Plan Review Details - Permit 12030619
Plan Review Stops For Permit 12030619
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-04-17 Cont ID  
Sent By wjolin Date 2012-04-17 Time 11:37 Rev Time 0.00
Received By wjolin Date 2012-04-17 Time 09:27 Sent To M
Notes
2012-04-17 11:37:381221 ANDREWS ROAD
 PERMIT #12030619
  
 REVIEW COMMENTS - FIRE DEPARTMENT
 1) DUST EXPLOSION AND FIRE PREVENTION SHALL CONFORM TO
 THE REQUIREMENTS OF CHAPTER 40 OF THE FLORIDA FIRE
 PREVENTION CODE (NFPA 1 FLORIDA EDITION).
 2) INDICATE IF ANY HOODS OR ENCLOSURES WILL BE USED
 WITH THE EQUIPMENT (SAWS, SANDERS) TO INCREASE THE
 EFFECIENCY OF DUST COLLECTION SYSTEM.
 3) INDICATE HOW THE DUCTWORK CONVEYING THE COMBUSTIBLE
 DUST WILL BE PROTECTED AGAINST FIRE OR DEFLAGRATION
 HAZARDS PER NFPA 664.
 4) DUCTWORK, WOODWORKING EQUIPMENT, AND DUST COLLECTORS
 NEED TO BE BONDED AND GROUNDED TO PREVENT STATIC
 ELECTRICITY AS AN IGNITION SOURCE
 5) DETAIL "A" NOT PROVIDED ON MECHANICAL SHEET.
 6) THE SUBMITTED DOCUMENTS REFERENCE AN EXCEPTION TO
 THE SPRINKLER REQUIREMENT FOUND IN NFPA 664 SECTION
 8.2.2.5.2; HOWEVER, THE IRD DUST COLLECTOR (MODEL
 460-IRD-20) INDICATES A FLOW RATE GREATER THAN 5000
 CFM.
 7) IN ADDITION TO EXIT SIGNS, EMERGENCY LIGHTING SHALL
 BE PROVIDED. RECOMMEND COMBINATION EXIT SIGN/EMERGENCY
 LIGHT FIXTURES.
  
 NOTES:
 1) WOODWORKING FACILITIES LARGER THAN 2,500 SQ.FT. ARE
 REQUIRED TO BE PROTECTED BY AN AUTOMATIC SPRINKLER
 SYSTEM.
 2) THIS ADDRESS DOES NOT HAVE A CURRENT BUSINESS TAX
 RECEIPT FROM THE CITY OF WEST PALM BEACH.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-04-25 Cont ID  
Sent By hmoser Date 2012-04-25 Time 13:22 Rev Time 0.00
Received By hmoser Date 2012-03-26 Time 13:32 Sent To  
Notes
2012-04-12 15:54:234/12/12 IN FIRE BOX
2012-03-27 13:33:14SENT TO MARTINEZ'S DESK FOR PROCESSING. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-04-25 Cont ID  
Sent By hmoser Date 2012-04-25 Time 13:19 Rev Time 0.00
Received By hmoser Date 2012-04-25 Time 13:19 Sent To  
Notes
2012-04-25 13:21:46PLANS DENIED
 DUST IN THE COLLECTOR MUST BE PROTECTED FROM FIRE.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]