Plan Review Stops For Permit 12030309 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2012-06-01 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2012-06-01 |
Time |
10:56 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2012-06-01 |
Time |
08:00 |
Sent To |
|
|
Notes |
2012-06-01 11:26:34 | BUILDING PLAN REVIEW | | PERMIT: 12030309 | | ADD: 2047 PALM BEACH LAKES | | CONT: LEIGHTON MCGINN | | TEL: (561)722-9697 | | | | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS | | * WEST PALM BEACH AMENDMENTS | | | | BUILDING APPROVED WITH EXCEPTION! | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE | | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. | | | | 1) SHEET A6 DETAIL #1 OVERFLOW SCUPPER LOCATION ALLOWS | | FOR 6" OF PONDING WHEN THE MAIN SCUPPERS ARE BLOCKED, | | SECTION 1503.4.3 ALLOWS FOR 2-4 INCHES OF PONDING | | MAXIMUM. REVISION IS REQUIRED BY THE ROOF SHEATHING | | INSPECTION. | | | | 1503.4.3 OVERFLOW SCUPPERS. WHEN OTHER MEANS OF | | DRAINAGE OF OVERFLOW WATER IS NOT PROVIDED, OVERFLOW | | SCUPPERS SHALL BE PLACED IN WALLS OR PARAPETS NOT LESS | | THAN 2 INCHES (51 MM) NOR MORE THAN 4 INCHES (102 MM) | | ABOVE THE FINISHED ROOF COVERING AND SHALL BE LOCATED | | AS CLOSE AS PRACTICAL TO REQUIRED VERTICAL LEADERS OR | | DOWNSPOUTS OR WALL AND PARAPET SCUPPERS. AN OVERFLOW | | SCUPPER SHALL BE SIZED IN ACCORDANCE WITH THE FLORIDA | | BUILDING CODE, PLUMBING. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | | | CONTRACTOR TO COLAGATE PLANS BEFORE ISSUANCE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2012-03-28 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2012-03-28 |
Time |
16:16 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2012-03-28 |
Time |
13:52 |
Sent To |
|
|
Notes |
2012-03-28 15:37:04 | BUILDING PLAN REVIEW | | PERMIT: 12030309 | | ADD: 2047 PALM BEACH LAKES | | CONT: LEIGHTON MCGINN | | TEL: (561)722-9697 | | | | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS | | * WEST PALM BEACH AMENDMENTS | | | | 2007 EXISTING BUILDING CODE LEVEL II 701.3 | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | ACTION: DENIED | | | | 1) LIFE SAFETY PLAN UNDER THE HEADING BUILDING CODE | | REQUIREMENTS PLEASE PROVIDE A COMPLIANCE METHOD 2007/09 | | EXISTING BUILDING CODE 101.5. | | | | 2) SHEET A1 INDICATES THREE 1 HOUR FIRE RATED WALLS BUT | | THERE IS NO WALL TAG IDENTIFYING MARKERS FOR SUCH WALLS | | FOUND ON THIS SHEET. | | | | 3) SHEET A1 THE DOORS LOCATED WITHIN THE FIRE RATED | | WALLS DO NOT SHOW ON THE DOOR SCHEDULE SHEET A4. | | | | 4) SHEET A1 THE HANDICAPPED TOLIET ROOM # 109 IT | | APPEARS THE DOOR IS SWINGING OVER THE CLEAR FLOOR SPACE | | FOR THE LAV AND WATER CLOSET. 11-4.22.2(1). | | | | 5) SHEET A1 INDICATES THE USE OF MEDICAL GAS PLEASE | | PROVIDE THE AMOUNT OF COMPRESSED GAS (CUBIC FT) TO BE | | BOTH USED AND STORED IN ROOM 134 TO SEE IF THIS MAY BE | | CONSIDERED A HAZARDOUS LOCATION AND OR A CONTROLED AREA | | REQUIRING A 1 HOUR SEPERATION. PLEASE PROVIDE MSDS | | SHEETS FOR ALL GASSES.2007/09 FBC-B 414.2 & 414.2.1 | | CONSTRUCTION REQUIREMENTS. | | | | 6) 421.3.12 FIRE ALARM SYSTEMS. 421.3.12.1 A FIRE ALARM | | ANNUNCIATOR PANEL SHALL BE PROVIDED PER FACILITY OR | | BUILDING AT A LOCATION THAT IS CONSTANTLY ATTENDED | | DURING THE FACILITY'S HOURS OF OPERATION AND SHALL | | ANNUNCIATE A FIRE ALARM FROM ANY MANUAL OR AUTOMATIC | | FIRE ALARM DEVICE. THE PANEL SHALL INDICATE THE ZONE OF | | ACTUATION OF THE ALARM, AND THERE SHALL BE A TROUBLE | | SIGNAL INDICATOR. EACH SMOKE COMPARTMENT SHALL BE | | ANNUNCIATED AS A SEPARATE FIRE ALARM ZONE. A FIRE ALARM | | SYSTEM ZONE SHALL NOT INCLUDE ROOMS OR SPACES IN OTHER | | SMOKE COMPARTMENTS AND SHALL BE LIMITED TO A MAXIMUM | | AREA OF 22,500 SQUARE FEET (2090 M2). | | | | 7) NEITHER IN THE STRUCTURAL NOR MECHANICAL PLANS ARE | | THERE ANCHORING DETAILS FOR THE FOUR ROOF TOP PACKAGE | | UNITS NOR TIE DOWN DETAILS FOR THE PACKAGE UNITS TO | | CURB. | | 2007/09 FBC-B 1609 . | | | | 8) A ROOFING CONTRACTOR IS SIGNED ON FOR THE ROOFING | | SUB-PERMIT AND ROOFING NOA 07-1203.01 FOR GAF RUBEROID, | | MODIFIED BITUMEN ROOF SYSTEMS FOR WOOD DECK, BUT NO | | SUB-SYSTEM WAS INDICATED WITHIN THE 30 PAGE REPORT. | | PLEASE NOTE THE ROOFING SUB-SYSTEMS GENERALLY HAVE A | | MAXIMUM DESIGN PRESSURE FROM 45-60 PSF AND A GENERAL | | LIMITATION # 7 WHICH DOES ALLOW FOR ENHANCED FASTENING | | IN ZONES 2 & 3 BY A FLORIDA REGISTERED PROFESSIONAL | | ENGINEER OR REGISTERED ARCHITECT. | | | | 9) SHEET A3 INDICATES THE USE OF SCUPPERS AND OVERFLOW | | SCUPPERS, THIS SHEET PROVIDES THE HEIGHT OF THE | | SCUPPERS AND OVER FLOW BUT NOT THE WIDTH, FBC-B | | 1503.4.3 OVERFLOW SCUPPERS SHALL BE SIZED IN ACCORDANCE | | WITH THE FBC-PLUMBING, THERE ARE TWO SCUPPERS AND ONLY | | ONE OVERFLOW, PROVIDE CALCULATIONS FOR SIZING. | | | | 10) SHEEET A1 DOES NOT PROVIDE A LIFE SAFETY PLAN NOR | | EXIT SIGNAGE REQUIRED BY FBC-B 1006.3 BUT E2 DOES | | PROVIDE THE EXIT SIGNAGE INDICATING EXITING THROUGH TWO | | STORAGE AREA, | | SOILED HOLDING ROOM 114 AND MATERIALS MANAGEMENT AND | | DELIVERS ROOM 131. FBC-B 1014.2 EGRESS SHALL NOT PASS | | THROUGH STORAGE ROOMSCLOSETS OR SPACES USED FOR SIMILAR | | PURPOSES. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | CONSTRUCTION SERVICES HOME PAGE | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2012-07-13 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2012-07-13 |
Time |
15:55 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2012-07-13 |
Time |
14:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2012-05-31 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2012-05-31 |
Time |
10:50 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2012-05-23 |
Time |
08:58 |
Sent To |
|
|
Notes |
2012-05-31 10:50:18 | THURSDAY, MAY 31, 2012 | | 1203309 | | 2047 PALM BEACH LAKES BLVD. | | RENOVATIONS TO SURGERY CENTER | | | | PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL | | EQUIPMENT WHICH INCLUDES THE SPECIFIC WORDING REGARDING | | THE SIZE AND TYPE OF HAZARDS. 2008 NEC 110.22, 110.16 | | INDICATE ON THE PLANS THE REQUIREMENT FOR A SIGN WHICH | | INDICATES THE TYPE AND LOCATION OF THE ON SITE | | EMERGENCY POWER SOURCE. NEC 700.8 | | VERIFY THE GENERATOR IS A LEVEL 1, TYPE 10, CLASS 8. | | 2010 FBC 421.3.13 | | PROVIDE A WIRING METHOD TO CONNECT A PORTABLE OR | | TEMPORARY ALTERNATE SOURCE OF POWER AS REQUIRED | | WHENEVER THE EMERGENCY GENERATOR IS OUT OF SERVICE FOR | | MAJOR MAINTENANCE OR REPAIR. NEC 700.5(B) | | | | | | ROBERT LECKY, CBO | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2012-03-26 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2012-03-26 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2012-03-26 |
Time |
12:58 |
Sent To |
|
|
Notes |
2012-03-26 15:27:12 | 1203309 | | 2047 PALM BEACH LAKES BLVD. | | RENOVATIONS TO SURGERY CENTER | | | | | | PROVIDE PANEL SCHEDULES AND A SUMMARY LOAD CALCULATION. | | LOCATE THE GENERATOR ON THE SITE PLAN. NEC 215.5 | | SPECIFY ON THE PLANS THE REQUIRED WIRING METHODS | | SUITABLE FOR HEALTH CARE FACILITIES. INCLUDE NUMBER OF | | RECEPTACLES AND TYPES LOCATED AT EACH PATIENT CARE | | AREA. SPECIFY THE BRANCHS IE. LS, CR OR EQ. INDICATE | | THE LIFE SAFETY BRANCH AND CRITICAL BRANCH OF THE | | EMERGENCY SYSTEM ARE TO BE INDEPENDENT OF ALL OTHER | | WIRING. NEC 517 | | PROVIDE A DETAIL VERIFYING THE REQUIRED WORKING | | CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN | | PROVIDED FOR THE ELECTRICAL EQUIPMENT AND PANEL BOARDS. | | NEC 110.26, 240.24, | | PROVIDE A LIGHTING DENSITY CALCULATION SHOWING | | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE | | REQUIREMENTS. FBC 13-415 ABC.5 | | SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE | | CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES. | | SPACE CONTROL FBC 13-415 ABC.1.2.; ADDITIONAL CONTROLS | | 13-415.ABC.1.3 | | | | PLANS ARE NOT CLEAR AS TO THE SCOPE OF THE NEW ELECTRIC | | WORK. A TYPE I ESSENTIAL ELECTRIC SYSTEM REQUIRES A | | REMOTE GENERATOR ANNUNCIATOR. THE EMERGENCY AND NORMAL | | ELECTRIC SERVICE MAINS REQUIRE SEPARATE ROOMS. SHEET E5 | | APPEARS INCOMPLETE. | | | | NOTE: | | SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE | | ALARM SYSTEM, LIGHTNING PROTECTION, NURSE CALL, VOICE | | AND DATA. | | | | | | ROBERT LECKY, CBO | | PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2012-06-05 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2012-06-05 |
Time |
13:33 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2012-06-05 |
Time |
11:13 |
Sent To |
|
|
Notes |
2012-06-05 13:33:45 | 2047 PALM BEACH LAKES BOULEVARD | | PERMIT #12030309 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | *****PROVISO***** | | | | PLEASE SUBMIT THE ENIGNEERED CIVIL DRAWINGS SHOWING THE | | UNDERGROUND FIRE SERVICE MAIN, FIRE DEPARTMENT | | CONNECTION, UNDERGROUND CITY WATER SUPPLY, NEAREST FIRE | | HYDRANTS, BACKFLOW PREVENTION ASSEMBLY, ETC. | | | | WESLEY JOLIN | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2012-04-03 |
|
|
Cont ID |
|
Sent By |
ddaniels |
Date |
2012-04-03 |
Time |
10:09 |
Rev Time |
0.00 |
Received By |
ddaniels |
Date |
2012-04-03 |
Time |
10:08 |
Sent To |
|
|
Notes |
2012-04-03 10:14:02 | | | FIRE DEPARTMENT REVIEW ***DENIED**** | | ADDRESS:2047 PALM BEACH LAKES BOULEVARD | | PERMIT # 12030309 | | CONTRACTOR: LEIGHTON MCGINN | | PHONE: 561 863-4455 | | | | 1.) THE SCOPE OF WORK SHALL BE INDICATED ON PLANS. | | 2.) DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE | | FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA | | EDITION OF NFPA 1 AND NFPA 101. | | 3.) ALL DEMOLITION WORK SHALL CONFORM TO THE | | REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS | | SHALL BE REMOVED FROM THE SITE DAILY. | | 4.) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | SYSTEM AND/OR FIRE ALARM SYSTEM. | | 5.) PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY | | TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, | | EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF | | TRAVEL ETC. | | 6.) PER FLORIDA ADMINISTRATIVE CODE SECTION | | 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS | | SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER | | SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE | | TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR | | EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN | | DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT | | FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION | | SUCH AS PRE-ENGINEERED SYSTEMS. | | | | | | DERRICK L. DANIELS, BATTALION CHIEF | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | (561) 805-6722 | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2012-07-24 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2012-07-24 |
Time |
16:52 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2012-06-28 |
Time |
13:57 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2012-06-07 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2012-06-07 |
Time |
17:49 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2012-05-15 |
Time |
17:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2012-04-12 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2012-04-12 |
Time |
10:32 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2012-03-14 |
Time |
16:44 |
Sent To |
|
|
Notes |
2012-03-14 16:46:11 | SENT TO C24 SHELF FOR REVIEW. JG. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2012-07-19 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2012-07-19 |
Time |
13:56 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2012-07-19 |
Time |
10:50 |
Sent To |
|
|
Notes |
2012-07-19 13:56:47 | PASS PROVISO | | 1) PROVIDE LETTER FROM THE ENGINEER SHOWING A COMPLETE | | DETAIL ON THE RTU CURB | | AND EXHAUST FAN CURB TIE DOWN TO ROOF. AND THE | | EQUIPMENT | | TIE DOWN TO CURB. ( BOLT SIZE HOW FAR APART THE BOLTS | | SHOULD BE) | | PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M) | | AT FIRST INSPECTION | | 2) PROVIDE A LETTER FROM THE ENGINEER SHOWING EQUIPMENT | | SCHEDULE. | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2012-06-05 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2012-06-05 |
Time |
10:22 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2012-06-05 |
Time |
10:22 |
Sent To |
|
|
Notes |
2012-06-05 10:25:45 | CAN NOT COMPLETE REVIEW LIFE SAFETY PLAN | | AND MECHANICAL PLAN DO NOT MATCH. | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2012-03-26 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2012-03-26 |
Time |
08:47 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2012-03-26 |
Time |
08:19 |
Sent To |
|
|
Notes |
2012-03-26 08:47:04 | PLANS DENIED | | 1) NO AIR CONDITIONING DUCT PLANS SUBMITTED WITH PLANS. | | SECTION 106 FBC 2007. | | 2) LIFE SAFETY PLAN PAGE LS 2 AND MECHANICAL FLOOR PLAN | | PAGE M 2 DO NOT MATCH. | | 3) PROVIDE A COMPLETE SET OF MECHANICAL PLANS . | | PLAN REVIEW BY HAROLD MOSER. | | 561-805-6732 | | [email protected] |
|
|
Review Stop |
MEDGAS |
MEDICAL GAS |
Rev No |
1 |
Status |
P |
Date |
2012-06-04 |
|
|
Cont ID |
|
Sent By |
lwagner |
Date |
2012-06-04 |
Time |
13:10 |
Rev Time |
0.00 |
Received By |
lwagner |
Date |
2012-06-01 |
Time |
14:15 |
Sent To |
|
|
Notes |
2012-06-04 13:12:24 | PRODUCT DETAILS FOR VACUUM PUMP, OXYGEN ENCLOSURE, AND | | STERILIZER REQUIRED. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2012-06-01 |
|
|
Cont ID |
|
Sent By |
lwagner |
Date |
2012-06-01 |
Time |
14:14 |
Rev Time |
0.00 |
Received By |
lwagner |
Date |
2012-06-01 |
Time |
13:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2012-03-19 |
|
|
Cont ID |
|
Sent By |
lwagner |
Date |
2012-03-19 |
Time |
15:14 |
Rev Time |
0.00 |
Received By |
lwagner |
Date |
2012-03-19 |
Time |
08:01 |
Sent To |
|
|
Notes |
2012-03-19 14:05:33 | FBC 2007 PLUMBING REVIEW #1 | | DENIED: | | | | PLEASE INCLUDE MISSING PLUMBING DRAWINGS: | | 1. SHEET P-1 DRAWING LIST : P-3, P-4, AND P-6 WERE NOT | | INCLUDED WITH THIS SET OF DRAWINGS. | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2012-07-19 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2012-07-19 |
Time |
15:40 |
Rev Time |
0.00 |
Received By |
lfranco |
Date |
2012-07-17 |
Time |
11:01 |
Sent To |
|
|
Notes |
2012-07-20 13:03:55 | PLANNING: ***** PASSED WITH PROVISO, PRIOR TO FINAL | | INSPECTION OF THE SITE, THE APPLICANT SHALL APPLY FOR A | | SEPARATE LANDSCAPE AND IRRIGATION PERMIT. TWO COPIES OF | | THE LANDSCAPE PLAN AND A CERTIFIED COST ESTIMATE THAT | | INCLUDES THE TOTAL COST OF ALL LANDSCAPE MATERIALS AND | | LABOR, BROKEN DOWN INTO UNIT COST SHALL BE SUBMITTED | | WITH THE LANDSCAPE PERMIT APPLICATION. | | THIS PERMIT IS ONLY FOR THE GENERATOR AND GENERATOR | | ENCLOSURE (WALL). | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME. | | | | LINDA MIA FRANCO, AICP | | SENIOR PLANNER | | PLANNING DIVISION | | TEL: (561) 822-1443 | | EMAIL: [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2012-06-06 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2012-06-06 |
Time |
20:40 |
Rev Time |
0.50 |
Received By |
lfranco |
Date |
2012-06-06 |
Time |
20:40 |
Sent To |
|
|
Notes |
2012-06-06 20:44:06 | PLANNING: ***** FAILED *****] | | | | | | 1, RESPOND TO COMMENTS IN WRITING WHEN RESUBMITING | | DOCUMENTS. | | | | 2. THE SCOPE OF WORK DENOTES ALL INTERIOR WORK AND | | RENOVATIONS, HOWEVER, SHEET E1, PLAN NOTES CALLS OUT | | FOR A PROPOSED ASC GENERATOR. THERE ARE NO CIVIL | | DRAWINGS THAT SHOW THIS GENERATOR OR ENCLOSURE. IS | | THERE A NEW GENERATOR PROPOSED? | | | | IF SO, PROVIDE THE FOLLOWING INFORMATION: | | | | A. INDICATE SETBACK DIMENSIONS FROM PROPOSED GENERATOR | | EQUIPMENT TO ALL PROPERTY LINES. PURSUANT TO SECTION | | 94-305(B)(4) OF THE ZLDR: MECHANICAL EQUIPMENT MAY NOT | | PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK. | | | | RESUBMITTAL: DIMENSIONS WERE NOT PROVIDED ON SITE PLAN | | SP-1 OR LP-1. | | | | B. PROVIDE ELEVATIONS AND A FLOOR PLAN OF SCREENING AND | | LANDSCAPING DETAIL. INCLUDE WALL HEIGHT, ETC. SCREENING | | ENCLOSURE AND LANDSCAPING SHALL MEET SECTION 94-444 OF | | THE ZONING AND LAND DEVELOPMENT REGULATIONS. SCREENING | | WALLS SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES | | PLANTED AT TWO-FOOT INTERVALS. OR PROVIDE INFORMATION | | OF EXISTING ENCLOSURE THAT MEETS THE REQUIREMENTS | | ABOVE. | | | | RESUBMITTAL: ELEVATIONS WERE NOT PROVIDED. PROVIDE A | | CROSS SECTION OF THE PROPOSED ENCLOSURE, GENERATOR | | (INCLUDING THE MOUNTING AND TANK), THE ENTIRE GENERATOR | | EQUIPMENT NEEDS TO BE SCREENED FROM VIEW. PROVIDE TOTAL | | HEIGHT DIMENSIONS OF FENCE ENCLOSURE AND GENERATOR. | | | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME. | | | | LINDA MIA FRANCO, AICP | | SENIOR PLANNER | | PLANNING DIVISION | | TEL: (561) 822-1443 | | EMAIL: [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2012-04-11 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2012-04-11 |
Time |
19:36 |
Rev Time |
0.50 |
Received By |
lfranco |
Date |
2012-04-11 |
Time |
19:36 |
Sent To |
|
|
Notes |
2012-04-11 19:41:40 | PLANNING: ***** FAILED *****] | | | | | | 1, RESPOND TO COMMENTS IN WRITING. | | | | 2. THE SCOPE OF WORK DENOTES ALL INTERIOR WORK AND | | RENOVATIONS, HOWEVER, SHEET E1, PLAN NOTES CALLS OUT | | FOR A PROPOSED ASC GENERATOR. THERE ARE NO CIVIL | | DRAWINGS THAT SHOW THIS GENERATOR OR ENCLOSURE. IS | | THERE A NEW GENERATOR PROPOSED? | | | | IF SO, PROVIDE THE FOLLOWING INFORMATION: | | | | A. INDICATE SETBACK DIMENSIONS FROM PROPOSED GENERATOR | | EQUIPMENT TO ALL PROPERTY LINES. PURSUANT TO SECTION | | 94-305(B)(4) OF THE ZLDR: MECHANICAL EQUIPMENT MAY NOT | | PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK. | | | | B. PROVIDE ELEVATIONS AND A FLOOR PLAN OF SCREENING AND | | LANDSCAPING DETAIL. INCLUDE WALL HEIGHT, ETC. SCREENING | | ENCLOSURE AND LANDSCAPING SHALL MEET SECTION 94-444 OF | | THE ZONING AND LAND DEVELOPMENT REGULATIONS. SCREENING | | WALLS SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES | | PLANTED AT TWO-FOOT INTERVALS. OR PROVIDE INFORMATION | | OF EXISTING ENCLOSURE THAT MEETS THE REQUIREMENTS | | ABOVE. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME. | | | | LINDA MIA FRANCO, AICP | | SENIOR PLANNER | | PLANNING DIVISION | | TEL: (561) 822-1443 | | EMAIL: [email protected] | | |
|
|