Plan Review Details - Permit 12030365
Plan Review Stops For Permit 12030365
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-07-26 Cont ID  
Sent By jgomez Date 2012-07-25 Time 14:46 Rev Time 0.00
Received By jgomez Date 2012-07-25 Time 14:45 Sent To  
Notes
2012-07-25 14:46:53BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE CURRENT ICC-ES EVALUATION REPORT ESR-2478
 FOR GACO GREEN 052 SPRAY APPLIED FOAM. ONE SUBMITTED
 EXPIRED IN AUGUST 2010.
 ***NOTE: ENGINEER OF RECORD TO REVIEW AND APPROVE IN
 WRITING PRIOR TO SUBMITTAL.
  
 2- SHEET A-1: ENGINEER TO REVISE ALTERATION LEVEL. THIS
 IS ALTERATION LEVEL 3 NOT 1.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) CLAY TILE ADHESIVE. (QUIKRETE ROOFTILE MORTAR CAN'T
 BE USED ABOVE 15' HEIGHT).
 B) ALL THE SIMPSON STRUCTURAL COMPONENTS SPECIFIED ON
 PLANS AND DETAILS AS REQUIRED BY DCA RULE 9N-3.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-04-25 Cont ID  
Sent By jgomez Date 2012-04-25 Time 15:55 Rev Time 0.00
Received By jgomez Date 2012-04-24 Time 14:25 Sent To  
Notes
2012-04-25 16:04:48RESIDENTIAL (R3) RENOVATION BUILDING REVIEW COMMENTS.
 2007 FBC-EXISTING BUILDING. FLORIDA RESIDENTIAL CODE
 WITH 2009 REVISIONS.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.3. COORDINATE INFORMATION WITH ITEM #2 BELOW.
 PLEASE MAKE SURE ALL THE INFORMATION IS COMPLETED IN
 THE FORM AND OWNER/AGENT SIGNS AND DATES FORM ALSO.
  
 2- SEC R806.1 REQUIRES ROOF VENTILATION. OTHERWISE
 UNVENTED ATTIC NEEDS TO BE DESIGNED BY AN ARCHITECT OR
 ENGINEER. ENGINEER OF RECORD TO PROVIDE COMPLETE
 DETAIL/S SPECS ON PLANS AS REQUIRED BY SEC. R806.1 AND
 R806.4.
  
 3- PROVIDE CURRENT ESR REPORT FOR THE ICYNENE
 INSULATION TO BE INSTALLED. REPORT SUBMITTED IS
 EXPIRED. VISIT THE ICC WEBSITE AND DOWNLOAD CURRENT
 REPORT.
  
 4- FLAT ROOF PRODUCT APPROVAL: PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS (2 COPIES) AS REQUIRED BY
 GENERAL LIMITATION #7 ON LAST PAGE OF NOA 09-0224.01
 SUBMITTED. NEED CALCULATIONS TO MEET THE DESIGN
 PRESSURES REQUIRED BY SEC. R301.2.1.4.3.
  
 5- SHEET A-1:
 A) SPECIFY EMERGENCY EGRESS FROM MASTER BEDROOM AS
 REQUIRED BY SEC. R310. SPECIFY WINDOW WIDTH, WINDOW
 HEIGHT AND TOTAL CLEAR OPEN AREA.
  
 B) IDENTIFY EGRESS WINDOWS ON FIRST FLOOR BEDROOMS
 WINDOWS TO VERIFY COMPLIANCE WITH SEC. R310.
  
 C) DESIGN PARAMETERS. REVISE ALTERATION TYPE SPECIFIED.
 THIS IS NOT ALTERATION TYPE II. SEE CHAPTER 4 OF 2007
 FBC-EXISTING BUILDING AND REVISE CLASSIFICATION OF WORK
 AS REQUIRED.
  
 6- SPECIFY SAFETY GLASS FOR WINDOW IN NOOK AREA, MASTER
 BATHROOM WINDOWS BY THE TUB AREA AS REQUIRED BY SEC.
 R308.4
  
 7- SHEET S-1: SPECIFY OVERFLOW SCUPPERS AS REQUIRED BY
 SEC. R903.4.1.
  
 8- SHEET S-2: REVISE DETAIL 1/S-2. RISER AND TREAD
 RATIO DOESN'T COMPLY WITH SEC. R311.5.3.2.
  
 9- DRAWINGS S-2 AND S-3 ARE MISSING ENGINEER'S SEAL AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE. ONLY ONE SET
 OF PLANS HAS THE SEAL. NEED SEAL ON THE OTHER SET.
  
 10- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR ALL THE
 SIMPSON STRUCTURAL COMPONENTS SPECIFIED ON PLANS AND
 DETAILS AS REQUIRED BY DCA RULE 9N-3.
  
 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 12- PROVIDE COMPLETE DETAIL/SPECIFICATIONS FOR NEW
 TRELLIS SHOWN ON SHEET SP-1. NO INFORMATION WAS
 SUBMITTED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-04-03 Cont ID  
Sent By rlecky Date 2012-04-03 Time 11:38 Rev Time 0.00
Received By rlecky Date 2012-04-03 Time 10:09 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2012-04-25 Cont ID  
Sent By jgomez Date 2012-04-25 Time 11:36 Rev Time 0.00
Received By jgomez Date 2012-04-25 Time 11:36 Sent To  
Notes
2012-04-25 11:41:08CONTRACTOR NEEDS TO SIGN THE PERMIT APPLICATION TO
 OBTAIN THE SEPARATE GAS PERMIT.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2012-07-18 Cont ID  
Sent By jwitmer Date 2012-07-18 Time 13:32 Rev Time 0.00
Received By jwitmer Date 2012-07-17 Time 13:32 Sent To  
Notes
2012-07-18 13:33:18SEE HISTORIC APPROVAL ON PLANS. JW

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2012-03-27 Cont ID  
Sent By fmittner Date 2012-03-27 Time 11:29 Rev Time 0.00
Received By fmittner Date 2012-03-27 Time 11:29 Sent To  
Notes
2012-03-27 11:30:37SOME WINDOWS HAVE BEEN CHANGED FROM WHAT WAS APPROVED
 BY THE HPB. FRIEDERIKE LEFT MESSAGE WITH CONTRACTOR AND
 ARCHITECT TO EXPLAIN DIFFERENCES. PLEASE REVISE TO WHAT
 WAS APPROVED BY BOARD. QUESTIONS CONTACT FRIEDERIKE
 MITTNER AT 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-07-27 Cont ID  
Sent By jgomez Date 2012-07-27 Time 13:38 Rev Time 0.00
Received By jgomez Date 2012-07-17 Time 17:10 Sent To  
Notes
2012-07-26 17:11:34SENT TO R9 SHELF FOR REVIEW. ELECTRICAL SHEETS WERE
 REVISED. JG.
2012-07-18 13:33:44INCOMING SENT TO J. GOMEZ DESK . JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-04-25 Cont ID  
Sent By jgomez Date 2012-04-25 Time 17:42 Rev Time 0.00
Received By jgomez Date 2012-03-27 Time 16:40 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2012-04-24 Cont ID  
Sent By jgomez Date 2012-04-24 Time 14:48 Rev Time 0.00
Received By jgomez Date 2012-04-24 Time 14:48 Sent To  
Notes
2012-04-24 14:49:16NO IMPACT FEES DUE. PLANS STAMPED ON 3/14/12.
 MU2012-4460-0000.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-07-27 Cont ID  
Sent By jgomez Date 2012-07-27 Time 13:46 Rev Time 0.00
Received By jgomez Date 2012-07-27 Time 13:46 Sent To  
Notes
2012-07-27 13:47:58MECHANICAL REVIEW PROVISO:
  
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY
 SEC. N1107.AB.1.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-04-25 Cont ID  
Sent By jgomez Date 2012-04-25 Time 11:49 Rev Time 0.00
Received By jgomez Date 2012-04-25 Time 11:49 Sent To  
Notes
2012-04-25 11:51:35RESIDENTIAL (R3) MECHANICAL REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE.
  
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY
 SEC. N1107.AB.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-04-24 Cont ID  
Sent By jgomez Date 2012-04-24 Time 16:15 Rev Time 0.00
Received By jgomez Date 2012-04-24 Time 16:15 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2012-03-27 Cont ID  
Sent By fmittner Date 2012-03-27 Time 11:28 Rev Time 0.00
Received By fmittner Date 2012-03-27 Time 11:28 Sent To  
Notes
***NONE***