Plan Review Stops For Permit 12030117 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2012-06-01 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2012-06-01 |
Time |
10:07 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2012-06-01 |
Time |
10:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2012-05-31 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2012-05-31 |
Time |
09:33 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2012-05-30 |
Time |
16:44 |
Sent To |
|
|
Notes |
2012-05-31 09:57:38 | ****CORRECTIONS**** | | ****PLAN REVIEW IN PROGRESS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | | | **IF ALL OTHER TRADES PASS REVIEW, ITEM 2 CAN BE | | ADDRESSED VIA EMAIL (ON ARCHITECT'S LETTERHEAD). PERMIT | | WILL BE ISSUED WITH A PROVISO THAT SHEET LS1 BE | | REVISED** | | | | 1. IMPACT FEES ASSESSMENT REQUIRED, 561-233-5025 FOR | | MORE INFORMATION. | | | | 2. SHEET LS 1, PLEASE REVISE THE ALLOWABLE AREAS TO | | INCLUDE THE FORMULA FOR AREA INCREASE FBC 506.1 WITH | | ENOUGH INFORMATION TO CONFIRM ACCURACY. | | | | REVISE PLAN TO DESIGNATE THE VARIOUS TENANT SPACES AND | | OCCUPANCY CLASSIFICATION. | | | | SEE FBC 506.3, A 3X SPRINKLER INCREASE IS FOR BUILDINGS | | WITH ONE STORY ABOVE GRADE. AS THIS IS A THREE STORY | | BUILDING, IT APPEARS THAT A 2X INCREASE SHOULD BE USED. | | | | SEE FBC 506.2, PLAN STATES THAT A 100% FRONTAGE (OPEN | | AREA INCREASE) WAS USED TO DETERMINE AREA, BUT THE AREA | | SHOULD BE REVISED AS THE REAR DOES NOT HAVE 30' TO | | PROPERTY LINE AND DISTANCE TO PROPERTY LINE IS UNCLEAR | | ON THE NORTH SIDE (SEE FBC 506.2.2). THE FORMULA | | APPEARS TO ALLOW A 75% INCREASE IF THERE IS 30' OPEN | | AREA AROUND THE ENTIRE PERIMETER, NOT 100%. | | | | IF YOU CANNOT COMPLY WITH THE BUILDING AREA LIMITATION | | PER FBC TABLE 503 FOR THE WORST CASE (A3, 15,500 SF), | | THE FORMULA SHOULD BE WEIGHTED FOR THE VARIOUS | | OCCUPANCIES AND OCCUPANCY SEPARATION WILL BE REQUIRED | | IN ADDITION TO TENANT SEPARATION, SEE FBC 506.4.1. | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2012-04-19 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2012-04-19 |
Time |
13:33 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2012-04-12 |
Time |
08:24 |
Sent To |
|
|
Notes |
2012-04-19 14:37:12 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. COMMENTS FROM PREVIOUS CHECKLIST WERE PROPERLY | | ADDRESSED WITH EXCEPTION OF IMPACT FEES. NEW COMMENTS | | ARE BASED ON NEW INFORMATION PROVIDED. | | | | 2. PROVISO ITEM, FBC EXISTING BUILDING, INTERIOR | | FINISHES (BOTH EXISTING AND NEW) TO COMPLY WITH FBC | | TABLE 803.5 FOR ASSEMBLY OCCUPANCY. | | | | 3. FBC EXISTING BUILDING 912.4.1, FBC 1008.1.9, EACH | | DOOR IN GROUP A WITH AN OCCUPANT LOAD OF 50 OR MORE | | SHALL NOT BE PROVIDED WITH A LATCH OR LOCK UNLESS IT IS | | PANIC HARDWARE OR FIRE EXIT HARDWARE, SEE ALSO | | EXCEPTION FOR MAIN DOOR. PLEASE ADVISE, WHICH DOORS | | WILL BE ALTERED AND IF EXTERIOR EXIT DOORS ARE TO BE | | REPLACED, PROVIDE PRODUCT APPROVALS AND NOTE ON PLAN. | | | | 4. THE MAIN ENTRY IS NOT CLEAR. PLEASE PROVIDE | | INFORMATION REGARDING HOW OCCUPANTS WILL ENTER THIS | | SPACE, FBC 1008. IT APPEARS THAT THE AREA IN THE | | COVERED PARKING MARKED GRAND STAIR IS THE MAIN ENTRANCE | | TO BOTH THIS TENANT SPACE AS WELL AS THE ADJACENT | | SPACES. | | | | 5. FBC EXISTING BUILDING 912.4.1, FBC 1008.1.2, DOORS | | ARE TO SWING IN THE DIRECTION OF TRAVEL WHERE THE | | OCCUPANT LOAD EXCEEDS 50. THE DOOR WHICH APPEARS TO BE | | THE MAIN ENTRY, DOOR 1 TO THE VALET, DOES NOT SWING IN | | THE DIRECTION OF EGRESS TRAVEL. THE NOTE WHICH STATES | | THAT THIS IS TO BE MARKED AS NOT AN EXIT IS NOTED; | | HOWEVER, IT APPEARS THAT THIS IS THE MAIN ENTRY FOR | | THIS PORTION OF THE BUILDING, AND OCCUPANTS TEND TO | | EXIT IN THE SAME MANNER IN WHICH THEY ENTERED. | | | | 6. FBC EXISTING BUILDING 912.4.1, FBC 1025.2, WIDTH OF | | THE MAIN ENTRANCE IS TO ACCOMMODATE FIFTY PERCENT OF | | THE OCCUPANT LOAD. PLEASE NOTE THAT, IF DOOR 1 TO VALET | | AREA IS THE MAIN ENTRANCE, AND THE GRAND STAIR REWORKED | | BY EXTENDING THE LANDING, IT APPEARS THAT IT MAY BE | | POSSIBLE TO ADD EXIT DOORS TO THE LOBBY AREA TO | | INCREASE EXIT CAPACITY. | | | | 7. FBC EXISTING BUILDING 912.4.1, FBC 1009, PLEASE | | PROVIDE STAIR WIDTHS. PLEASE CONFIRM THAT ANY STAIRS | | WHICH DO NOT SHOW RISER AND TREAD DIMENSIONS ARE IN | | COMPLIANCE. REGARDING THE STAIRS WHICH HAVE A 7.25 RISE | | RATHER THAN A 7 INCH RISE AS REQUIRED, THESE STAIRS MAY | | REMAIN IN USE. HOWEVER, PLEASE REWORK STAIRS WHICH SHOW | | A TREAD LESS THAN 11 INCHES. | | | | 8. PROVIDE THE WIDTH FOR THE EXIT RAMPS, FBC EXISTING | | BUILDING 912.4.1, FBC 1010. | | | | 9. PLEASE REVISE THE OCCUPANT LOAD FOR THE SOCCER | | FIELDS AND INCLUDE AN OCCUPANT LOAD FOR THE FUTURE | | BASKETBALL COURT. THE OCCUPANT LOAD SHOULD INCLUDE THE | | 12 PLAYERS, SUPPORT PARTICIPANTS SUCH AS SUBSTITUTES, | | OFFICIALS, COACHES, AND A REASONABLE NUMBER OF | | SPECTATORS. | | | | 10. FBC EXISTING BUILDING 912.4.1, ALL ELEMENTS IN THE | | MEANS OF EGRESS SUCH AS HANDRAILS, GUARDRAILS ARE TO | | COMPLY WITH FBC CHAPTER 10. IN LIEU OF REQUIRING | | DETAILS FOR EVERY EXISTING ELEMENT, THIS WILL BE A | | PROVISO ITEM. | | | | 11. IMPACT FEES MAY BE DUE TO PALM BEACH COUNTY. | | 233-5025 FOR MORE INFORMATION. THE PLANS ARE TO BE | | STAMPED AND THE RECEIPT PROVIDED. | | | | PLEASE FEEL FREE TO CONTACT ME AT YOUR CONVENIENCE TO | | DISCUSS. | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2012-03-08 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2012-03-08 |
Time |
10:40 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2012-03-07 |
Time |
15:49 |
Sent To |
|
|
Notes |
2012-03-08 11:08:08 | ****CORRECTIONS**** | | ****REVISED 3/16**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. PLEASE STATE WHICH METHOD IMPLEMENTED IN THE DESIGN | | OF THIS ALTERATION, PLEASE SEE FBC EXISTING BUILDING | | 101.5. | | | | 2. PLEASE REVISE PLAN TO SHOW EXISTING FIRE RATED WALLS | | (OCCUPANCY SEPARATION, CORRIDORS, ETC.), AND PROPOSED | | NEW FIRE RATED WALLS. FBC CHAPTER 7. IT IS NOT CLEAR | | WHERE THE RATED WALLS TERMINATE AT THE TOP, NO HEAD OF | | WALL DETAIL PROVIDED, FBC708.4. | | | | 3. PROVIDE A CODE SUMMARY - EXISTING OCCUPANCY | | CLASSIFICATION, PROPOSED NEW OCCUPANCY CLASSIFICATION, | | OCCUPANT LOAD FBC1004, BUILDING TYPE, SPRINKLER | | INFORMATION, . IF THIS IS A CHANGE OF OCCUPANCY, PLANS | | SHOULD CLEARLY SHOW COMPLIANCE WITH REQUIREMENTS. | | PROVIDE A LIFE SAFETY PLAN FOR THE NEW OCCUPANCY. | | | | 4. REVISE FLOOR PLAN TO PROVIDE AREA USE DESIGNATIONS. | | APPLICATION MAKES REFERENCE TO AN INDOOR SOCCER ARENA, | | PLANS SHOW LOBBY IN AN EXISTING WAREHOUSE. | | | | 5. IMPACT FEES MAY BE DUE TO PALM BEACH COUNTY. | | 233-5025 FOR MORE INFORMATION. THE PLANS ARE TO BE | | STAMPED AND THE RECEIPT PROVIDED. | | | | | | | | | | | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2012-05-30 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2012-05-30 |
Time |
11:06 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2012-05-30 |
Time |
09:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2012-04-25 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2012-04-25 |
Time |
17:30 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2012-04-25 |
Time |
16:11 |
Sent To |
|
|
Notes |
2012-04-25 17:14:18 | 12030117 | | 1016 CLARE AVE. #4 | | INTERIOR REMODEL FOR INDOOR SOCCER | | | | PLEASE SUBMIT AN ELECTRICAL PLAN. | | | | INCLUDE A RISER PLAN SHOWING THE NEW AND EXISTING | | ELECTRIC SERVICE COMPONENTS WITH MAIN DISCONNECT, | | SERVICE GROUNDING, CONDUIT SIZE AND TYPE, VOLTAGE, | | CONDUCTOR SIZE AND TYPE ALL LOCATED ON THE PLAN. | | INCLUDE A SUMMARY LOAD CALCULATION SHOWING EXISTING | | ELECTRIC SERVICE CAN HANDLE THE NEW LOADS; VERIFY | | SAFETY CLEARANCES AND ACCESS. NEC 110.26, 215.5 | | PROVIDE PANEL SCHEDULES SHOWING RATING, SIZE AND WIRING | | METHOD FOR THE NEW ELECTRICAL CIRCUITS. NEC 210.3 | | SHOW SERVICE LOCATION ON THE PLAN. NEC 230.72 | | SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE | | CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES | | AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL | | FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3, | | EXISTING BUILDING CODE 711.1 | | PROVIDE AN INTERSYSTEM BONDING TERMINAL. NEC 250.94 | | PROVIDE FOR GFCI PROTECTION FOR ANY PROPOSED VENDING | | MACHINES. NEC 422.51 | | GFCI PROTECTION IS REQUIRED FOR RECEPTACLES IN | | BATHROOMS, OUTDOORS, AND ADJACENT TO SINKS. NEC 210.8 | | PROVIDE SPECIFICATIONS ON LIGHT FIXTURES SHOWING | | PROTECTION AGAINST DAMAGE. LUMINAIRES SUBJECT TO | | PHYSICAL DAMAGE INSTALLED IN PLAYING AREAS AND | | SPECTATOR SEATING AREAS SHALL BE PROTECTED FROM DAMAGE. | | NEC 410.10(E) | | VERIFY THE REQUIRED WORKING CLEARANCES AND DEDICATED | | WORKING SPACE HAS BEEN PROVIDED FOR THE ELECTRICAL | | EQUIPMENT AND PANEL BOARDS. NEC 110.26, 240.24, 408.17 | | PROVIDE A MECHANISM TO GUARD THE PANEL BOARDS TO | | PREVENT PHYSICAL DAMAGE IF LOCATED NEAR THE PLAYING | | FIELDS. NEC 110.27 | | SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE | | ALARM SYSTEM, VOICE AND DATA. | | | | ROBERT LECKY | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2012-03-12 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2012-03-12 |
Time |
12:08 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2012-03-12 |
Time |
11:29 |
Sent To |
|
|
Notes |
2012-04-25 16:24:18 | THIS REVIEW WAS FOR BATHROOMS AND NOT A CHANGE OF | | OCCUPANCY OR THE ADDITION OF SOCCER FIELDS. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2012-06-01 |
|
|
Cont ID |
|
Sent By |
ddaniels |
Date |
2012-06-01 |
Time |
11:00 |
Rev Time |
0.00 |
Received By |
ddaniels |
Date |
2012-06-01 |
Time |
11:00 |
Sent To |
|
|
Notes |
2012-06-01 11:05:32 | 06/01/2012 PLANS REVIEWS BY FIRE ***APPROVED*** | | | | ALL COMMENT ADDRESSED | | | | DERRICK DANIELS, BATTALION CHIEF / FIRE MARSHAL |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2012-04-27 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2012-04-27 |
Time |
11:45 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2012-04-27 |
Time |
10:30 |
Sent To |
|
|
Notes |
2012-04-27 11:00:17 | 1016 CLARE AVENUE - SUITE #4 | | PERMIT #12030117 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | EACH SMOKE OR FIRE-RATED WALL SHALL BE PERMANENTLY | | IDENTIFIED WITH SIGNS OR STENCILING READING FIRE/SMOKE | | BARRIER-PROTECT ALL OPENINGS. CHARACTERS SHALL BE AT | | LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN WIDTH. | | IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 FEET ON | | CENTER. | | | | PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL | | BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. | | | | SHEET LS-5: PROVIDE DETAILS (AISLE, HANDRAIL, | | GUARDRAIL) FOR THE 3 TIER BENCH TYPE SEATING. | | | | SHEET M1: NO FIRE DAMPERS SHOWN FOR DUCTWORK PASSING | | THROUGH FIRE-RATED WALLS. | | | | WESLEY JOLIN | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2012-03-09 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2012-03-09 |
Time |
13:23 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2012-03-09 |
Time |
12:56 |
Sent To |
|
|
Notes |
2012-03-09 13:23:01 | 1016 CLARE AVENUE - SUITE #4 | | PERMIT #12030117 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | THE PLANS INDICATE THE USE OF FIRE RATED GYPSUM BOARD | | FOR ALL NEW PARTITIONS. ARE ALL OPENINGS AND | | PENETRATIONS INTENDED TO BE PROTECTED? | | | | INDICATE EXISTING WALLS THAT HAVE A FIRE RATING WITH | | PROTECTED OPENINGS AND PENETRATIONS. | | | | ALL FIRE RATED DOORS SHALL BE SELF CLOSING AND POSITIVE | | LATCHING. | | | | PROVIDE A PERMANENT SIGN ON THE CORRIDOR DOOR OF THE | | FIRE ROOM INDICATING "FACP" AND "SPR RISER". | | | | FIRE SPRINKLERS WILL NEED TO BE ADDED/RELOCATED TO | | ACCOUNT FOR THE NEW ROOMS AND NEW WALL LOCATIONS. | | | | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE | | ALARM SYSTEM. | | | | WESLEY JOLIN | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2012-06-01 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2012-06-01 |
Time |
12:16 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2012-05-24 |
Time |
11:10 |
Sent To |
|
|
Notes |
2012-05-29 11:12:40 | INCOMING SENT TO B-06 BOX, EXPEDITED/ 2ND EXPEDITED | | REVIEW/ 3RD REVIEW. JW |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2012-05-02 |
|
|
Cont ID |
|
Sent By |
lmartine |
Date |
2012-05-02 |
Time |
08:56 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2012-04-05 |
Time |
09:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2012-03-29 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2012-03-29 |
Time |
11:08 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2012-03-06 |
Time |
11:15 |
Sent To |
|
|
Notes |
2012-03-07 11:16:08 | EXPEDITED | | B--4 |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2012-06-05 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2012-06-05 |
Time |
13:41 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2012-06-05 |
Time |
13:41 |
Sent To |
|
|
Notes |
2012-06-05 13:41:54 | MU 2012 010236 0000 |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2012-03-16 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2012-03-16 |
Time |
09:03 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2012-03-16 |
Time |
09:03 |
Sent To |
|
|
Notes |
2012-03-16 09:03:56 | SEE BUILDING REVIEW. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2012-05-29 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2012-05-29 |
Time |
15:46 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2012-05-29 |
Time |
14:21 |
Sent To |
|
|
Notes |
2012-05-29 15:46:23 | PROVISO | | 1) PROVIDE THE NOA. FOR OUT SIDE LUVER.REFER TO RULE 9 | | N3 SECTION 72.101 (31) C . | | 2) REFER TO SECTION 304.1 GENERAL 2010 FBC (M) | | PROVIDE MANUFACTURE INSTALLATION INSTRUCTIONS FOR FIRE | | DAMPERS AT FIRST INSPECTION | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2012-04-25 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2012-04-25 |
Time |
10:25 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2012-04-25 |
Time |
10:05 |
Sent To |
|
|
Notes |
2012-04-25 10:25:43 | PLANS DENIED | | 1) PROVIDE FRESH AIR CALCULATIONS PER SECTION | | 13-409.AB.3.3 | | 2) PROVIDE ENERGY CALCULATIONS PER SECTION 13- 470.AB.1 | | SIZING. | | 3) NOTES ON PLANS SAY SEE SHEET M-2 .NO SHEET M-2 WAS | | SUBMITTED | | 4) PROVIDE PRODUCT APPROVALS FOR OUTSIDE GRILL FOR BATH | | EXHAUST 106.3 FBC. | | 5) ELEVATOR EQUIPMENT ROOM AND STORAGE ROOM SHOW NEW | | DUCT NOT EXISTING . | | PAGE M-1 OF PLANS. | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2012-03-14 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2012-03-14 |
Time |
12:21 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2012-03-14 |
Time |
10:25 |
Sent To |
|
|
Notes |
2012-03-14 12:21:19 | PLANS DENIED | | 1) PROVIDE PRODUCT APPROVALS FOR OUTSIDE AIR GRILLE, | | AND SIZE OF GRILLE. | | SECTION 106.3 FBC. | | 2) ELEVATOR EQUIPMENT ROOM AND STORAGE ROOM SHOW NEW | | DUCT | | PROVIDE DUCT AND GRILLE SIZE ON THE PLANS | | 3) PROVIDE TWO COPIES OF THE MANUFACTURERS INSTALLATION | | INSTRUCTIONS ON | | THE FIRE DAMPERS WITH THE PLANS 304.1 GENERAL 2007 FBC | | (M) | | 4) REFER TO SECTION 601.4 BALANCED RETURN AIR EXCEPTION | | #3 FOR | | STORAGE ROOM. | | 5) REFER TO SECTION 601.4 BALANCED RETURN AIR FOR LOBBY | | 2007 FBC (M) | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2012-04-26 |
|
|
Cont ID |
|
Sent By |
lwagner |
Date |
2012-04-26 |
Time |
12:51 |
Rev Time |
0.00 |
Received By |
lwagner |
Date |
2012-04-26 |
Time |
12:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2012-03-13 |
|
|
Cont ID |
|
Sent By |
lwagner |
Date |
2012-03-13 |
Time |
13:48 |
Rev Time |
0.00 |
Received By |
lwagner |
Date |
2012-03-13 |
Time |
12:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2012-06-01 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2012-06-01 |
Time |
10:48 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2012-06-01 |
Time |
10:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2012-05-02 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2012-05-02 |
Time |
08:55 |
Rev Time |
0.00 |
Received By |
lmartine |
Date |
2012-05-02 |
Time |
08:55 |
Sent To |
|
|
Notes |
2012-05-02 08:55:32 | SEE PLANS FOR ZONING APPROVAL |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2012-03-29 |
|
|
Cont ID |
|
Sent By |
astelly |
Date |
2012-03-29 |
Time |
11:08 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2012-03-29 |
Time |
11:08 |
Sent To |
|
|
Notes |
2012-03-29 11:08:42 | PER ANGELLA VANN, PLEASE PROVIDE PLANS FOR THE CHANGE | | OF OCCUPANCY. | | | | S HILL | | 805-6724 |
|
|