Plan Review Details - Permit 12030654
Plan Review Stops For Permit 12030654
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2012-03-28 Cont ID  
Sent By shill Date 2012-03-28 Time 15:07 Rev Time 0.00
Received By shill Date 2012-03-28 Time 15:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-04-19 Cont ID  
Sent By rlecky Date 2012-04-19 Time 12:59 Rev Time 0.00
Received By rlecky Date 2012-04-19 Time 12:59 Sent To  
Notes
2012-04-19 13:00:56PLANS REDLINED PER CONTRACTORS REQUEST.RL

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-04-06 Cont ID  
Sent By ddaniels Date 2012-04-05 Time 12:20 Rev Time 0.00
Received By rlecky Date 2012-04-06 Time 12:46 Sent To  
Notes
2012-04-06 15:12:2412030654
 3330 45TH ST #A
 INTERIOR WAREHOUSE REMODEL
  
 PROVIDE AN ELECTRICAL PERMIT. PROVIDE A PANEL SCHEDULE
 SHOWING RATING, SIZE AND WIRING METHOD FOR THE NEW
 ELECTRICAL CIRCUITS. NEC 210.3
 A GFCI GENERAL PURPOSE RECEPTACLE MUST BE INSTALLED AT
 AN ACCESSIBLE LOCATION FOR THE SERVICE OF HEATING, AIR
 CONDITIONING, AND REFRIGERATION EQUIPMENT. NEC 210.63
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES
 AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL
 FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3,
 EXISTING BUILDING CODE 711.1
  
 NOTE:
 SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE
 ALARM SYSTEM, VOICE AND DATA.
  
  
  
 ROBERT LECKY, CBO
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-04-24 Cont ID  
Sent By wjolin Date 2012-04-24 Time 10:03 Rev Time 0.00
Received By wjolin Date 2012-04-24 Time 09:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-04-05 Cont ID  
Sent By ddaniels Date 2012-04-05 Time 12:09 Rev Time 0.00
Received By ddaniels Date 2012-04-05 Time 12:09 Sent To E
Notes
2012-04-05 12:20:40FIRE DEPARTMENT REVIEW ***DENIED***
 ADDRESS:3330 45TH STREET SUITE A
 PERMIT # 12030654
 CONTRACTOR: CAREY CONSTRUCTION COMPANY
 PHONE: 561 746-1440
  
 1.) ADDRESS ON PLANS DOES NOT MATCH THE ADDRESS ON THE
 PERMIT APPLICATION.
 2.) DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE
 FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA
 EDITION OF NFPA 1 AND NFPA 101.
 3.) ALL DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY.
 4.) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
 5.) EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL
 BE PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING
 READING FIRE/SMOKE BARRIER?PROTECT ALL OPENINGS.
 CHARACTERS SHALL BE AT LEAST 4-INCHES IN HEIGHT AND
 HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE SPACED NOT
 MORE THAN 15 FEET ON CENTER. REFERENCE SECTION 8.3.2.4
 OF FLORIDA FIRE PREVENTION CODE ? NFPA 101
 6.) PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY
 SHALL BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
 REFERENCE SECTION 8.3.5.1 OF FLORIDA FIRE PREVENTION
 CODE ? NFPA 101
  
  
 DERRICK L. DANIELS, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6722
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-04-10 Cont ID  
Sent By shill Date 2012-04-10 Time 15:32 Rev Time 0.00
Received By shill Date 2012-03-28 Time 14:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2012-04-10 Cont ID  
Sent By jroach Date 2012-04-10 Time 14:42 Rev Time 0.00
Received By jroach Date 2012-04-10 Time 14:33 Sent To  
Notes
***NONE***