Plan Review Details - Permit 12030094
Plan Review Stops For Permit 12030094
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-03-29 Cont ID  
Sent By rmcdouga Date 2012-03-29 Time 16:52 Rev Time 0.00
Received By rmcdouga Date 2012-03-29 Time 16:51 Sent To  
Notes
2012-03-29 16:54:17PRODUCT APPROVALS FOR EXTERIOR DOORS WERE SUBMITTED BY
 MISTAKE. NO EXTERIOR DOORS ARE BEING REPLACED PER
 CONTRACTOR.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-03-19 Cont ID  
Sent By rmcdouga Date 2012-03-19 Time 13:26 Rev Time 0.00
Received By rmcdouga Date 2012-03-14 Time 08:10 Sent To  
Notes
2012-03-19 13:52:212007 FBC W/2009 REVISIONS
  
 1) THE PRODUCT APPROVAL FOR THE EXTERIOR GLAZED DOOR
 HAS DESIGN PRESSURES OF + 48 , -51 PSF AND THE PLANS
 SPECIFY THE REQUIRED PRESSURES FOR A 10 SQFT OPENING OF
 +56, -55 PSF. PLEASE SUBMIT PRODUCT APPROVALS FOR A
 DOOR WITH DESIGN PRESSURES GREATER THAN THE ONES
 SPECIFIED ON THE PLANS. FBC R301.2.1
  
 2) THE GLAZED EXTERIOR DOOR IS REQUIRED BY FBCR
 301.2.1.2 AND EXISTING BUILDING 606.4 TO HAVE OPENING
 PROTECTION FROM WIND BORNE DEBRIS. THE PRODUCT APPROVAL
 THAT WAS SUBMITTED IS FOR A NON-IMPACT GLAZED DOOR.
 SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR STORM PANELS
 AND INSTALLATION SCHEDULES FOR THE NEW GLAZED DOORS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-03-26 Cont ID  
Sent By rlecky Date 2012-03-26 Time 10:14 Rev Time 0.00
Received By rlecky Date 2012-03-26 Time 10:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-03-08 Cont ID  
Sent By rlecky Date 2012-03-08 Time 13:08 Rev Time 0.00
Received By rlecky Date 2012-03-08 Time 12:49 Sent To  
Notes
2012-03-08 13:08:2312030094
 1449 8TH ST.
 INTERIOR RENOVATION
  
 PROVIDE AN ELECTRIC SERVICE RISER PLAN WITH WIRE SIZES,
 GROUNDING ETC. INDICATE THE LOCATION OF THE SERVICE.
 SHOW LOCATION OF MAIN BREAKER AND METER. NEC 215.15
 THE MAIN SERVICE DISCONNECT MUST BE LOCATED NEAREST THE
 POINT OF ENTRANCE OF THE SERVICE CONDUCTORS. NEC 230.70
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. FBC R313
 FOR THE NEW WALL SPACES ADD RECEPTACLES SO THAT NO WALL
 SPACE IS MORE THAN 6 FEET FROM A RECEPTACLE AND ALL
 WALL SPACES MORE THAN 2 FEET IN WIDTH HAVE A RECEPTACLE
 I.E. NEW CLOSET WALL. NEC 210.52
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. 2008 NEC 250.94
 ALL NEW RECEPTACLES SHALL BE TAMPER RESISTANT. 2008 NEC
 406.11
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-03-29 Cont ID  
Sent By rmcdouga Date 2012-03-29 Time 16:52 Rev Time 0.00
Received By rmcdouga Date 2012-03-23 Time 10:14 Sent To  
Notes
2012-03-23 10:03:38TO ELECTRIC

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-03-19 Cont ID  
Sent By rmcdouga Date 2012-03-19 Time 13:26 Rev Time 0.00
Received By rmcdouga Date 2012-03-06 Time 11:31 Sent To  
Notes
2012-03-06 11:31:45 
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2012-03-19 Cont ID  
Sent By rmcdouga Date 2012-03-19 Time 08:29 Rev Time 0.00
Received By rmcdouga Date 2012-03-19 Time 08:29 Sent To  
Notes
2012-03-19 08:29:47NO MECHANICAL WORK IS SHOWN ON THE PLANS.

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-03-29 Cont ID  
Sent By rmcdouga Date 2012-03-29 Time 16:51 Rev Time 0.00
Received By rmcdouga Date 2012-03-29 Time 16:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-03-29 Cont ID  
Sent By rmcdouga Date 2012-03-19 Time 08:21 Rev Time 0.00
Received By rmcdouga Date 2012-03-19 Time 08:21 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2012-03-19 Cont ID  
Sent By jroach Date 2012-03-19 Time 13:52 Rev Time 0.00
Received By rmcdouga Date 2012-03-19 Time 13:52 Sent To  
Notes
***NONE***