Plan Review Details - Permit 12030147
Plan Review Stops For Permit 12030147
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-04-02 Cont ID  
Sent By jwitmer Date 2014-04-02 Time 07:01 Rev Time 0.00
Received By jwitmer Date 2014-04-02 Time 06:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-04-16 Cont ID  
Sent By jwitmer Date 2013-04-16 Time 09:43 Rev Time 0.00
Received By jwitmer Date 2013-04-16 Time 09:43 Sent To  
Notes
2013-04-16 09:37:022007-09 FBC-B SUBMITTED 03/07/2014
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). DEFERRED SUBMITTALS
 WILL REQUIRE ADDITIONAL REVIEWS.
  
 1) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 2) 2ND REQUEST, COMPONENTS & CLADDING FBC-B 1609.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 3) SHEET A4-1, A 4-2 & A4-3 DETAIL # 10 PLEASE PROVIDE
 PRODUCT SPECIFICATIONS.2007/09 FBC-B 1406.2.2
 ARCHITECTURAL TRIM. ARCHITECTURAL TRIM THAT EXCEEDS 40
 FEET (12 192 MM) IN HEIGHT ABOVE GRADE PLANE SHALL BE
 CONSTRUCTED OF APPROVED NONCOMBUSTIBLE MATERIALS .

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-10-01 Cont ID  
Sent By jwitmer Date 2012-10-01 Time 13:09 Rev Time 0.00
Received By jwitmer Date 2012-10-01 Time 13:09 Sent To  
Notes
2012-10-01 15:41:29BUILDING PLAN REVIEW
 PERMIT: 12030147
 ADD: 7670 OKEECHOBEE BLVD
 CONT:TBD
 TEL: (561)###-####
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 NEW 3 STORY TYPE II-B SPRINKLERED BUILDING
  
 2ND REVIEW
 OCT. 01/ 2012
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) 2ND REQUEST, LS1-1 & A1-1, THE PLANS INDICATE RATED
 TENANT SEPARATION WALLS THAT DOUBLE AS CORRIDOR WALLS,
 BUT WHERE THE TENANT SEPERATION WALLS CONTINUE AROUND
 THE VARIOUS COMMON ELEMENT ROOMS (RESTROOMS, ELECTRICAL
 AND OR MECHANICAL ROOMS) THE ONE HOUR RATING IS
 MISSING. 2007/09 FBC-B 708.1(7). THE EXCEPTION BETWEEN
 BUSINESS OCCUPANCIES UP TO 3,000 SQUARE FEET WITHOUT
 RATED TENANT SPERATION WALLS WOULD BE SUITES ON THE
 SAME SIDE OF A CORRIDOR WHERE THE TOTAL OF TWO OR MORE
 SUITES WOULD BE A TOTAL OF UNDER 3,000 SQUARE FEET. AS
 DEPICTED ON THE LS SHEET THE AREAS OF CONCERN ARE
 INDICATED WITHIN THE TENANT SPACE.
  
 3) 2ND REQUEST, LS1-1 & A1-1, THE PLANS ROOM TYPES,
 SOME OF THESE ROOM HAVE INCIDENTAL USE AREAS (TABLE
 508.2 INCIDENTAL USE AREAS) ( MECHANICAL AND OR STORAGE
 ROOM < 100 S F) ) AND NEED TO CONSTRUCT THE WALLS IN
 ACCORDANCE WITH 2007/09 FBC-B 508.2.2.1 (SMOKE
 PARTITIONS).
  
 4) COMPLIED.
  
 5A) 2ND REQUEST, SHEET LS1-2 & A1-2, PLANS NOW INDICATE
 THE ROOM USAGE AND THE CONFERENCE ROOM AREA OF 1440 SQ
 FT CREATES AN A-3 OCCUPANCY, THE COVER SHEET INDICATED
 A LOADING OF 15 SQUARE FEET PER PERSON, OR A OCCUPANT
 LOAD OF 96. THE 1440 SQUARE FEET CREATES AN ACCESSORY
 OCCUPANCY
 2007FBC-B 508.3.1 THAT WILL REQUIRE FIRE RATED
 CORRIDORS PER 2007 FBC-B TABLE 1017.1.
  
 5B) THE SAME HOLDS TRUE FOR THE MULTIPURPOSE ROOM #
 206, THIS ROOM IS APPROXIMATELY 2340 SQUARE FEET, BEING
 A MULTIPURPOSE ROOM AGAIN WE WILL BE TAKING THE WORST
 CASE SENARIO WITH 7 SQ FT PER PERSON, THIS ROOM WOULD
 ALSO BE CONSIDERED AN A-3 OCCUPANCY.
  
 5C) IN BOTH ROOMS PLEASE PROVIDE A FURNATURE PLAN THAT
 WILL REDUCE THE OCCUPANT LOADS AND BRING THE REQUIRED
 DOOR WIDTH AND STAIR WIDTH BACK INTO COMPLIANCE. 2007
 FBC-B 1005.1. PLEASE NOTE WITH THE OCCUPANT LOAD TAKEN
 AT 7 SQUARE FEET FOR THE CONFERENCE ROOM AND
 MULTI-PURPOSE ROOM WOULD CREATE AN OCCUPANT LOAD OF
 OVER 500 REQUIRING A THIRD EXIT, 2007 FBC-B TABLE
 1019.1.
  
 COMMENT FROM 1ST REVIEW.THE PLANS DO NOT INDICATE ROOM
 TYPES, SOME OF THESE ROOM MAY BE INCIDENTAL USE AREAS
 AND NEED TO CONSTRUCT THE WALLS IN ACCORDANCE WITH
 2007/09 FBC-B 508.2.2.1 (SMOKE PARTITIONS).
  
 6A) 2ND REQUEST. SHEET A1-1 THE ELEVATOR MACHINE ROOM
 DOES NOT INDICATE RATED WALLS 3006.4. PLEASE SHOW ALL
 FIRE AND OR SMOKE RATED WALLS ON A1-1, A1-2 AND A1-3
 SINCE THE ROOMS AND DOORS ARE IDENTIFIED. 106.1.2.
 ADDITIONAL DATA. INDICATE ALL FIRE RATED WALLS, SMOKE
 PARTITIONS ON THE A1 SHEETS FOR ALL THREE STORIES,
 THERE ARE MANY WALLS THAT DO NOT INDICATE FIRE RATED
 WALLS
  
 .6B) COMPLIED.
  
 7) COMPLIED.
  
 8) 2ND REQUEST, SHEET A2-1 THE PRE-ENGINEERED ROOF
 ACCESS HATCH REQUIRES EITHER A FL STATE APPROVAL OR
 MIAMI-DADE NOA, RULE 9N-3(31)(A).
  
 9) 2ND REQUEST, SHEET A2-1 THE PRE-ENGINEERED A/C
 STANDS WILL ALSO REQUIRE EITHER A FL APPROVAL OR
 MIAMI-DADE NOA. RULE 9N-3(31)(G).
  
 10) SHEET A2-1 INDICATES THREE ROOMS 2 WITH
 APRROXIMATELY 6'-0" IN HEIGHT THE THIRD APPROXIMATELY
 8'-0 IN HEIGHT, WHAT WILL THESE ROOMS BE USED FOR?
 FBC-B 1509.2.
  
 11) COMPLIED.
  
 12) 2ND REQUEST, RESPONCE NOTED. SHEET A4-1, A 4-2 &
 A4-3 DETAIL # 10 PLEASE PROVIDE PRODUCT
 SPECIFICATIONS.2007/09 FBC-B 1406.2.2 ARCHITECTURAL
 TRIM. ARCHITECTURAL TRIM THAT EXCEEDS 40 FEET (12 192
 MM) IN HEIGHT ABOVE GRADE PLANE SHALL BE CONSTRUCTED OF
 APPROVED NONCOMBUSTIBLE MATERIALS AND SHALL BE SECURED
 TO THE WALL WITH METAL OR OTHER APPROVED NONCOMBUSTIBLE
 BRACKETS.
  
 13) SEMI- COMPLIED. SHEET A4-1 & A4-3 DETAIL # 17
 GAURDRAILS SEE OPENING LIMITATION OF 4 INCHES 1013.3
 FBC-B.
  
 14) COMPLIED AS NOTED: ASSISSTANTS DESK.
  
 15) 2ND REQUEST, ONCE ALL THE FIRE & SMOKE RATED WALLS
 ARE IDENTIFIED THE DOOR SCHEDULE WILL NEED TO BE
 UPDATED. 2007/09 FBC-B TABLE 715.4.
  
 16) COMPLIED.
  
 17) S1-2 THIS STRUCTURE WILL REQUIRE A SPECIAL
 INSPECTOR WPB ADMINISTRATIVE CODE 109.3.7 BUILDINGS
 MORE THAN 2 STORIES IN HEIGHT, AND TILT WALL
 CONSTRUCTION. CONTACT KEN CONRAD FOR REQUIRED LICENSING
 AND FORMS AT 561-805-6666.
  
 18) COMPLIED.
  
  
  
 19) 2ND REQUEST, 106.3.3 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 20) 2ND REQUEST, COMPONENTS & CLADDING FBC-B 1609.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 21) COMPLIED AS NOTED, EXTERIOR GLAZING WILL BE LARGE
 MISSILE IMACT.
  
 22) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-03-16 Cont ID  
Sent By jwitmer Date 2012-03-16 Time 16:55 Rev Time 0.00
Received By jwitmer Date 2012-03-14 Time 15:13 Sent To  
Notes
2012-03-14 15:56:52BUILDING PLAN REVIEW
 PERMIT: 12030147
 ADD: 7670 OKEECHOBEE BLVD
 CONT:TBD
 TEL: (561)###-####
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 NEW 3 STORY TYPE II-B SPRINKLERED BUILDING
  
 1ST REVIEW
 ACTION: DENIED
  
 1) LS1-1 THE 2 VERTICAL EXITS MUST MEET THE
 REQUIREMENTS OF FOR EXIT DISCHARGE IN 2007/09 FBC-B
 1024.1EXITS SHALL DISCHARGE DIRECTLY TO THE EXTERIOR OF
 THE BUILDING.
  
 2) LS1-1 THE PLANS INDICATE RATED TENANT SEPARATION
 WALLS THAT DOUBLE AS CORRIDOR WALLS, BUT WHERE THE
 TENANT SEPERATION WALLS CONTINUE AROUND THE VARIOUS
 COMMON ELEMENT ROOMS (RESTROOMS, ELECTRICAL AND OR
 MECHANICAL ROOMS) THE ONE HOUR RATING IS MISSING.
 2007/09 FBC-B 708.1(7).
  
 3) LS1-1 THE PLANS DO NOT INDICATE ROOM TYPES, SOME OF
 THESE ROOM MAY BE INCIDENTAL USE AREAS AND NEED TO
 CONSTRUCT THE WALLS IN ACCORDANCE WITH
 2007/09 FBC-B 508.2.2.1 (SMOKE PARTITIONS).
  
 4) SHEET LS1-2 IT APPEARS THAT THIS PLAN IS NOT A
 SINGLE TENANT OCCUPANCY WHERE TENANT SEPERATION WALLS
 WILL BE REQUIRED. FBC -B 2007/09 708.1(7).
  
 5) SHEET LS1-2 THE PLANS DO NOT INDICATE ROOM TYPES,
 SOME OF THESE ROOM MAY BE INCIDENTAL USE AREAS AND NEED
 TO CONSTRUCT THE WALLS IN ACCORDANCE WITH
 2007/09 FBC-B 508.2.2.1 (SMOKE PARTITIONS).
  
 6A) SHEET A1-1 THE ELEVATOR MACHINE ROOM DOES NOT
 INDICATE RATED WALLS 3006.4. PLEASE SHOW ALL FIRE AND
 OR SMOKE RATED WALLS ON A1-1, A1-2 AND A1-3 SINCE THE
 ROOMS AND DOORS ARE IDENTIFIED. 106.1.2. ADDITIONAL
 DATA. INDICATE ALL FIRE RATED WALLS, SMOKE PARTITIONS
 ON THE A1 SHEETS FOR ALL THREE STORIES, THERE ARE MANY
 WALLS THAT DO NOT INDICATE FIRE RATED WALLS
  
 .6B) PLEASE PROVIDE THE FOLLOWING STATEMENT FBC-B 712.6
 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE
 AND SMOKE BARRIER - PROTECT ALL OPENINGS."
  
  
 7) SHEET A2-1 STORAGE ROOM 209 IS OVER 100 SQ FT
 2007/09 FBC-B 508.2.2.1 IN FULLY SPRINKLERED BUILDINGS
 INCIDENTIAL USE ROOM ARE TO BE BUILT WITH SMOKE
 PARTITIONS SEE
 SECTION 710.
  
 8) SHEET A2-1 THE PRE-ENGINEERED ROOF ACCESS HATCH
 REQUIRES EITHER A FL STATE APPROVAL OR MIAMI-DADE NOA,
 RULE 9N-3(31)(A).
  
 9) SHEET A2-1 THE PRE-ENGINEERED A/C STANDS WILL ALSO
 REQUIRE EITHER A FL APPROVAL OR MIAMI-DADE NOA. RULE
 9N-3(31)(G).
  
 10) SHEET A2-1 INDICATES THREE ROOMS 2 WITH
 APRROXIMATELY 6'-0" IN HEIGHT THE THIRD APPROXIMATELY
 8'-0 IN HEIGHT, WHAT WILL THESE ROOMS BE USED FOR?
 FBC-B 1509.2.
  
 11) SHEET A5-3 DETAIL 05 INDICATES THE SIZE OF THE SUMP
 PIT 12"X12", PLEASE REVIEW FBC-P 712.3.2 FOR MINIMUM
 SIZE 18 INCHES IN DIAMETER AND 24 INCHES DEEP.
  
 12) SHEET A4-1, A 4-2 & A4-3 DETAIL # 10 PLEASE PROVIDE
 PRODUCT SPECIFICATIONS.2007/09 FBC-B 1406.2.2
 ARCHITECTURAL TRIM. ARCHITECTURAL TRIM THAT EXCEEDS 40
 FEET (12 192 MM) IN HEIGHT ABOVE GRADE PLANE SHALL BE
 CONSTRUCTED OF APPROVED NONCOMBUSTIBLE MATERIALS AND
 SHALL BE SECURED TO THE WALL WITH METAL OR OTHER
 APPROVED NONCOMBUSTIBLE BRACKETS.
  
 13) SHEET A4-1 & A4-3 DETAIL # 17 GAURDRAILS THE HEIGHT
 REQUIREMENT IS MINIMUM OF 42 INCHES FBC-B 1013.2, & SEE
 OPENING LIMITATION OF 4 INCHES 1013.3 FBC-B.
  
 14) SHEET A6-2 RECEPTION DESK TO COMPLY WITH 2007/09
 FBC-B 11-7.2 INFORMATION COUNTERS.(2)(I) A PORTION OF
 THE MAIN COUNTER WHICH IS A MINIMUM OF 36 INCHES (915
 MM) IN LENGTH SHALL BE PROVIDED WITH A MAXIMUM HEIGHT
 OF 36 INCHES (915 MM); OR
  
 15) ONCE ALL THE FIRE & SMOKE RATED WALLS ARE
 IDENTIFIED THE DOOR SCHEDULE WILL NEED TO BE UPDATED.
 2007/09 FBC-B TABLE 715.4.
  
 16) PLEASE PROVIDE SOILS INVESTIGATIVE REPORTS (3)
 FBC-B1802.2 WHERE REQUIRED. THE OWNER OR APPLICANT
 SHALL SUBMIT A FOUNDATION AND SOILS INVESTIGATION TO
 THE BUILDING OFFICIAL WHERE REQUIRED IN SECTIONS
 1802.2.1 THROUGH 1802.2.7.
  
 17) S1-2 THIS STRUCTURE WILL REQUIRE A SPECIAL
 INSPECTOR WPB ADMINISTRATIVE CODE 109.3.7 BUILDINGS
 MORE THAN 2 STORIES IN HEIGHT, AND TILT WALL
 CONSTRUCTION. CONTACT KEN CONRAD
 FOR REQUIRED LICENSING AND FORMS.
  
 18) S1-4, SHEET S1-2 INDICATES THIS TABLE TO BE FOR
 COMPONENTS AND CLADDING BUT IS LABELED GROSS PRESSURES,
 2007/09 FBC-B PRESSURES FOR AN EXPOSURE C AND BUILDING
 HEIGHT OF
 40 FEET INCLUDES A MULTIPLIER OF 1.49. FOR THE ROOFING
 NEGATIVE PRESSURES IN A B EXPOSURE AND NO HEIGHT
 ADJUSTMENTS THE MINIMUM NEGATIVE PRESSURES FOR 10 SQ FT
 IS -89 PRESSURES WITHIN THIS TABLE ARE LOW FOR THE 2007
 FBC.
  
 19) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 20) COMPONENTS & CLADDING FBC-B 1609. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 21) SHEET S1-2 NOTE INDICATING IMPACT RESISTANT WINDOWS
 AND ALTERNATE TO BE SHUTTERED. PLEASE NOTE: 104.6*/
 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE DEBRIS IMPACT
 PROTECTION QUESTION# 13 RECOGNIZING SUCH CONCERNS AS
 ABSENTEE OWNERS, OR CASES WHERE LONGER TIME & EFFORT IS
 NECESSARY TO SECURE SHUTTERS ON LARGE OR MULTI-STORY
 BUILDINGS, WHAT MEASURES ARE BEING RECOMMENDED OR
 IMPLEMENTED TO ENSURE THAT COMPLETE INSTALLATION OR
 SECURING IS DONE SUFFICIENTLY IN ADVANCE OF THE
 HURRICANE?
  
 IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE
 GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE,
 SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING,
 CHAPTER 1,
 ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY
 OF WEST PALM BEACH, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR
 ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION
 OF EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR
 MULTI-STORY BUILDINGS, OR MULTIPLE
 ON THE SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST
 BE SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS
 FOR REVIEW BY THE CONSTRUCTION SERVICES DEPARTMENT. ANY
 SUCH PLAN SHALL INCLUDE, AT A MINIMUM, ON SITE LOCATION
 OF THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH
 COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND
 THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE ACCOMPLISHED WITHIN
 TWELVE (12) HOURS OR LESS OF THE
 OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES
 OF A HURRICANE WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD)
 ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE
 MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO
 REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED
 UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE
 BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE.
  
 IN LEAU OF LARGE MISSLE IMPACT RATED WINDOWS, STORM
 SHUTTERS MAY BE USED ON THE FIRST FLOOR IF: 104.6*/
 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE DEBRIS IMPACT
 PROTECTION
  
 22) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2014-04-21 Cont ID  
Sent By rlecky Date 2014-04-21 Time 13:41 Rev Time 0.00
Received By rlecky Date 2014-04-21 Time 13:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2013-04-02 Cont ID  
Sent By rlecky Date 2013-04-02 Time 12:53 Rev Time 0.00
Received By rlecky Date 2013-04-02 Time 12:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-09-24 Cont ID  
Sent By rlecky Date 2012-09-24 Time 15:57 Rev Time 0.00
Received By rlecky Date 2012-09-17 Time 14:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-03-20 Cont ID  
Sent By rlecky Date 2012-03-20 Time 13:51 Rev Time 0.00
Received By rlecky Date 2012-03-14 Time 16:59 Sent To  
Notes
2012-03-20 13:52:5512030147
 7670 OKEECHOBEE BLVD
 NEW 3 STORY OFFICE BUILDING
  
 PROVIDE A LIGHTING DENSITY CALCULATION VERIFYING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.5
 A SEPARATE BRANCH CIRCUIT SHALL SUPPLY ELEVATOR CAR
 LIGHTS. NEC 620.22
 PROVIDE A DETAIL SHOWING THAT THE REQUIRED WORKING
 CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN
 PROVIDED FOR THE ELECTRICAL EQUIPMENT AND PANEL BOARDS.
 NEC 110.26, 240.24, 408.17
 OVERCURRENT DEVICES SHALL NOT BE LOCATED IN THE
 VICINITY OF EASILY IGNITABLE MATERIAL. SEE STORAGE ROOM
 #345. NEC 240.24
  
 NOTE:
 SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE
 ALARM SYSTEM, VOICE AND DATA.
 A SEPARATE PERMIT AND PLANS WITH WIND LOAD ENGINEERING
 FOR POLES, BASES AND FIXTURES IS REQUIRED.
  
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2012-10-05 Cont ID  
Sent By mgonzale Date 2012-10-05 Time 12:13 Rev Time 0.50
Received By mgonzale Date 2012-10-05 Time 12:13 Sent To  
Notes
2012-10-05 12:13:39PLANS ARE REVIEWED THRU ENG.
  
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2012-04-12 Cont ID  
Sent By mgonzale Date 2012-04-12 Time   Rev Time 1.00
Received By mgonzale Date 2012-04-12 Time   Sent To  
Notes
2012-04-12 15:42:33NO OBJECTION! PLANS ARE ACCEPTABLE.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2013-04-17 Cont ID  
Sent By wjolin Date 2013-04-17 Time 15:44 Rev Time 0.00
Received By wjolin Date 2013-04-17 Time 14:06 Sent To  
Notes
2013-04-17 15:44:357670 OKEECHOBEE BOULEVARD
 PERMIT #12030147
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A1.1: PANIC/FIRE EXIT HARDWARE IS NEEDED IN
 ASSEMBLY OCCUPANCIES WHERE THE DOOR SERVES 50 OR
 PERSONS. DOOR #100, 101, 102, 107 & 108 WILL REQUIRE
 PANIC/FIRE EXIT HARDWARE. CURRENTLY THE SPECIFICATIONS
 DO NOT INDICATE THIS TYPE OF HARDWARE FOR THESE DOORS.
  
 SHEET A1.2: PANIC/FIRE EXIT HARDWARE IS NEEDED IN
 ASSEMBLY OCCUPANCIES WHERE THE DOOR SERVES 50 OR
 PERSONS. DOOR #201, 214, 218, 220, 223 & 224 WILL
 REQUIRE PANIC/FIRE EXIT HARDWARE. CURRENTLY THE
 SPECIFICATIONS DO NOT INDICATE THIS TYPE OF HARDWARE
 FOR THESE DOORS.
  
 SHEET E2-3: AN EXIT SIGN IS NEEDED AT THE SECONDARY
 EGRESS DOOR IN BREAKROOM #307.
  
 ELECTRICAL DRAWINGS: THE FIRE ALARM SYSTEM WILL NEED TO
 BE EQUIPPED WITH VOICE EVACUATION CAPABILITIES FOR AN
 ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD GREATER THAN
 300 PERSONS. PROVIDE SPEAKER/STROBE NOTIFICATION
 APPLIANCES (REFERENCE SECTION 12.3.4.3.3 OF FLORIDA
 FIRE PREVENTION CODE - NFPA 101). PROVIDE A
 PRE-RECORDED FIRE ALARM EVACUATION MESSAGE NOTIFYING
 OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN THE
 BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE
 BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE
  
 INSPECTOR NOTES: THE BUILDING IS FUNCTIONING AS A MIXED
 OCCUPANCY (NON-SEPARATED ASSEMBLY AND BUSINESS) THAT
 WILL NEED A FIRE ALARM SYSTEM WITH VOICE EVACUATION AND
 PANIC/FIRE EXIT HARDWARE ON EGRESS DOORS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-10-01 Cont ID  
Sent By wjolin Date 2012-10-01 Time 11:27 Rev Time 0.00
Received By wjolin Date 2012-09-28 Time 12:16 Sent To  
Notes
2012-10-01 11:27:357670 OKEECHOBEE BOULEVARD
 PERMIT #12030147
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****APPROVED WITH PROVISIONS - SUBMIT REVISION*****
  
 REPEAT COMMENT: SHEET LS1-1: UPDATE THE CODE LIST TO
 REFERENCE THE 2010 EDITION OF THE FLORIDA FIRE
 PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF BOTH
 NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS.
  
 PROVIDE COPY OF PROJECT SPECIFICATIONS AS REFERENCED BY
 DOOR SCHEDULE.
  
 PROVIDE A SEATING/FURNITURE LAYOUT FOR THE MULTIPURPOSE
 ROOM #206 AND CONFERENCE ROOM #208.
  
 ELECTRICAL DRAWINGS: THE FIRE ALARM SYSTEM WILL NEED TO
 BE EQUIPPED WITH VOICE EVACUATION CAPABILITIES FOR AN
 ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD GREATER THAN
 300 PERSONS. PROVIDE SPEAKER/STROBE NOTIFICATION
 APPLIANCES (REFERENCE SECTION 12.3.4.3.3 OF FLORIDA
 FIRE PREVENTION CODE ? NFPA 101). PROVIDE A
 PRE-RECORDED FIRE ALARM EVACUATION MESSAGE NOTIFYING
 OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN THE
 BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE
 BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR.
  
 REPEAT COMMENT: SHEET E2-2: ONLY TWO EXIT SIGNS
 PROVIDED FOR ENTIRE FLOOR.
  
 REPEAT COMMENT: SHEET E2-3: ONLY TWO EXIT SIGNS
 PROVIDED FOR ENTIRE FLOOR.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE
  
 INSPECTOR NOTES: THE BUILDING IS FUNCTIONING AS A MIXED
 OCCUPANCY (NON-SEPARATED ASSEMBLY AND BUSINESS) THAT
 WILL NEED A FIRE ALARM SYSTEM WITH VOICE EVACUATION AND
 PANIC/FIRE EXIT HARDWARE ON EGRESS DOORS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-04-06 Cont ID  
Sent By wjolin Date 2012-04-06 Time 13:43 Rev Time 0.00
Received By wjolin Date 2012-04-06 Time 08:28 Sent To  
Notes
2012-04-06 13:43:367670 OKEECHOBEE BOULEVARD
 PERMIT #12030147
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: ALL CONSTRUCTION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. SMOKING SHALL BE PROHIBITED
 EXCEPT IN DESIGNATED AREAS OUTSIDE THE BUILDING. ALL
 INTERIOR CONSTRUCTION AREAS SHALL HAVE "NO SMOKING"
 SIGNS POSTED.
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 GENERAL: PROVIDE BUILDING ADDRESS VISIBLE FROM THE
 STREET. NUMBERS SHALL BE ATTACHED TO THE BUILDING AND
 BE AT LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND
 SHALL CONTRAST THE BACKGROUND.
  
 GENERAL: PORTABLE FIRE EXTINGUISHERS SHALL HAVE A
 MINIMUM RATING OF 2A:10BC AND SHALL BE TAGGED BY A
 LICENSED FIRE EXTINGUISHER COMPANY.
  
 GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 GENERAL: WHEN IDENTIFYING THE FIRE RATED WALLS WITH
 SIGNAGE OR STENCILING, THE CHARACTERS SHALL BE AT LEAST
 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH.
 IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON
 CENTER.
  
 GENERAL: NO INTERIOR FINISH CLASSIFICATIONS INDICATED
 FOR WALL AND CEILING MATERIALS.
  
 SHEET C6: FIRE DEPARTMENT CONNECTION SHALL BE
 IDENTIFIED WITH A SIGN STATING, "NO PARKING - FIRE DEPT
 CONNECTION". THIS WILL CAUSE THE REMOVAL OF 1 OF 9
 PARKING SPACES.
  
 SHEET C6: CONFIRM THE FIRE DEPARTMENT CONNECTIONS AND
 FIRE HYDRANTS WILL BE PROVIDED WITH CLEARANCES OF 7?-6?
 TO THE FRONT AND SIDES AND 4? TO THE BACKSIDE PER
 SECTION 18.3.4.1 OF NFPA 1 FLORIDA EDITION.
  
 SHEET C6: PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES
 FOR SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 SHEET C6: PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 SHEET C6: PROVIDE PERMANENT WEATHERPROOF SIGN MARKING
 THE FIRE DEPARTMENT CONNECTION AND IDENTIFY THE
 BUILDING BEING SERVED.
  
 SHEET LS1-1 AND FP1-0: UPDATE THE CODE LIST TO
 REFERENCE THE 2010 EDITION OF THE FLORIDA FIRE
 PREVENTION CODE WHICH CONTAINS THE 2009 EDITION OF BOTH
 NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS. FIRE
 SPRINKLER DESIGN SHALL CONFORM TO THE 2007 EDITION OF
 NFPA 13.
  
 **SHEET LS1-1: THE BUILDING IS FUNCTIONING AS A
 NON-SEPARATED MULTIUSE OCCUPANCY. THE OCCUPANCY TYPE IS
 INDICATED AS BUSINESS; HOWEVER, MULTIPURPOSE ROOM #206
 AND CONFERENCE ROOM #208 ARE FUNCTIONING AS ASSEMBLY
 OCCUPANCIES.
  
 SHEET LS1-1: BOTH STAIR ENCLOSURES DISCHARGE INSIDE THE
 BUILDING. PER SECTION 7.7 (NFPA 101), NOT MORE THAN 50%
 OF THE EXITS ARE ALLOWED TO DISCHARGE INSIDE THE
 BUILDING.
  
 SHEET A7-1: PROVIDE THE DOOR SCHEDULE HARDWARE GROUP
 INFORMATION (LOCKS, LATCHES, CLOSERS, PANIC HARDWARE,
 ETC.)
  
 MECHANICAL: PROVIDE DUCT SMOKE DETECTORS FOR AIR
 SYSTEMS EXCEEDING 2000 CFM.
  
 ELECTRICAL: MONITOR FIRE SPRINKLER TAMPER SWITCHES,
 FLOW SWITCHES, AND CLEAN AGENT SUPPRESSION SYSTEM.
 PROVIDE/MONITOR TAMPER SWITCHES ON BACKFLOW PREVENTER.
  
 SHEET E2-2: ONLY TWO EXIT SIGNS PROVIDED FOR ENTIRE
 FLOOR.
  
 SHEET E2-3: ONLY TWO EXIT SIGNS PROVIDED FOR ENTIRE
 FLOOR.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-04-21 Cont ID  
Sent By skennedy Date 2014-04-21 Time 13:59 Rev Time 0.00
Received By skennedy Date 2014-03-18 Time 11:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2013-05-02 Time   Rev Time 0.00
Received By rregueir Date 2013-04-01 Time 13:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-12-10 Cont ID  
Sent By shill Date 2012-12-05 Time 17:10 Rev Time 0.00
Received By shill Date 2012-09-12 Time 17:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-09 Cont ID  
Sent By rregueir Date 2012-05-09 Time 16:01 Rev Time 0.00
Received By rregueir Date 2012-03-13 Time 09:40 Sent To  
Notes
2012-03-14 09:41:00**DIGITAL** SEE PROJECTDOX

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2014-04-02 Cont ID  
Sent By jwitmer Date 2014-04-02 Time 06:38 Rev Time 0.00
Received By jwitmer Date 2014-04-02 Time 06:38 Sent To  
Notes
2014-04-02 06:39:11BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2013-04-16 Cont ID  
Sent By jwitmer Date 2013-04-16 Time 09:44 Rev Time 0.00
Received By jwitmer Date 2013-04-16 Time 09:44 Sent To  
Notes
2013-04-16 09:45:06BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2012-10-01 Cont ID  
Sent By jwitmer Date 2012-10-01 Time 09:45 Rev Time 0.00
Received By jwitmer Date 2012-10-01 Time 09:45 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2012-03-19 Time   Rev Time 0.00
Received By jwitmer Date 2012-03-19 Time 08:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2013-04-26 Cont ID  
Sent By rregueir Date 2013-04-26 Time 09:20 Rev Time 0.00
Received By rregueir Date 2013-04-26 Time 09:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2012-12-04 Cont ID  
Sent By rregueir Date 2012-12-04 Time 17:32 Rev Time 0.00
Received By rregueir Date 2012-12-04 Time 17:14 Sent To  
Notes
2012-12-04 17:32:05REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2010
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. NOT COMPLIED. THE 8X8 EXHAUST DUCT PENETRATING THE
 SHAFT ENCLOSURE ON PAGE M2-2 IS MISSING A FIRE/SMOKE
 DAMPER. SEE DRAWING MARK-UP IN PROJECTDOX FOR EXACT
 LOCATION.
  
 2. OK
  
 3. OK
  
 4. OK
  
 5. NOT COMPLIED. THE UPER DETAIL FOR THE STAND CALLS
 FOR GALVANIZED STEEL PIPE SUPPORTS, WHILE THE LOWER
 DETAIL CALLS FOR A PRE-MANUFACTURED STAND. WHICH IS
 CORRECT? IF A PRE-MANUFACTURED STAND IS TO BE USED,
 PROVIDE THE ACTUAL PRODUCT APPROVAL FOR THE STAND,
 APPROVED IN WRITING BY THE ENGINEER FOR THIS PROJECT
 PER FBC-B 106.3.3.
  
 6. NOT COMPLIED. SHOW ALL DUCT MOUNTED SMOKE DETECTORS
 ON THE MECHANICAL SHEETS. CODE COMPLIANCE OF THE
 DETECTOR LOCATION CANNOT BE DETERMINED BY SHOWING
 DETECTORS ON AN ELECTRICAL SHEET WHICH DOES NOT SHOW
 THE HVAC DISTRIBUTION SYSTEM. FBC-M 606.2.1 AND FBC-B
 106.1.
  
 7. NOT COMPLIED. SEE COMMENT #6 ABOVE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-05-09 Cont ID  
Sent By rregueir Date 2012-05-09 Time 16:01 Rev Time 0.00
Received By rregueir Date 2012-03-14 Time 09:41 Sent To  
Notes
2012-04-17 16:09:01REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGES M2-2 AND M2-3: DUCT PENETRATIONS OF THE SHAFT
 ENCLOSURES ADJACENT TO THE ELEVATOR SHALL BE PROTECTED
 BY FIRE AND SMOKE DAMPERS PER FBC-M 607.5.5.
  
 2. PAGE M2-3: THERE IS A FOOTNOTE #3 POINTING AT THE
 FRESH AIR DUCT FROM THE ROOF. HOWEVER, THERE IS NO TEXT
 ON THIS PAGE ASSOCIATED WITH THIS FOOTNOTE. PLEASE
 CLARIFY. FBC-B 106.1.
  
 3. PAGE M2-3: AHU #14 RETURN DROPS ARE SHOWN ON FLOOR
 PLAN AS EXHAUST DROPS. PLEASE CLARIFY. BALANCED RETURN
 IS REQUIRED PER FBC-M 601.4.
  
 4. PAGE M2-2: AHU #5 FRESH AIR MOTORIZED DAMPER IS NOT
 SHOWN IN THE CORRECT LOCATION. SHOW THE MOTORIZED
 DAMPER IN THE FRESH AIR DUCT PER FBC-B 13-409.AB.3.3.
  
 5. PAGE M4-2 AND M4-2A KEY NOTE #4 REFERS TO A DETAIL
 FOR THE CONDENSER STANDS ON PAGE M5-1. NO SUCH DETAIL
 COULD BE FOUND ON THAT PAGE. PLEASE CLARIFY WHETHER
 THESE CONDENSER STANDS ARE SITE BUILT WITH CUSTOM
 ENGINEERING OR IF THEY ARE PRE-ENGINEERED, MANUFACTURED
 STANDS. IF THE PRE-ENGINEERED STANDS ARE USED, A
 PRODUCT APPROVAL FOR THE STANDS IS REQUIRED TO BE
 SUBMITTED PER FAC RULE 9N-1.
  
 6. PAGE M2-2: DUCT SMOKE DETECTOR REQUIRED IN SUPPLY
 SIDE OF AHU #4 PER FBC-M 606.2.1.
  
 7. PAGE M2-3: DUCT SMOKE DETECTOR REQUIRED IN SUPPLY
 SIDE OF AHU #15 PER FBC-M 606.2.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-03-15 Cont ID  
Sent By lwagner Date 2012-03-15 Time 14:09 Rev Time 0.00
Received By lwagner Date 2012-03-15 Time 09:09 Sent To  
Notes
2012-03-15 14:08:54****PROVISO****
 CLEANOUTS REQUIRED 708.3.4 AND 1101.8

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2014-04-17 Cont ID  
Sent By eschneid Date 2014-04-04 Time 09:16 Rev Time 1.00
Received By eschneid Date 2014-04-04 Time 09:15 Sent To  
Notes
2014-04-04 09:41:22FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES TO THE COMMENTS BELOW:
  
 1) REPEAT COMMENT: OUTSTANDING ITEMS FROM RESOLUTION
 NO. 266-12 (WHICH WERE ALSO INCLUDED ON PREVIOUS
 ORDINANCE NO. 4318-11) APPROVED ON OCTOBER 29, 2012:
  
 A. PREPARE A CONSTRUCTION SITE SECURITY AND MANAGEMENT
 PLAN FOR APPROVAL BY THE CITY'S POLICE DEPARTMENT CRIME
 PREVENTION THROUGH ENVIRONMENTAL DESIGN (CPTED)
 OFFICIAL. NOTE: WHILE A DIAGRAM WAS SUBMITTED WITH THE
 PERMIT RESUBMITTAL, THE PLAN SHALL BE SUBMITTED
 DIRECTLY TO THE CPTED OFFICER FOR REVIEW. THE OFFICER
 IS NOT PART OF THE PERMIT REVIEW PROCESS.
  
 I. THE APPLICANT, AFTER SITE CLEARING AND PLACEMENT OF
 CONSTRUCTION TRAILERS, SHALL INSTITUTE SECURITY
 MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES FOR
 THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT BE
 LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL,
 VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS,
 REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE
 SUBCONTRACTORS TO SECURE MACHINERY AND TOOLS AT END OF
 WORK DAY, FENCING WITH SCREENING, AND/OR ANY OTHER
 MEASURE DEEMED APPROPRIATE TO PROVIDE A SAFE AND SECURE
 WORKING ENVIRONMENT.
  
 II. THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED
 THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT.
 NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A
 STOP-WORK ORDER FOR THE ENTIRE PLANNED DEVELOPMENT.
  
 III. "NO TRESPASSING" SIGNS SHALL BE POSTED EVERY 500
 FEET AROUND THE PERIMETER OF THE CONSTRUCTION SITE.
  
 B. VERIFICATION THAT ALL OVERHEAD UTILITY LINES WITHIN
 THE SUBJECT PROPERTY SHALL BE BURIED AT THE TIME OF NEW
 CONSTRUCTION.
  
 2) THE FOLLOWING SEPARATE PERMITS, WITH PLANS, ARE
 REQUIRED (PLEASE NOTE THAT THE SUBMITTAL OF THE SHEETS
 WITH THIS PERMIT IS NOT SUFFICIENT FOR PERMIT
 APPROVAL):
  
 A. LANDSCAPE (PLEASE NOTE THE LANDSCAPE PLAN SUBMITTED
 WAS NOT THE APPROVED LSP) - REPEAT COMMENT.
 B, AWNING
 C. SIGNAGE
 D. SITE LIGHTING.
 E. BICYCLE RACK.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
2014-03-20 15:31:113/20/14

Review Stop Z ZONING
Rev No 3 Status F Date 2013-05-02 Cont ID  
Sent By eschneid Date 2013-05-02 Time 11:28 Rev Time 3.00
Received By eschneid Date 2013-04-19 Time 15:03 Sent To  
Notes
2013-04-19 15:03:25FAILED
  
 REPEAT COMMENT: PLEASE PROVIDE WRITTEN RESPONSES TO THE
 COMMENTS BELOW:
  
 1) REPEAT COMMENT: OUTSTANDING ITEMS FROM RESOLUTION
 NO. 266-12 (WHICH WERE ALSO INCLUDED ON PREVIOUS
 ORDINANCE NO. 4318-11) APPROVED ON OCTOBER 29, 2012:
  
 A. PREPARE A CONSTRUCTION SITE SECURITY AND MANAGEMENT
 PLAN FOR APPROVAL BY THE CITY'S POLICE DEPARTMENT CRIME
 PREVENTION THROUGH ENVIRONMENTAL DESIGN (CPTED)
 OFFICIAL.
  
 I. THE APPLICANT, AFTER SITE CLEARING AND PLACEMENT OF
 CONSTRUCTION TRAILERS, SHALL INSTITUTE SECURITY
 MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES FOR
 THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT BE
 LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL,
 VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS,
 REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE
 SUBCONTRACTORS TO SECURE MACHINERY AND TOOLS AT END OF
 WORK DAY, FENCING WITH SCREENING, AND/OR ANY OTHER
 MEASURE DEEMED APPROPRIATE TO PROVIDE A SAFE AND SECURE
 WORKING ENVIRONMENT.
  
 II. THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED
 THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT.
 NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A
 STOP-WORK ORDER FOR THE ENTIRE PLANNED DEVELOPMENT.
  
 III. "NO TRESPASSING" SIGNS SHALL BE POSTED EVERY 500
 FEET AROUND THE PERIMETER OF THE CONSTRUCTION SITE.
  
 B. VERIFICATION THAT ALL OVERHEAD UTILITY LINES WITHIN
 THE SUBJECT PROPERTY SHALL BE BURIED AT THE TIME OF NEW
 CONSTRUCTION.
  
 2) REPEAT COMMENT: PROVIDE VERIFICATION FROM THE CITY'S
 ENGINEERING SERVICES & PUBLIC WORKS DEPARTMENT THAT THE
 FOLLOWING ADDITIONAL OUTSTANDING ITEMS FROM RESOLUTION
 NO. 266-12 HAVE BEEN MET:
  
 A. BUILDING PERMIT: PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR ANY CONSTRUCTION RELATING TO THE DEVELOPMENT
 APPROVED AS PART OF THE HULETT ENVIRONMENTAL SERVICES
 CPD, THE APPLICANT SHALL PROVIDE VERIFICATION THAT THE
 FOLLOWING ITEMS HAVE BEEN SUBMITTED TO THE CITY'S
 ENGINEERING & PUBLIC WORKS DEPARTMENT:
  
 I. SIGNED AND SEALED DRAINAGE CALCULATIONS AND A COPY
 OF THE SOUTH FLORIDA WATER MANAGEMENT DISTRICT PERMIT.
  
 II. VERIFICATION OF THE PALM BEACH COUNTY WATER AND
 SANITARY SEWER APPROVALS.
  
 III. THE STORMWATER SYSTEM DESIGN.
  
 IV. A TRAFFIC PLAN DESIGN, INCLUDING ALL DRIVEWAY
 CONNECTIONS WEKIVA WAY FOR ALL ADJACENT BUSINESSES.
  
 V. FINAL ENGINEERING PLANS CONTAINING SECTIONS FOR THE
 PROPOSED PARKING LOT AND PAVING AND DRAINAGE DETAILS.
  
 3) REPEAT COMMENT: THE SITE PLAN AND REGULATING PLAN
 ARE NOT THE APPROVED VERSIONS (APPROVED VERSIONS ARE
 DATED 7/20/12).
  
 4 ) REPEAT COMMENT: SHEET A1-1 NEEDS TO SHOW TWO (2)
 FEET FROM THE BACK OF THE WHEEL STOP TO THE END OF THE
 PARKING SPACE NOT 1.5 FEET.
  
 5) REPEAT COMMENT: PROVIDE A DRAWING THAT VERIFIES THAT
 THE ROOF TOP MECHANICAL EQUIPMENT IS SCREENED FOR VIEW
 BY THE PARAPET. THE MECHANICAL EQUIPMENT STAND IS OVER
 TWO (2) FEET TALL, EXCLUDING THE EQUIPMENT, AND NO
 INFORMATION IS PROVIDED ON THE PARAPET HEIGHT.
  
 6) THE FOLLOWING SEPARATE PERMITS ARE REQUIRED:
  
 A. LANDSCAPE (LANDSCAPE PLAN SUBMITTED WAS NOT THE
 APPROVED LSP) - REPEAT COMMENT.
 B, AWNING
 C. SIGNAGE
 D. SITE LIGHTING (THE PHOTOMETRIC CALCULATIONS SHALL BE
 EXTENDED TO THE PROPERTY LINE TO VERIFY THAT THE
 LIGHTING DOES NOT EXCEED ONE FOOT CANDLE AT THE
 PROPERTY LINE, WHICH IT DOES ALONG THE EASTERN BOUNDARY
 (REPEAT COMMENT).
 E. SITE CIVIL TO THE CITY'S ENGINEERING & PUBLIC WORKS
 DEPARTMENT PLEASE NOTE THAT THE PAVING, DRAINAGE AND
 GRADING PLAN INCLUDED WITH THIS SUBMITTAL IS NOT
 CORRECT. IT SHOWS ONE SPACE TOO MANY IN THE PARKING BAY
 ON THE NORTH SIDE OF THE ACCESS ROAD (REPEAT COMMENT).
 F. PARKING LOT STRIPING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2012-12-05 Cont ID  
Sent By eschneid Date 2012-12-05 Time 11:09 Rev Time 3.00
Received By eschneid Date 2012-12-05 Time 11:09 Sent To  
Notes
2012-12-05 11:51:37FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES TO THE COMMENTS BELOW:
  
 1) OUTSTANDING ITEMS FROM RESOLUTION NO. 266-12 (WHICH
 WERE ALSO INCLUDED ON PREVIOUS ORDINANCE NO. 4318-11)
 APPROVED ON OCTOBER 29, 2012:
  
 A. TREE MITIGATION: PRIOR TO THE ISSUANCE OF A
 DEMOLITION OR SITE CLEARING PERMIT FOR ACTIVITY
 RELATING TO THE DEVELOPMENT APPROVED AS PART OF THE
 HULETT ENVIRONMENTAL SERVICES CPD, THE APPLICANT SHALL:
  
 I. OBTAIN APPROVAL OF A TREE ALTERATION PERMIT FROM THE
 PLANNING DIVISION.
  
 II. PROVIDE A MITIGATION PLAN FOR THE 94 CALIPER INCHES
 OF EXISTING TREES THAT ARE BEING REMOVED AS PART OF THE
 DEVELOPMENT PLAN. THE TREE MITIGATION SHALL EITHER
 OCCUR ON-SITE OR OFF-SITE AND SHALL BE APPROVED BY THE
 PLANNING DIVISION AS PART OF THE TREE ALTERATION
 PERMIT.
  
 B. PREPARE A CONSTRUCTION SITE SECURITY AND MANAGEMENT
 PLAN FOR APPROVAL BY THE CITY'S POLICE DEPARTMENT CRIME
 PREVENTION THROUGH ENVIRONMENTAL DESIGN (CPTED)
 OFFICIAL.
  
 I. THE APPLICANT, AFTER SITE CLEARING AND PLACEMENT OF
 CONSTRUCTION TRAILERS, SHALL INSTITUTE SECURITY
 MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES FOR
 THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT BE
 LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL,
 VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS,
 REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE
 SUBCONTRACTORS TO SECURE MACHINERY AND TOOLS AT END OF
 WORK DAY, FENCING WITH SCREENING, AND/OR ANY OTHER
 MEASURE DEEMED APPROPRIATE TO PROVIDE A SAFE AND SECURE
 WORKING ENVIRONMENT.
  
 II. THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED
 THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT.
 NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A
 STOP-WORK ORDER FOR THE ENTIRE PLANNED DEVELOPMENT.
  
 III. "NO TRESPASSING" SIGNS SHALL BE POSTED EVERY 500
 FEET AROUND THE PERIMETER OF THE CONSTRUCTION SITE.
  
 C. VERIFICATION THAT ALL OVERHEAD UTILITY LINES WITHIN
 THE SUBJECT PROPERTY SHALL BE BURIED AT THE TIME OF NEW
 CONSTRUCTION.
  
 2) ADDITIONAL OUTSTANDING ITEMS FROM RESOLUTION NO.
 266-12:
  
 A. BUILDING PERMIT: PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR ANY CONSTRUCTION RELATING TO THE DEVELOPMENT
 APPROVED AS PART OF THE HULETT ENVIRONMENTAL SERVICES
 CPD, THE APPLICANT SHALL PROVIDE VERIFICATION THAT THE
 FOLLOWING ITEMS HAVE BEEN SUBMITTED TO THE CITY'S
 ENGINEERING & PUBLIC WORKS DEPARTMENT:
  
 I. SIGNED AND SEALED DRAINAGE CALCULATIONS AND A COPY
 OF THE SOUTH FLORIDA WATER MANAGEMENT DISTRICT PERMIT.
  
 II. VERIFICATION OF THE PALM BEACH COUNTY WATER AND
 SANITARY SEWER APPROVALS.
  
 III. THE STORMWATER SYSTEM DESIGN.
  
 IV. A TRAFFIC PLAN DESIGN, INCLUDING ALL DRIVEWAY
 CONNECTIONS WEKIVA WAY FOR ALL ADJACENT BUSINESSES.
  
 V. FINAL ENGINEERING PLANS CONTAINING SECTIONS FOR THE
 PROPOSED PARKING LOT AND PAVING AND DRAINAGE DETAILS.
  
 3) THE SITE PLAN AND REGULATING PLAN ARE NOT THE
 APPROVED VERSIONS (APPROVED VERSIONS ARE DATED
 7/20/12).
  
 4 ) SHEET A1-1 NEEDS TO SHOW TWO (2) FEET FROM THE BACK
 OF THE WHEEL STOP TO THE END OF THE PARKING SPACE NOT
 1.5 FEET.
  
 5) PROVIDE A DRAWING THAT VERIFIES THAT THE ROOF TOP
 MECHANICAL EQUIPMENT IS SCREENED FOR VIEW BY THE
 PARAPET. THE MECHANICAL EQUIPMENT STAND IS OVER TWO (2)
 FEET TALL, EXCLUDING THE EQUIPMENT, AND NO INFORMATION
 IS PROVIDED ON THE PARAPET HEIGHT.
  
 6) THE FOLLOWING SEPARATE PERMITS ARE REQUIRED:
  
 A. LANDSCAPE (LANDSCAPE PLAN SUBMITTED WAS NOT THE
 APPROVED LSP)
 B, AWNING
 C. SIGNAGE
 D. SITE LIGHTING (THE PHOTOMETRIC CALCULATIONS SHALL BE
 EXTENDED TO THE PROPERTY LINE TO VERIFY THAT THE
 LIGHTING DOES NOT EXCEED ONE FOOT CANDLE AT THE
 PROPERTY LINE, WHICH IS DOES ALONG THE EASTERN
 BOUNDARY)
 E. SITE CIVIL TO THE CITY'S ENGINEERING & PUBLIC WORKS
 DEPARTMENT PLEASE NOTE THAT THE PAVING, DRAINAGE AND
 GRADING PLAN INCLUDED WITH THIS SUBMITTAL IS NOT
 CORRECT. IT SHOWS ONE SPACE TOO MANY IN THE PARKING BAY
 ON THE NORTH SIDE OF THE ACCESS ROAD.
 F. PARKING LOT STRIPING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2012-03-14 Cont ID  
Sent By eschneid Date 2012-03-14 Time 11:53 Rev Time 0.25
Received By eschneid Date 2012-03-14 Time 11:53 Sent To  
Notes
2012-03-14 12:04:14FAILED
  
 THIS BUILDING NEEDS TO BE APPROVED BY THE CITY
 COMMISSION AS A MAJOR PLANNED DEVELOPMENT AMENDMENT. IT
 IS AT LEAST 2.5 MONTHS AWAY FROM THE CITY COMMISSION
 HEARING DATE. ZONING STAFF WILL NOT REVIEW THE
 APPLICATION UNTIL IT HAS GONE THROUGH THE PUBLIC
 HEARING PROCESS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.