Plan Review Details - Permit 12030309
Plan Review Stops For Permit 12030309
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-06-01 Cont ID  
Sent By jwitmer Date 2012-06-01 Time 10:56 Rev Time 0.00
Received By jwitmer Date 2012-06-01 Time 08:00 Sent To  
Notes
2012-06-01 11:26:34BUILDING PLAN REVIEW
 PERMIT: 12030309
 ADD: 2047 PALM BEACH LAKES
 CONT: LEIGHTON MCGINN
 TEL: (561)722-9697
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET A6 DETAIL #1 OVERFLOW SCUPPER LOCATION ALLOWS
 FOR 6" OF PONDING WHEN THE MAIN SCUPPERS ARE BLOCKED,
 SECTION 1503.4.3 ALLOWS FOR 2-4 INCHES OF PONDING
 MAXIMUM. REVISION IS REQUIRED BY THE ROOF SHEATHING
 INSPECTION.
  
 1503.4.3 OVERFLOW SCUPPERS. WHEN OTHER MEANS OF
 DRAINAGE OF OVERFLOW WATER IS NOT PROVIDED, OVERFLOW
 SCUPPERS SHALL BE PLACED IN WALLS OR PARAPETS NOT LESS
 THAN 2 INCHES (51 MM) NOR MORE THAN 4 INCHES (102 MM)
 ABOVE THE FINISHED ROOF COVERING AND SHALL BE LOCATED
 AS CLOSE AS PRACTICAL TO REQUIRED VERTICAL LEADERS OR
 DOWNSPOUTS OR WALL AND PARAPET SCUPPERS. AN OVERFLOW
 SCUPPER SHALL BE SIZED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, PLUMBING.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
 CONTRACTOR TO COLAGATE PLANS BEFORE ISSUANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-03-28 Cont ID  
Sent By jwitmer Date 2012-03-28 Time 16:16 Rev Time 0.00
Received By jwitmer Date 2012-03-28 Time 13:52 Sent To  
Notes
2012-03-28 15:37:04BUILDING PLAN REVIEW
 PERMIT: 12030309
 ADD: 2047 PALM BEACH LAKES
 CONT: LEIGHTON MCGINN
 TEL: (561)722-9697
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) LIFE SAFETY PLAN UNDER THE HEADING BUILDING CODE
 REQUIREMENTS PLEASE PROVIDE A COMPLIANCE METHOD 2007/09
 EXISTING BUILDING CODE 101.5.
  
 2) SHEET A1 INDICATES THREE 1 HOUR FIRE RATED WALLS BUT
 THERE IS NO WALL TAG IDENTIFYING MARKERS FOR SUCH WALLS
 FOUND ON THIS SHEET.
  
 3) SHEET A1 THE DOORS LOCATED WITHIN THE FIRE RATED
 WALLS DO NOT SHOW ON THE DOOR SCHEDULE SHEET A4.
  
 4) SHEET A1 THE HANDICAPPED TOLIET ROOM # 109 IT
 APPEARS THE DOOR IS SWINGING OVER THE CLEAR FLOOR SPACE
 FOR THE LAV AND WATER CLOSET. 11-4.22.2(1).
  
 5) SHEET A1 INDICATES THE USE OF MEDICAL GAS PLEASE
 PROVIDE THE AMOUNT OF COMPRESSED GAS (CUBIC FT) TO BE
 BOTH USED AND STORED IN ROOM 134 TO SEE IF THIS MAY BE
 CONSIDERED A HAZARDOUS LOCATION AND OR A CONTROLED AREA
 REQUIRING A 1 HOUR SEPERATION. PLEASE PROVIDE MSDS
 SHEETS FOR ALL GASSES.2007/09 FBC-B 414.2 & 414.2.1
 CONSTRUCTION REQUIREMENTS.
  
 6) 421.3.12 FIRE ALARM SYSTEMS. 421.3.12.1 A FIRE ALARM
 ANNUNCIATOR PANEL SHALL BE PROVIDED PER FACILITY OR
 BUILDING AT A LOCATION THAT IS CONSTANTLY ATTENDED
 DURING THE FACILITY'S HOURS OF OPERATION AND SHALL
 ANNUNCIATE A FIRE ALARM FROM ANY MANUAL OR AUTOMATIC
 FIRE ALARM DEVICE. THE PANEL SHALL INDICATE THE ZONE OF
 ACTUATION OF THE ALARM, AND THERE SHALL BE A TROUBLE
 SIGNAL INDICATOR. EACH SMOKE COMPARTMENT SHALL BE
 ANNUNCIATED AS A SEPARATE FIRE ALARM ZONE. A FIRE ALARM
 SYSTEM ZONE SHALL NOT INCLUDE ROOMS OR SPACES IN OTHER
 SMOKE COMPARTMENTS AND SHALL BE LIMITED TO A MAXIMUM
 AREA OF 22,500 SQUARE FEET (2090 M2).
  
 7) NEITHER IN THE STRUCTURAL NOR MECHANICAL PLANS ARE
 THERE ANCHORING DETAILS FOR THE FOUR ROOF TOP PACKAGE
 UNITS NOR TIE DOWN DETAILS FOR THE PACKAGE UNITS TO
 CURB.
 2007/09 FBC-B 1609 .
  
 8) A ROOFING CONTRACTOR IS SIGNED ON FOR THE ROOFING
 SUB-PERMIT AND ROOFING NOA 07-1203.01 FOR GAF RUBEROID,
 MODIFIED BITUMEN ROOF SYSTEMS FOR WOOD DECK, BUT NO
 SUB-SYSTEM WAS INDICATED WITHIN THE 30 PAGE REPORT.
 PLEASE NOTE THE ROOFING SUB-SYSTEMS GENERALLY HAVE A
 MAXIMUM DESIGN PRESSURE FROM 45-60 PSF AND A GENERAL
 LIMITATION # 7 WHICH DOES ALLOW FOR ENHANCED FASTENING
 IN ZONES 2 & 3 BY A FLORIDA REGISTERED PROFESSIONAL
 ENGINEER OR REGISTERED ARCHITECT.
  
 9) SHEET A3 INDICATES THE USE OF SCUPPERS AND OVERFLOW
 SCUPPERS, THIS SHEET PROVIDES THE HEIGHT OF THE
 SCUPPERS AND OVER FLOW BUT NOT THE WIDTH, FBC-B
 1503.4.3 OVERFLOW SCUPPERS SHALL BE SIZED IN ACCORDANCE
 WITH THE FBC-PLUMBING, THERE ARE TWO SCUPPERS AND ONLY
 ONE OVERFLOW, PROVIDE CALCULATIONS FOR SIZING.
  
 10) SHEEET A1 DOES NOT PROVIDE A LIFE SAFETY PLAN NOR
 EXIT SIGNAGE REQUIRED BY FBC-B 1006.3 BUT E2 DOES
 PROVIDE THE EXIT SIGNAGE INDICATING EXITING THROUGH TWO
 STORAGE AREA,
 SOILED HOLDING ROOM 114 AND MATERIALS MANAGEMENT AND
 DELIVERS ROOM 131. FBC-B 1014.2 EGRESS SHALL NOT PASS
 THROUGH STORAGE ROOMSCLOSETS OR SPACES USED FOR SIMILAR
 PURPOSES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2012-07-13 Cont ID  
Sent By rlecky Date 2012-07-13 Time 15:55 Rev Time 0.00
Received By rlecky Date 2012-07-13 Time 14:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2012-05-31 Cont ID  
Sent By rlecky Date 2012-05-31 Time 10:50 Rev Time 0.00
Received By rlecky Date 2012-05-23 Time 08:58 Sent To  
Notes
2012-05-31 10:50:18THURSDAY, MAY 31, 2012
 1203309
 2047 PALM BEACH LAKES BLVD.
 RENOVATIONS TO SURGERY CENTER
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 EQUIPMENT WHICH INCLUDES THE SPECIFIC WORDING REGARDING
 THE SIZE AND TYPE OF HAZARDS. 2008 NEC 110.22, 110.16
 INDICATE ON THE PLANS THE REQUIREMENT FOR A SIGN WHICH
 INDICATES THE TYPE AND LOCATION OF THE ON SITE
 EMERGENCY POWER SOURCE. NEC 700.8
 VERIFY THE GENERATOR IS A LEVEL 1, TYPE 10, CLASS 8.
 2010 FBC 421.3.13
 PROVIDE A WIRING METHOD TO CONNECT A PORTABLE OR
 TEMPORARY ALTERNATE SOURCE OF POWER AS REQUIRED
 WHENEVER THE EMERGENCY GENERATOR IS OUT OF SERVICE FOR
 MAJOR MAINTENANCE OR REPAIR. NEC 700.5(B)
  
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-03-26 Cont ID  
Sent By rlecky Date 2012-03-26 Time 15:26 Rev Time 0.00
Received By rlecky Date 2012-03-26 Time 12:58 Sent To  
Notes
2012-03-26 15:27:121203309
 2047 PALM BEACH LAKES BLVD.
 RENOVATIONS TO SURGERY CENTER
  
  
 PROVIDE PANEL SCHEDULES AND A SUMMARY LOAD CALCULATION.
 LOCATE THE GENERATOR ON THE SITE PLAN. NEC 215.5
 SPECIFY ON THE PLANS THE REQUIRED WIRING METHODS
 SUITABLE FOR HEALTH CARE FACILITIES. INCLUDE NUMBER OF
 RECEPTACLES AND TYPES LOCATED AT EACH PATIENT CARE
 AREA. SPECIFY THE BRANCHS IE. LS, CR OR EQ. INDICATE
 THE LIFE SAFETY BRANCH AND CRITICAL BRANCH OF THE
 EMERGENCY SYSTEM ARE TO BE INDEPENDENT OF ALL OTHER
 WIRING. NEC 517
 PROVIDE A DETAIL VERIFYING THE REQUIRED WORKING
 CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN
 PROVIDED FOR THE ELECTRICAL EQUIPMENT AND PANEL BOARDS.
 NEC 110.26, 240.24,
 PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.5
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES.
 SPACE CONTROL FBC 13-415 ABC.1.2.; ADDITIONAL CONTROLS
 13-415.ABC.1.3
  
 PLANS ARE NOT CLEAR AS TO THE SCOPE OF THE NEW ELECTRIC
 WORK. A TYPE I ESSENTIAL ELECTRIC SYSTEM REQUIRES A
 REMOTE GENERATOR ANNUNCIATOR. THE EMERGENCY AND NORMAL
 ELECTRIC SERVICE MAINS REQUIRE SEPARATE ROOMS. SHEET E5
 APPEARS INCOMPLETE.
  
 NOTE:
 SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE
 ALARM SYSTEM, LIGHTNING PROTECTION, NURSE CALL, VOICE
 AND DATA.
  
  
 ROBERT LECKY, CBO
 PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-06-05 Cont ID  
Sent By wjolin Date 2012-06-05 Time 13:33 Rev Time 0.00
Received By wjolin Date 2012-06-05 Time 11:13 Sent To  
Notes
2012-06-05 13:33:452047 PALM BEACH LAKES BOULEVARD
 PERMIT #12030309
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 PLEASE SUBMIT THE ENIGNEERED CIVIL DRAWINGS SHOWING THE
 UNDERGROUND FIRE SERVICE MAIN, FIRE DEPARTMENT
 CONNECTION, UNDERGROUND CITY WATER SUPPLY, NEAREST FIRE
 HYDRANTS, BACKFLOW PREVENTION ASSEMBLY, ETC.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-04-03 Cont ID  
Sent By ddaniels Date 2012-04-03 Time 10:09 Rev Time 0.00
Received By ddaniels Date 2012-04-03 Time 10:08 Sent To  
Notes
2012-04-03 10:14:02 
 FIRE DEPARTMENT REVIEW ***DENIED****
 ADDRESS:2047 PALM BEACH LAKES BOULEVARD
 PERMIT # 12030309
 CONTRACTOR: LEIGHTON MCGINN
 PHONE: 561 863-4455
  
 1.) THE SCOPE OF WORK SHALL BE INDICATED ON PLANS.
 2.) DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE
 FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA
 EDITION OF NFPA 1 AND NFPA 101.
 3.) ALL DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY.
 4.) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
 5.) PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
 6.) PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS
 SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER
 SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE
 TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR
 EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN
 DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT
 FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION
 SUCH AS PRE-ENGINEERED SYSTEMS.
  
  
 DERRICK L. DANIELS, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6722
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-07-24 Cont ID  
Sent By shill Date 2012-07-24 Time 16:52 Rev Time 0.00
Received By shill Date 2012-06-28 Time 13:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-06-07 Cont ID  
Sent By shill Date 2012-06-07 Time 17:49 Rev Time 0.00
Received By shill Date 2012-05-15 Time 17:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-04-12 Cont ID  
Sent By shill Date 2012-04-12 Time 10:32 Rev Time 0.00
Received By shill Date 2012-03-14 Time 16:44 Sent To  
Notes
2012-03-14 16:46:11SENT TO C24 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2012-07-19 Cont ID  
Sent By hmoser Date 2012-07-19 Time 13:56 Rev Time 0.00
Received By hmoser Date 2012-07-19 Time 10:50 Sent To  
Notes
2012-07-19 13:56:47PASS PROVISO
 1) PROVIDE LETTER FROM THE ENGINEER SHOWING A COMPLETE
 DETAIL ON THE RTU CURB
 AND EXHAUST FAN CURB TIE DOWN TO ROOF. AND THE
 EQUIPMENT
 TIE DOWN TO CURB. ( BOLT SIZE HOW FAR APART THE BOLTS
 SHOULD BE)
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 AT FIRST INSPECTION
 2) PROVIDE A LETTER FROM THE ENGINEER SHOWING EQUIPMENT
 SCHEDULE.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2012-06-05 Cont ID  
Sent By hmoser Date 2012-06-05 Time 10:22 Rev Time 0.00
Received By hmoser Date 2012-06-05 Time 10:22 Sent To  
Notes
2012-06-05 10:25:45CAN NOT COMPLETE REVIEW LIFE SAFETY PLAN
 AND MECHANICAL PLAN DO NOT MATCH.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-03-26 Cont ID  
Sent By hmoser Date 2012-03-26 Time 08:47 Rev Time 0.00
Received By hmoser Date 2012-03-26 Time 08:19 Sent To  
Notes
2012-03-26 08:47:04PLANS DENIED
 1) NO AIR CONDITIONING DUCT PLANS SUBMITTED WITH PLANS.
 SECTION 106 FBC 2007.
 2) LIFE SAFETY PLAN PAGE LS 2 AND MECHANICAL FLOOR PLAN
 PAGE M 2 DO NOT MATCH.
 3) PROVIDE A COMPLETE SET OF MECHANICAL PLANS .
 PLAN REVIEW BY HAROLD MOSER.
 561-805-6732
 [email protected]

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status P Date 2012-06-04 Cont ID  
Sent By lwagner Date 2012-06-04 Time 13:10 Rev Time 0.00
Received By lwagner Date 2012-06-01 Time 14:15 Sent To  
Notes
2012-06-04 13:12:24PRODUCT DETAILS FOR VACUUM PUMP, OXYGEN ENCLOSURE, AND
 STERILIZER REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-06-01 Cont ID  
Sent By lwagner Date 2012-06-01 Time 14:14 Rev Time 0.00
Received By lwagner Date 2012-06-01 Time 13:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-03-19 Cont ID  
Sent By lwagner Date 2012-03-19 Time 15:14 Rev Time 0.00
Received By lwagner Date 2012-03-19 Time 08:01 Sent To  
Notes
2012-03-19 14:05:33FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 PLEASE INCLUDE MISSING PLUMBING DRAWINGS:
 1. SHEET P-1 DRAWING LIST : P-3, P-4, AND P-6 WERE NOT
 INCLUDED WITH THIS SET OF DRAWINGS.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 3 Status P Date 2012-07-19 Cont ID  
Sent By lfranco Date 2012-07-19 Time 15:40 Rev Time 0.00
Received By lfranco Date 2012-07-17 Time 11:01 Sent To  
Notes
2012-07-20 13:03:55PLANNING: ***** PASSED WITH PROVISO, PRIOR TO FINAL
 INSPECTION OF THE SITE, THE APPLICANT SHALL APPLY FOR A
 SEPARATE LANDSCAPE AND IRRIGATION PERMIT. TWO COPIES OF
 THE LANDSCAPE PLAN AND A CERTIFIED COST ESTIMATE THAT
 INCLUDES THE TOTAL COST OF ALL LANDSCAPE MATERIALS AND
 LABOR, BROKEN DOWN INTO UNIT COST SHALL BE SUBMITTED
 WITH THE LANDSCAPE PERMIT APPLICATION.
 THIS PERMIT IS ONLY FOR THE GENERATOR AND GENERATOR
 ENCLOSURE (WALL).
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO, AICP
 SENIOR PLANNER
 PLANNING DIVISION
 TEL: (561) 822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2012-06-06 Cont ID  
Sent By lfranco Date 2012-06-06 Time 20:40 Rev Time 0.50
Received By lfranco Date 2012-06-06 Time 20:40 Sent To  
Notes
2012-06-06 20:44:06PLANNING: ***** FAILED *****]
  
  
 1, RESPOND TO COMMENTS IN WRITING WHEN RESUBMITING
 DOCUMENTS.
  
 2. THE SCOPE OF WORK DENOTES ALL INTERIOR WORK AND
 RENOVATIONS, HOWEVER, SHEET E1, PLAN NOTES CALLS OUT
 FOR A PROPOSED ASC GENERATOR. THERE ARE NO CIVIL
 DRAWINGS THAT SHOW THIS GENERATOR OR ENCLOSURE. IS
 THERE A NEW GENERATOR PROPOSED?
  
 IF SO, PROVIDE THE FOLLOWING INFORMATION:
  
 A. INDICATE SETBACK DIMENSIONS FROM PROPOSED GENERATOR
 EQUIPMENT TO ALL PROPERTY LINES. PURSUANT TO SECTION
 94-305(B)(4) OF THE ZLDR: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 RESUBMITTAL: DIMENSIONS WERE NOT PROVIDED ON SITE PLAN
 SP-1 OR LP-1.
  
 B. PROVIDE ELEVATIONS AND A FLOOR PLAN OF SCREENING AND
 LANDSCAPING DETAIL. INCLUDE WALL HEIGHT, ETC. SCREENING
 ENCLOSURE AND LANDSCAPING SHALL MEET SECTION 94-444 OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS. SCREENING
 WALLS SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES
 PLANTED AT TWO-FOOT INTERVALS. OR PROVIDE INFORMATION
 OF EXISTING ENCLOSURE THAT MEETS THE REQUIREMENTS
 ABOVE.
  
 RESUBMITTAL: ELEVATIONS WERE NOT PROVIDED. PROVIDE A
 CROSS SECTION OF THE PROPOSED ENCLOSURE, GENERATOR
 (INCLUDING THE MOUNTING AND TANK), THE ENTIRE GENERATOR
 EQUIPMENT NEEDS TO BE SCREENED FROM VIEW. PROVIDE TOTAL
 HEIGHT DIMENSIONS OF FENCE ENCLOSURE AND GENERATOR.
  
  
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO, AICP
 SENIOR PLANNER
 PLANNING DIVISION
 TEL: (561) 822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2012-04-11 Cont ID  
Sent By lfranco Date 2012-04-11 Time 19:36 Rev Time 0.50
Received By lfranco Date 2012-04-11 Time 19:36 Sent To  
Notes
2012-04-11 19:41:40PLANNING: ***** FAILED *****]
  
  
 1, RESPOND TO COMMENTS IN WRITING.
  
 2. THE SCOPE OF WORK DENOTES ALL INTERIOR WORK AND
 RENOVATIONS, HOWEVER, SHEET E1, PLAN NOTES CALLS OUT
 FOR A PROPOSED ASC GENERATOR. THERE ARE NO CIVIL
 DRAWINGS THAT SHOW THIS GENERATOR OR ENCLOSURE. IS
 THERE A NEW GENERATOR PROPOSED?
  
 IF SO, PROVIDE THE FOLLOWING INFORMATION:
  
 A. INDICATE SETBACK DIMENSIONS FROM PROPOSED GENERATOR
 EQUIPMENT TO ALL PROPERTY LINES. PURSUANT TO SECTION
 94-305(B)(4) OF THE ZLDR: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 B. PROVIDE ELEVATIONS AND A FLOOR PLAN OF SCREENING AND
 LANDSCAPING DETAIL. INCLUDE WALL HEIGHT, ETC. SCREENING
 ENCLOSURE AND LANDSCAPING SHALL MEET SECTION 94-444 OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS. SCREENING
 WALLS SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES
 PLANTED AT TWO-FOOT INTERVALS. OR PROVIDE INFORMATION
 OF EXISTING ENCLOSURE THAT MEETS THE REQUIREMENTS
 ABOVE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO, AICP
 SENIOR PLANNER
 PLANNING DIVISION
 TEL: (561) 822-1443
 EMAIL: [email protected]
  