAST ELEVATION SHALL NOT BE
 BLOCKED. IT SHALL BE MAINTAINED. A FILM TO OBSCURE THE
 INTERIOR MAY BE INSTALLED.

Review Stop Z ZONING
Rev No 1 Status F Date 2012-04-11 Cont ID  
Sent By AAPONTE Date 2012-04-11 Time 10:03 Rev Time 0.00
Received By aaponte Date 2012-04-11 Time 10:03 Sent To  
Notes
2012-04-11 10:06:251. PROPOSED FAUX WINDOW WAS PERMITTED DURING PREVIOUS
 REVIEW BECAUSE MECHANICAL EQUIPMENT DID NOT MAKE A REAL
 WINDOW VIABLE. CHANGES SUBMITTED WITH THIS REVISION
 INCLUDE AN OFFICE SPACE THAT MAY HIGHLY BENEFIT FROM
 NATURAL LIGHT. PLEASE MODIFY DRAWINGS TO INCLUDE A REAL
 WINDOW WITH ONLY ONE PORTION AS A FAUX WNDOWS (ELEVATOR
 PORTION).
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.