Plan Review Details - Permit 12030385
Plan Review Stops For Permit 12030385
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-04-19 Cont ID  
Sent By rlecky Date 2012-04-19 Time 14:25 Rev Time 0.00
Received By rlecky Date 2012-04-19 Time 14:20 Sent To  
Notes
2012-04-19 14:25:22PROVIDE SIGNED AND SEALED WIND LOAD ENGINEERING
 CALCULATIONS FOR THE POLE AND FIXTURE. PROVIDE
 STRUCTURAL DETAIL FOR INSTALLATION SUITABLE TO WITH
 STAND A WIND LOAD OF 140 MPH WITH EXPOSURE C.
  
 ROBERT LECKY
 PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-04-19 Cont ID  
Sent By rlecky Date 2012-04-19 Time 14:30 Rev Time 0.00
Received By rlecky Date 2012-04-19 Time 14:15 Sent To  
Notes
2012-04-19 14:28:05PROVIDE ELECTRICAL INFORMATION DETAILING THE SIZE OF
 THE BRANCH CIRCUIT, WIRING METHOD, CONDUIT BURIAL
 DEPTH, LOCATION OF POLES, ETC.
  
 ROBERT LECKY, CBO
 PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-04-19 Cont ID  
Sent By rlecky Date 2012-04-19 Time 14:30 Rev Time 0.00
Received By rlecky Date 2012-03-14 Time 16:28 Sent To  
Notes
2012-03-14 16:28:16ZONING

Review Stop Z ZONING
Rev No 1 Status F Date 2012-04-11 Cont ID  
Sent By lfranco Date 2012-04-11 Time 20:14 Rev Time 0.00
Received By lfranco Date 2012-03-19 Time 16:23 Sent To  
Notes
2012-04-11 20:16:09PLANNING: *** FAILED ****
  
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. PROVIDE LOCATION OF NEW PROPOSED LIGHTS. THE PLANS
 SHOW THE PHOTOMETRICS, BUT THE LIGHTS ARE NOT CLEARLY
 LOCATED OR DELINIATED.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO, AICP
 SENIOR PLANNER
 PLANNING DIVISION
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
2012-03-19 16:23:48GIVEN TO LF