Plan Review Details - Permit 12030044
Plan Review Stops For Permit 12030044
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2012-08-29 Cont ID  
Sent By jwitmer Date 2012-08-28 Time 10:00 Rev Time 0.00
Received By jwitmer Date 2012-08-27 Time 10:12 Sent To  
Notes
2012-08-27 10:12:44BUILDING PROVISO:
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) 8/24/12 AS PER DISCUSSION WITH HENRY SHAWAH WITH
 WHITING-TURNER SINCE THE WIND PRESSURES ARE CODE
 COMPLIANT, THE PRODUCT APPROVALS WILL COME IN AT A
 LATER DATE, TO BE REVIEWED AS A REVISION UNDER SEPERATE
 REVIEW AND ASSOCIATED FEES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-07-25 Cont ID  
Sent By jwitmer Date 2012-07-25 Time 15:20 Rev Time 0.00
Received By jwitmer Date 2012-07-17 Time 17:01 Sent To  
Notes
2012-07-25 16:40:46BUILDING PLAN REVIEW
 PERMIT: 12030044
 ADD: 4847 FRED GLADSTONE
 CONT: THE WHITING TURNER CO.
 TEL: (954)776-0800
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 7/25/2012
 ACTION: DENIED
  
 1-4E) COMPLIED.
  
  
  
 4F) FIRE/ SMOKE PARTITIONS INSPECT 2007/09 FBC-B
 420.3.10.21 WHERE IT IS NOT POSSIBLE TO INSPECT
 FIRE/SMOKE PARTITIONS BECAUSE OF THE FIRE-TESTED
 MEMBRANE, FIRE-RATED ACCESS PANELS SHALL BE INSTALLED
 ADJACENT TO EACH SIDE OF THE SMOKE PARTITIONS AT
 INTERVALS NOT EXCEEDING 30 FEET (9.00 M) AND IN SUCH
 LOCATIONS AS NECESSARY TO VIEW ALL SURFACES OF THE
 PARTITION. FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS,
 SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING. SUCH IDENTIFICATION SHALL BE ABOVE ANY
 DECORATIVE CEILING AND IN CONCEALED SPACES. SUGGESTED
 WORDING FOR A FIRE/SMOKE PARTITION IS AS FOLLOWS: "FIRE
 AND SMOKE BARRIER - PROTECT ALL OPENINGS."
  
  
 4G) THIS WILL BE A COMMON STATEMENT FOR ALL SLEEPING
 UNITS FOR ALL COMPARTMENTS ON ALL FLOORS, THIS SHEET
 NOR IF SHEETS INDICATE HOW MANY OCCUPANTS ARE IN A ROOM
 NOR IS THERE A FURNITURE LAYOUT THAT WILL ALLOW FOR
 CODE COMPLIANCE FOR SECTION 403.2.2 & 403.2.3 FOR UNIT
 TYPES A-E.
  
 4H-4M) COMPLIED.
  
 4N)ALTERNATE MATERIALS & METHODS, CURRENTLY UNDER
 CONSIDERATION BY THE BUILDING OFFICIAL.
 COMMENT COMMEND TO ALL FLOORS. 2007/09 FBC-B 420.3.2.6
 DOORS TO RESIDENT TOILET ROOMS SHALL BE SIDE HINGED.
 PLEASE ALSO NOTE THE HARDWARE SCHEDULE DOES NOT
 INDICATE TYPE OF HARDWARE THAT WOULD MEET THE
 ACCESSIBILITY CODE 11-4.13.9.
  
 4O) COMMENT COMMON TO ALL FLOORS. 2007/09 FBC-B
 420.3.2.7 EACH RESIDENT SHALL HAVE A WARDROBE, LOCKER
 OR CLOSET FOR EACH RESIDENT.
  
  
 4P-4V) COMPLIED.
  
  
 5-7) COMPLIED.
  
 NEW COMMENT: SHEETS A-105, A106 & A-107 LOADED WRONG.
  
 8) SHEET A106 ROOF PLAN: EIGHT ROOF DRAINS ARE MISSING
 A EMERGENCY ROOF DRAIN. THE OVERFLOW SCUPPERS THAT ARE
 SHOWN (6) ARE LOCATED SOMEWHERE BETWEEN 2?- 4? ABOVE
 THE EDGE OF THE INSULATED ROOF. 1503.4.3 OVERFLOW
 SCUPPERS ARE DESIGNED TO BE USED WITH SCUPPERS WHERE
 THE ROOF SLOPES TO THE SCUPPERS, AND IF THE SCUPPERS
 ARE BLOCKED THEN THE OVERFLOW SCUPPERS WILL ONLY POND
 2-4 INCHES. WITH THE ROOF HAVING ??/ 12? OR 1? PER
 4?-0? AND THE ROOF DRAIN TO THE OVER FLOW SCUPPER IS 32
 FEET AWAY THE PONDING WOULD BE 8-10 INCHES DEEP.
  
 9-10) COMPLIED.
  
 11) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, SOLID & GLAZED, ROLL UP OR
 COILING OVERHEAD DOORS AND OR INCLUDING ROOF HATCHES.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E SKYLIGHTS
 (F) PRE-ENGINEERED A/C STANDS
  
 NEW COMMENT:
 ROOF TILE 05-0901.06 EXPIRED 12/16/07
 NOA 08-0528 AUTO-SLIDDERS/ NON- IMPACT, NO TECHNICAL
 SHEETS PROVIDED.
 NOA 08-0715.14 STOREFRONT / NON-IMPACT, NO TECHNICAL
 SHEETS PROVIDED.
 NOA 09-0121.10 FIXED WINDOW LMI NO TECHNICAL SHEETS
 PROVIED.
 NOA 09-0923.09 AMWELD OUTSWING DOOR NO TECHNICAL SHEETS
 PROVIDED.
 NOA 11-0119.24 LOUVER, NO TECHNICAL SHEETS PROVIDED.
 NOA 11-0822.10 NO TECHNICAL SHEETS PROVIDED.
 NOA 12-0206.11 NO TECHNICAL SHEETS PROVIDED.
 NOA 11-0722.10 BILCO ROOF HATCH NO TECHNICAL SHEETS
 PROVIDED.
  
 12) FBC-B 1609.1.2 PROTECTION OF OPENINGS. LARGE IMPACT
 RESISTANT GLAZING TO A HEIGHT OF 30'-0" OR :
 420.4.2.5.2 PERMANENTLY ATTACHED PROTECTIVE SYSTEMS
 SUCH AS SHUTTERS AND BAFFLING SHALL BE DESIGNED TO MEET
 THE WIND LOAD REQUIREMENTS OF THIS CODE AND THE DEBRIS
 IMPACT REQUIREMENTS AS SPECIFIED BY SECTIONS 1626.2
 THROUGH 1626.4.
  
 420.4.2.5.3 REMOVABLE PROTECTIVE SYSTEMS DESIGNED TO
 INTRICATELY FIT WITH THE WALL/WINDOW SYSTEM OF THE
 FACILITY AND STORED ON SITE AT THE FACILITY AND THAT
 MEET THE WIND LOAD REQUIREMENTS OF THIS CODE AND THE
 DEBRIS IMPACT REQUIREMENTS SPECIFIED BY SECTIONS 1626.2
 THROUGH 1626.4 MAY BE USED TO PROTECT THE EXTERIOR
 UNITS.
  
  
 PLEASE NOTE: 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR
 WIND-BORNE DEBRIS IMPACT PROTECTION QUESTION# 13
 RECOGNIZING SUCH CONCERNS AS ABSENTEE OWNERS, OR CASES
 WHERE LONGER TIME & EFFORT IS NECESSARY TO SECURE
 SHUTTERS ON LARGE OR MULTI-STORY BUILDINGS, WHAT
 MEASURES ARE BEING RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING IS DONE
 SUFFICIENTLY IN ADVANCE OF THE HURRICANE?
  
 IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE
 GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE,
 SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING,
 CHAPTER 1,
 ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY
 OF WEST PALM BEACH, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR
 ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION
 OF EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR
 MULTI-STORY BUILDINGS, OR MULTIPLE
 ON THE SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST
 BE SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS
 FOR REVIEW BY THE CONSTRUCTION SERVICES DEPARTMENT. ANY
 SUCH PLAN SHALL INCLUDE, AT A MINIMUM, ON SITE LOCATION
 OF THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH
 COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND
 THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE ACCOMPLISHED WITHIN
 TWELVE (12) HOURS OR LESS OF THE
 OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES
 OF A HURRICANE WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD)
 ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE
 MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO
 REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED
 UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE
 BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE.
  
 IN LEAU OF LARGE MISSILE IMPACT RATED WINDOWS, STORM
 SHUTTERS MAY BE USED ON THE FIRST FLOOR IF: 104.6*/
 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE DEBRIS IMPACT
 PROTECTION.
  
 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-03-21 Cont ID  
Sent By jwitmer Date 2012-03-21 Time 16:33 Rev Time 0.00
Received By jwitmer Date 2012-03-19 Time 08:30 Sent To  
Notes
2012-03-21 16:34:22 
 BUILDING PLAN REVIEW
 PERMIT: 12030044
 ADD: 4847 FRED GLADSTONE
 CONT: THE WHITING TURNER CO.
 TEL: (954)776-0800
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1A) PLEASE PROVIDE (3) SURVEY INDICATING WHAT FLOOD
 ZONE THIS NEW BUILDING WILL BE LOCATED. WPB ADMIN.
 106.3.5.1.
  
 1B) THERE ARE SEPARATE BUILDINGS AND FEATURES THAT ARE
 PART OF THIS PERMIT SET OF PLANS. SEPARATE ADDRESSES,
 PERMITS (PERMIT APPLICATIONS) AND ASSOCIATED FEES WILL
 BE REQUIRED FOR RECORD KEEPING PURPOSES (INSPECTIONS).
  
 2) PLEASE PROVIDE (3) ORIGINAL SOILS REPORTS 2007/09
 FBC-B1802.6.
  
 3) THIS BUILDING QUALIFIES FOR A SPECIAL RESIDENT
 INSPECTOR 109.3.7 WPB ADMIN.:
 A) TYPE II CONSTRUCTION
 B) FOR BUILDINGS WITH AN AREA GREATER THAN 20,000
 SQUARE FEET
 C) FOR BUILDINGS GREATER THAN 2 STORIES IN HEIGHT
 FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME'
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 4 SHEET A101, LIFE SAFETY SHEET G-101 AND A002
 PARTITION TYPES DO NOT MATCH UP:
  
 4A) STAIR # 3 OR ROOM # S103 WALL TAG TYPE F01 NO FIRE
 RATING VERSES G-101. FBC-B 1020.1.
  
 4B) STAIR # 3 WALL TAG MISSING, RATING FBC-B 1020.1.
  
 4C) STAIR # 3 SEE DETAIL # 1/ A451, WRONG PLAN UP
 LOADED, A551.
  
 4D) WALL TAG TYPE F01 IS INDICATED DRYWALL ON ONE SIDE,
 SEE
 FL. BOAF INFORMAL INTERPRETATIONS 6341 REQUIRING
 DRYWALL ON BOTH SIDES OF THE WALL.
  
 4E) COMMON STATEMENT FOR ALL FLOORS!!! SHEET A101
 VERSES G-101, LIFE SAFETY SHEETS INDICATE THE CORRIDOR
 WALLS TO BE SMOKE PARTITIONS AS REQUIRED BY SECTION
 2007/09 FBC-B 407.3 SMOKE PARTITIONS IN ACCORDANCE WITH
 SECTION 710 SMOKE PARTITIONS.
 PLEASE SEE BOAF INFORMAL INTERPRETATION # 6341.
 PLEASE PROVIDE ON SHEET A002 A HEADING TYPE FOR SMOKE
 PARTITIONS AND SMOKE BARRIER WALLS AS IS PROVIDED FOR
 FIRE RATED WALLS, ON THIS IDENTIFY WALL RATINGS.
 COMMON STATEMENT FOR ALL FLOORS!!! SHEET A101 VERSES
 G-101, LIFE SAFETY SHEETS INDICATE THE CORRIDOR WALLS
 TO BE SMOKE PARTITIONS AS REQUIRED BY SECTION 2007/09
 FBC-B 407.3 SMOKE PARTITIONS IN ACCORDANCE WITH SECTION
 710 SMOKE PARTITIONS. PLEASE PROVIDE ON SHEET A002 A
 HEADING TYPE FOR SMOKE PARTITIONS AND SMOKE BARRIER
 WALLS AS IS PROVIDED FOR FIRE RATED WALLS, ON THIS
 IDENTIFY WALL RATINGS.
  
  
 4F) FIRE/ SMOKE PARTITIONS INSPECT 2007/09 FBC-B
 420.3.10.21 WHERE IT IS NOT POSSIBLE TO INSPECT
 FIRE/SMOKE PARTITIONS BECAUSE OF THE FIRE-TESTED
 MEMBRANE, FIRE-RATED ACCESS PANELS SHALL BE INSTALLED
 ADJACENT TO EACH SIDE OF THE SMOKE PARTITIONS AT
 INTERVALS NOT EXCEEDING 30 FEET (9.00 M) AND IN SUCH
 LOCATIONS AS NECESSARY TO VIEW ALL SURFACES OF THE
 PARTITION. FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS,
 SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING. SUCH IDENTIFICATION SHALL BE ABOVE ANY
 DECORATIVE CEILING AND IN CONCEALED SPACES. SUGGESTED
 WORDING FOR A FIRE/SMOKE PARTITION IS AS FOLLOWS: "FIRE
 AND SMOKE BARRIER - PROTECT ALL OPENINGS."
  
  
 4G) THIS WILL BE A COMMON STATEMENT FOR ALL SLEEPING
 UNITS FOR ALL COMPARTMENTS ON ALL FLOORS, THIS SHEET
 NOR IF SHEETS INDICATE HOW MANY OCCUPANTS ARE IN A ROOM
 NOR IS THERE A FURNITURE LAYOUT THAT WILL ALLOW FOR
 CODE COMPLIANCE FOR SECTION 403.2.2 & 403.2.3 FOR UNIT
 TYPES A-E.
  
 4H) SMOKE COMPARTMENT/ SMOKE BARRIER FBC-B 407.4 WALL
 MISSING 1 HOUR FIRE RATING ON THIS SHEET AND A002, WALL
 TYPE A01 MISSING 1 HOUR FIRE RATING. SEE G-101.
  
 4I) COMMON TO ALL FLOORS. ELEVATOR SHAFT WALLS SHALL BE
 CONSTRUCTED IN ACCORDANCE WITH FBC-B 706.5.
  
 4J) COMMON TO ALL FLOORS VERTICAL EXIT STAIRWELL.
 MISSING WALL IDENTIFICATION TAG.
 G-101 INDICATES A TWO HOUR FIRE RATING. FBC-B 1020.1.
  
 4K) STAIRWELL S101 EXIT DOES NOT DISCHARGE AT THE
 EXTERIOR OF THE BUILDING. IT ALSO DOES NOT MEET THE
 REQUIREMENTS OF A VESTIBULE FBC 1024.1. WALL RATINGS?
  
 4L) ROOM 166, DOOR # 166 PLEASE NOTE THAT ON SHEET THE
 DOOR SCHEDULE THE HARDWARE IS NOT SPECIFIED, FBC-B
 420.3.3.8 LOCKABLE DOOR IS REQUIRED.
  
  
  
  
 4M) ROOM 166 WALL TAG M03 DETAIL IS MISSING ON SHEET
 A002. G-101 INDICATES THIS WALL IS PART OF THE SMOKE
 PARTITION REQUIREMENTS FOR CORRIDOR. FBC 407.3/ 710.
  
 4N COMMENT COMMEND TO ALL FLOORS. 2007/09 FBC-B
 420.3.2.6 DOORS TO RESIDENT TOILET ROOMS SHALL BE SIDE
 HINGED. PLEASE ALSO NOTE THE HARDWARE SCHEDULE DOES NOT
 INDICATE TYPE OF HARDWARE THAT WOULD MEET THE
 ACCESSIBILITY CODE 11-4.13.9.
  
 4O) COMMENT COMMON TO ALL FLOORS. 2007/09 FBC-B
 420.3.2.7 EACH RESIDENT SHALL HAVE A WARDROBE, LOCKER
 OR CLOSET FOR EACH RESIDENT.
  
  
 4P) THIS COMMENT IS FOR ALL DINING AREAS FOR ALL
 FLOORS. PLEASE PROVIDE THE SQUARE FOOT AREA OF EACH
 DINING AREA AND THE AMOUNT OF RESIDENTS TO BE SERVED.
 2007/09 FBC ?B 420.3.4.1.
  
 4Q) PLANS DO NOT INDICATE COMPLIANCE WITH 2007/09 FBC-B
 420.3.4.4 A BARBER/BEAUTY ROOM SHALL BE PROVIDED WITH
 FACILITIES AND EQUIPMENT FOR RESIDENT HAIR CARE AND
 GROOMING. THE AREA OF THE ROOM SHALL BE A MINIMUM OF
 200 SQUARE FEET (18.58 M2) WITH THE LEAST DIMENSION OF
 12 FEET (3.66 M).
  
 4R) ROOM 130C SOILED UTILITY 2 OF THE WALL
 IDENTIFICATION TAGS ARE A01 PLEASE REVIEW G-101
 REFERENCING A 1-HOUR WALL RATING. FBC-B 420.3.3.6/ SEE
 REQUIREMENTS FROM NFPA 101 HAZARDOUS AREAS LIFE SAFETY
 CODE ADOPTED BY THE FLORIDA FIRE PREVENTION CODE.
  
 4S) COMMENT COMMON TO ALL FLOORS. PROVIDE COMPLIANCE
 WITH:
 2007/09 FBC-B 420.3.3.13 STORAGE ALCOVE SPACE FOR A
 MINIMUM OF ONE WHEELCHAIR AND ONE STRETCHER SHALL BE
 PROVIDED IN AN AREA LOCATED AWAY FROM NORMAL TRAFFIC.
  
 4T) STAIRWELL # 2 WALL IDENTIFICATION TAG INDICATES
 TYPE F, STEEL STUD WALL PLANS APPEAR TO BE A BLOCK WALL
 PLEASE PROVIDE WALL TYPE AND COMPLIANCE WITH FBC-B
 1020.1.
  
 4U) WINDOW HAZARDOUS LOCATION FBC-B 2406.3 (5) 5.
 GLAZING IN DOORS AND ENCLOSURES FOR HOT TUBS,
 WHIRLPOOLS, SAUNAS, STEAM ROOMS, BATHTUBS AND SHOWERS.
 GLAZING IN ANY PORTION OF A BUILDING WALL ENCLOSING
 THESE COMPARTMENTS WHERE THE BOTTOM EXPOSED EDGE OF THE
 GLAZING IS LESS THAN 60 INCHES (1524 MM) ABOVE A
 STANDING SURFACE.
  
 4V) ROOM 172 A DOOR MAY REQUIRE 12" LATCH SIDE OF DOOR
 IN HALLWAY. NOTE DOOR SCHEDULE DOES NOT INDICATE
 HARDWARE.
 IF DOOR IS EQUIPPED WITH BOTH A DOOR CLOSER AND LATCH A
 CLEARANCE OF 112 INCHES IS REQUIRED.
  
 5) SHEET A-104 :
  
 5A) THE AREA OF THE GYMNASIUM IS APPROX 5340 SQ FT.
 SHEET G-0011 CODE SUMMARY DOES NOT PROVIDE THE SQUARE
 FOOTAGE PER FLOOR BUT IS INDICATING THE AREA INCREASE
 ALLOWED PER STORY IS 47,264. G101 DOES PROVIDE THE AREA
 OF THE THREE SMOKE COMPARTMENTS, TOTALING TO 36,565
 SQUARE FEET. THE AREA OF THE GYM IS OVER 10% OF THE
 FLOOR AREA (ACCESSORY OCCUPANCIES 508.3.1.) ACCESSORY
 OCCUPANCIES SHALL BE CLASSIFIED IN ACCORDANCE WITH
 SECTION 302.1. GYMNASIUMS ARE CLASSIFIED AS AN A-3
 OCCUPANCY FBC-B TABLE 508.3.3 WOULD REQUIRE 1 HOUR
 SEPARATION BETWEEN THE I-2 OCCUPANCY AND THE A-3
 GYMNASIUM WITH OPENING PROTECTION IN ACCORDANCE WITH
 FBC-B TABLE 715.4.
  
 5B) FL BC-B 11-6.1(3) LONG-TERM CARE FACILITIES AND
 NURSING HOMES. AT LEAST 50 PERCENT OF PATIENT BEDROOMS
 AND TOILETS, AND ALL PUBLIC USE AND COMMON USE AREAS
 ARE REQUIRED TO BE DESIGNED AND CONSTRUCTED TO BE
 ACCESSIBLE.
 IT APPEARS THAT THE BATHROOM 196A IS NOT ACCESSIBLE.
  
 5C) STORAGE ROOM 194A, LINEN STORAGE 190C, HOUSE
 KEEPING 194B & SOILED LINEN ROOM 190B DO NOT INDICATE
 ANY SMOKE AND OR FIRE RATINGS .
  
 5D) THERE IS AN UNIDENTIFIED AREA THAT APPEARS TO BE A
 RECEPTION COUNTER, ADDITIONAL INFORMATION IS REQUIRED,
 106.1.2/ 420.3.6.2.
  
 6) SHEET G102:
  
 6A) SMOKE COMPARTMENT WALL THAT SEPARATES COMPARTMENTS
 A/ B. WALL TYPE A01 & F01 BOTH ARE INDICATED AS NONE
 FIRE RATED. SMOKE COMPARTMENT WALLS REQUIRED BY 407.4
 SHALL BE IN ACCORDANCE WITH 709, 709.3 REQUIRES A 1
 HOUR SEPARATION CONTINUOUS FROM OUTSIDE OF WALL TO
 OUTSIDE OF WALL.
  
 6B) SATELLITE MAINTENANCE ROOM THE DOOR IS 45 MINUTE
 FIRE RATED BUT THE WALL DESIGNATION TAG A)! NO FIRE
 RATING. SEE G102 1 HR FIRE RATED.
  
 6C) CENTRAL STORAGE: G102 INDICATES THESE WALLS ALSO 1
 HOUR FIRE RATED WALLS.
  
 6D) ELEVATOR SHAFT WALL TAG DESIGNATION (F01) AS WELL
 AS STAIRWELL (STAIR # 1) WALLS 2 HRS IF FOUR STORIES OR
 MORE. FBC-B 1020.1.
  
 6E) SOILED UTILITY ROOM # 230C G102 INDICATES THE 1
 HOUR FIRE RATED WALLS FBC-B 420.3.3.6 NFPA 101
 CLASSIFIES AS HAZARDOUS LOCATION .
  
 6F) COMMON COMMENT TO ALL FLOORS. ROOM # 230A CART
 STORAGE, PLEASE PROVIDE ADDITIONAL INFORMATION, IT
 APPEARS THIS AREA MAY BE USED FOR LAUNDRY / LINEN CART
 STORAGE IF SO PLEASE PROVIDE DOCUMENTATION FOR A
 CLOSED-CART SYSTEM THAT WOULD BE IN COMPLIANCE WITH THE
 FLORIDA FIRE PREVENTION CODE, FBC-B 420.3.3.11.
  
 6G) WALL TYPE D01 ON G102 THIS WALL IS DESIGNATED AS A
 SMOKE PARTITION, PLEASE INDICATE COMPLIANCE WITH 710.
  
 7) SHEET G103:
  
 7A) MISSING INFORMATION ON WALL DESIGNATION TAG. SMOKE
 COMPARTMENT WALL/ SMOKE BARRIER FBC-B 709 1 HOUR RATING
 FROM OUTSIDE WALL TO OUTSIDE WALL.
  
 7B) SMOKE COMPARTMENT WALL THAT SEPARATES COMPARTMENTS
 A/ B. WALL TYPE A01 & F01 BOTH ARE INDICATED AS NONE
 FIRE RATED. SMOKE COMPARTMENT WALLS REQUIRED BY 407.4
 SHALL BE IN ACCORDANCE WITH 709, 709.3 REQUIRES A 1
 HOUR SEPARATION CONTINUOUS FROM OUTSIDE OF WALL TO
 OUTSIDE OF WALL.
  
 8) SHEET A106 ROOF PLAN: EIGHT ROOF DRAINS ARE MISSING
 A EMERGENCY ROOF DRAIN. THE OVERFLOW SCUPPERS THAT ARE
 SHOWN (6) ARE LOCATED SOMEWHERE BETWEEN 2?- 4? ABOVE
 THE EDGE OF THE INSULATED ROOF. 1503.4.3 OVERFLOW
 SCUPPERS ARE DESIGNED TO BE USED WITH SCUPPERS WHERE
 THE ROOF SLOPES TO THE SCUPPERS, AND IF THE SCUPPERS
 ARE BLOCKED THEN THE OVERFLOW SCUPPERS WILL ONLY POND
 2-4 INCHES. WITH THE ROOF HAVING ??/ 12? OR 1? PER
 4?-0? AND THE ROOF DRAIN TO THE OVER FLOW SCUPPER IS 32
 FEET AWAY THE PONDING WOULD BE 8-10 INCHES DEEP.
  
 9) SHEET S-6.6 WIND LOAD SCHEDULE INDICATES PRESSURES
 BUT NOT THE WIND DESIGN CRITERIA: 1609.6.2 WIND DESIGN
 PROCEDURES
 9.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
 9.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
 9.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4. NOTE THIS FACILITY HAS A
 BUILDING CATEGORY III, HEALTH CARE FACILITIES WITH A
 CAPACITY OF 50OR MORE RESIDENT PATIENTS BUT NOT HAVING
 SURGERY OR EMERGENCY TREATMENT FACILITIES.
 9.4 A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4) EXPOSURE C
 9.5 POSITIVE & NEGATIVE PRESSURES FOR BOTH DOOR &
 WINDOW OPENINGS FOR SIZE OF OPENINGS, ROOF PRESSURES
 FOR FLAT ROOF AS WELL AS SLOPED ROOF 7 TO 27 DEGREES .
 9.6 MEAN ROOF HEIGHT- THE AVERAGE OF THE ROOF EAVE
 HEIGHT AND THE HEIGHT TO THE HIGHEST POINT ON THE ROOF
 SURFACE, EXCEPT THAT EAVE HEIGHT SHALL BE USED FOR ROOF
 ANGLE OF LESS THAN OR EQUAL TO 10 DEGREES (0.18 RAD).
  
 10) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 11) FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, SOLID & GLAZED, ROLL UP OR
 COILING OVERHEAD DOORS AND OR INCLUDING ROOF HATCHES.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E SKYLIGHTS
 (F) PRE-ENGINEERED A/C STANDS
  
 12) FBC-B 1609.1.2 PROTECTION OF OPENINGS. LARGE IMPACT
 RESISTANT GLAZING TO A HEIGHT OF 30'-0" OR :
 420.4.2.5.2 PERMANENTLY ATTACHED PROTECTIVE SYSTEMS
 SUCH AS SHUTTERS AND BAFFLING SHALL BE DESIGNED TO MEET
 THE WIND LOAD REQUIREMENTS OF THIS CODE AND THE DEBRIS
 IMPACT REQUIREMENTS AS SPECIFIED BY SECTIONS 1626.2
 THROUGH 1626.4.
  
 420.4.2.5.3 REMOVABLE PROTECTIVE SYSTEMS DESIGNED TO
 INTRICATELY FIT WITH THE WALL/WINDOW SYSTEM OF THE
 FACILITY AND STORED ON SITE AT THE FACILITY AND THAT
 MEET THE WIND LOAD REQUIREMENTS OF THIS CODE AND THE
 DEBRIS IMPACT REQUIREMENTS SPECIFIED BY SECTIONS 1626.2
 THROUGH 1626.4 MAY BE USED TO PROTECT THE EXTERIOR
 UNITS.
  
 PLEASE NOTE: 104.6*/ 1609.1.4/ 1714.5 STANDARDS FOR
 WIND-BORNE DEBRIS IMPACT PROTECTION QUESTION# 13
 RECOGNIZING SUCH CONCERNS AS ABSENTEE OWNERS, OR CASES
 WHERE LONGER TIME & EFFORT IS NECESSARY TO SECURE
 SHUTTERS ON LARGE OR MULTI-STORY BUILDINGS, WHAT
 MEASURES ARE BEING RECOMMENDED OR IMPLEMENTED TO ENSURE
 THAT COMPLETE INSTALLATION OR SECURING IS DONE
 SUFFICIENTLY IN ADVANCE OF THE HURRICANE?
  
 IN MATTERS CONCERNING PUBLIC SAFETY, HEALTH, AND THE
 GENERAL WELFARE NOT SPECIFICALLY ADDRESSED IN THE CODE,
 SECTION 104.6 OF THE FLORIDA BUILDING CODE, BUILDING,
 CHAPTER 1,
 ADMINISTRATIVE CODE2004 EDITION AS AMENDED BY THE CITY
 OF WEST PALM BEACH, PROVIDES THE ABILITY FOR THE
 BUILDING OFFICIAL TO IMPLEMENT REQUIREMENTS FOR
 ENSURING STABILITY, STRENGTH, AND THE PROPER OPERATION
 OF EXISTING BUILDINGS.
  
 IN ORDER TO ASSURE THE SECURING OF SHUTTERS ON LARGE OR
 MULTI-STORY BUILDINGS, OR MULTIPLE
 ON THE SAME PROPERTY, PRE-STORM PREPARATION PLANS MUST
 BE SUBMITTED BY THE PROPERTY OWNERS OR MANAGING AGENTS
 FOR REVIEW BY THE CONSTRUCTION SERVICES DEPARTMENT. ANY
 SUCH PLAN SHALL INCLUDE, AT A MINIMUM, ON SITE LOCATION
 OF THE SHUTTERS, PARTY RESPONSIBLE FOR SECURING THE
 SHUTTERS ( SAID PARTY MUST BE LOCATED WITHIN PALM BEACH
 COUNTY), TOTAL NUMBER OF OPENINGS TO BE PROTECTED AND
 THE TOTAL TIME REQUIRED TO SECURE ALL OPENINGS.
 PROTECTION OF OPENINGS SHALL BE ACCOMPLISHED WITHIN
 TWELVE (12) HOURS OR LESS OF THE
 OFFICIAL NOTIFICATION BY THE NATIONAL WEATHER SERVICES
 OF A HURRICANE WATCH.
  
 PROVISIONS IN THE BUILDING CODES (AND THIS STANDARD)
 ARE NOT INTENDED TO PROHIBIT THE USE OF ALTERNATE
 MATERIALS AND METHODS, AND THE BUILDING OFFICIAL TO
 REVIEW AND APPROVE ANY ALTERNATE DEEMED EQUIVALENT IN
 QUALITY, STRENGTH, EFFECTIVENESS, FIRE RESISTANCE,
 DURABILITY AND SAFETY PRESCRIBED BY THIS CODE. BASED
 UPON THIS CODE PROVISION, ACCEPTANCE OF ALTERNATE
 MATERIALS AND METHODS MAY BE APPROVED ON A CASE-BY-CASE
 BASIS AND SHALL REQUIRE SUFFICIENT EVIDENCE OR PROOF TO
 SUBSTANTIATE ANY CLAIM MADE REGARDING THE ALTERNATE.
  
 IN LEAU OF LARGE MISSILE IMPACT RATED WINDOWS, STORM
 SHUTTERS MAY BE USED ON THE FIRST FLOOR IF: 104.6*/
 1609.1.4/ 1714.5 STANDARDS FOR WIND-BORNE DEBRIS IMPACT
 PROTECTION.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2012-08-17 Cont ID  
Sent By rlecky Date 2012-08-20 Time 15:20 Rev Time 0.00
Received By rlecky Date 2012-08-20 Time 09:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-07-19 Cont ID  
Sent By rlecky Date 2012-07-19 Time 11:05 Rev Time 0.00
Received By rlecky Date 2012-07-13 Time 16:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-03-30 Cont ID  
Sent By rlecky Date 2012-03-30 Time 15:52 Rev Time 0.00
Received By rlecky Date 2012-03-21 Time 12:56 Sent To  
Notes
2012-03-30 15:53:4212030044
 4847 FRED GLADSTONE DR.
 TYPE IIIA 3 STORY BUILDING
 INSTITUTIONAL GROUP I-2
  
 E000
 UPDATE THE PLAN WITH A LEGEND AND GENERAL NOTES.
 INCLUDE A CONDUIT SCHEDULE FOR BRANCH CIRCUITS AND
 FEEDERS
 E001
 PLEASE CLARIFY THE FEEDER SIZE PROPOSED FOR ATS ?LS.
 BOTH 250 KCMIL AND 500KCMIL HAVE BEEN PROPOSED.
 CLARIFY HOW THE GENERATOR QUICK CONNECT WILL FUNCTION
 SAFELY.
 E102
 CLARIFY THE USE OF ALUMINUM EQUIPMENT GROUNDING
 CONDUCTORS. THE GENERAL RULE SUGGESTS THAT GROUNDING
 CONDUCTORS WHICH FACILITATE THE BONDING OF PANEL BOARDS
 SHOULD BE COPPER. NEC 517.11
 E002
 PROVIDE SERVICE RISER SPECIFICATION FOR GUARD SHACK
 TRANSFORMER AND PANEL EQLGS. PROVIDE GROUND ROD AND
 NEUTRAL TO BOND AT GUARD SHACK.
 CLARIFY/COORDINATE AND UPDATE THE RISER PLAN AND PANEL
 SCHEDULES FOR THE FEEDER AND LOADS FOR THE KITCHEN
 PANEL EQLB1.
 NEC 215.5
 E003
 VERIFY THE 112 ? KVA TRANSFORMERS OR LARGER ARE LOCATED
 WITHIN FIRE-RESISTANT ROOMS WITH A ONE HOUR FIRE RATING
 OR COMPLY WITH THE NEC EXCEPTIONS. NEC 450.21 (B)
 E203
 A GFCI PROTECTED RECEPTACLE IS REQUIRED IN THE ELEVATOR
 EQUIPMENT ROOMS. NEC 620.23
 E501A
 FIRE PUMP ROOM REQUIRES A 2 HOUR FIRE RATING. FBC
 420.3.19
 VERIFY ALL CIRCUIT CONDUCTORS AND CONTROL WIRING FOR
 THE FIRE PUMP AND GENERATOR ARE INDEPENDENT AND HAVE A
 MINIMUM OF 2 HOUR AND 1 HOUR FIRE PROTECTION
 RESPECTIVELY. NEC 695.6, 605.14
 E600
 PROVIDE A DETAIL WHICH ILLUSTRATES THE REQUIRED WORKING
 CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN
 PROVIDED AS REQUIRED FOR THE ELECTRICAL EQUIPMENT AND
 PANEL BOARDS. NEC 110.26, 240.24, 408.17
 PROVIDE A SAFETY LABELING SCHEDULE FOR THE ELECTRICAL
 EQUIPMENT WHICH INCLUDES THE SPECIFIC WORDING REGARDING
 THE SIZE AND TYPE OF HAZARDS. NEC 110.22, 110.16
 E602
 A GFCI PROTECTED RECEPTACLE IS REQUIRED IN THE ELEVATOR
 EQUIPMENT ROOMS. NEC 620.23
 E301A
 PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.5
 CLARIFY OR SUMMARIZE ON THE PLAN HOW THE LIGHTING WILL
 BE CONTROLLED USING MOTION SENSORS OR SIMILAR
 TECHNIQUES. SPACE CONTROL FBC 13-415 ABC.1.2.
 ADDITIONAL CONTROLS 13-415.ABC.1.3
 P101
 BUILDING DRAINS APPEAR TO CROSS THROUGH AND OVER THE
 ELECTRICAL EQUIPMENT WITHIN THE SPACE DEDICATED TO THE
 EQUIPMENT. NEC 110.26 (F)
  
 NOTE:
 SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE
 ALARM SYSTEM, LIGHTNING PROTECTION, NURSE CALL, VOICE
 AND DATA.
 A SEPARATE PERMIT AND PLANS WITH WIND LOAD ENGINEERING
 FOR POLES, BASES AND FIXTURES IS REQUIRED.
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2012-08-10 Cont ID  
Sent By mgonzale Date 2012-08-10 Time   Rev Time 1.00
Received By mgonzale Date 2012-08-10 Time   Sent To I
Notes
2012-08-10 05:52:55NO CONFLICT WITH UTILITIES
  
 PERMITTED THRU ENG E10070002
 PBCHD PERMIT OBTAIN TO EXTEND WATERLINES ON-SITE.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2012-06-15 Cont ID  
Sent By mgonzale Date 2012-06-15 Time   Rev Time 1.00
Received By mgonzale Date 2012-06-15 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-08-06 Cont ID  
Sent By ddaniels Date 2012-08-06 Time 09:27 Rev Time 0.00
Received By ddaniels Date 2012-08-06 Time 09:26 Sent To  
Notes
2012-08-06 09:45:098/6/12 PLANS REVIEWED BY FIRE ***APPROVED*** PENDING
  
 1. REMOVE FLORIDA PREVENTION CODE( 2007/2009 EDITION)
 ON PLANS SHEET G011.
  
 2. REMOVE NFPA 101 LIFE SAFETY CODE ( 200 EDITION )
 REFERENCE FOR CMS ON PLANS SHEET G011.
  
 3. PER OUR CONVERSATION ALL LIFE SAFETY CODES SHALL
 APPLY WITH 2012 EDTION OF THE NFPA 101 / FLORIDA FIRE
 PREVENTION CODE.
  
 DERRICK L. DANIELS, BATTALION CHIEF / FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL
 (561) 805-6733
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-03-27 Cont ID  
Sent By ddaniels Date 2012-03-27 Time 11:20 Rev Time 0.00
Received By ddaniels Date 2012-03-27 Time 11:19 Sent To  
Notes
2012-03-27 11:24:49 
 FIRE PLAN REVIEW
 PERMIT # 12030044
 ADDRESS 4855 FRED GLADSTONE DRIVE
  
  
  
 03/27/2012 PLANS REVIEWED BY FIRE **DENIED**
  
  
  
  
 1.) DESIGN SHALL CONFORM TO THE 2009 EDITION OF THE
 FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA
 EDITION OF NFPA 1 AND NFPA 101.
 2.) ALL DEMOLITION WORK SHALL CONFORM TO THE
 REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY.
  
 DERRICK L. DANIELS, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6733
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-09-27 Cont ID  
Sent By rregueir Date 2012-08-28 Time 10:38 Rev Time 0.00
Received By rregueir Date 2012-08-14 Time 08:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2012-08-13 Time   Rev Time 0.00
Received By rregueir Date 2012-07-12 Time 13:34 Sent To  
Notes
2012-07-12 13:34:29DIGITAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-06-25 Cont ID  
Sent By rregueir Date 2012-06-25 Time 08:20 Rev Time 0.00
Received By rregueir Date 2012-03-19 Time 08:20 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2012-08-24 Cont ID  
Sent By jwitmer Date 2012-08-24 Time 14:38 Rev Time 0.00
Received By jwitmer Date 2012-08-24 Time 14:38 Sent To  
Notes
2012-08-24 14:40:59IMPACT FEES:
 RECEIPT # 2012-0516-99
 TRACK # MU-2012-008270-0000
 FEES: $142,680.74

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-06-25 Cont ID  
Sent By rregueir Date 2012-06-25 Time 08:20 Rev Time 0.00
Received By rregueir Date 2012-03-19 Time 08:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-07-24 Cont ID  
Sent By lwagner Date 2012-08-02 Time 12:53 Rev Time 0.00
Received By rregueir Date 2012-08-02 Time 15:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-06-25 Cont ID  
Sent By rregueir Date 2012-06-25 Time 08:21 Rev Time 0.00
Received By rregueir Date 2012-06-25 Time 08:21 Sent To  
Notes
2012-06-25 08:21:42REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2010
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. GATE HOUSE AND GENERATOR ARE TO BE COVERED UNDER
 SEPARATE PERMITS.
  
 2. PAGE M201 DRYER EXHAUST DUCTS PENETRATING 1-HR RATED
 WALL AT MULTIPLE LOCATIONS. SHOW HOW THESE PENETRATIONS
 ARE TO BE PROTECTED PER FBC-M 607.1.1.
  
 3. PAGE M202 DRYER EXHAUST DUCTS PENETRATING 1-HR RATED
 WALL AT MULTIPLE LOCATIONS. SHOW HOW THESE PENETRATIONS
 ARE TO BE PROTECTED PER FBC-M 607.1.1.
  
 4. PRODUCT APPROVAL IS REQQUIRED FOR ALL PRE-ENGINEERED
 AC STANDS PER FBC-M 301.12 AND FAC RULE 9N.1. PRODUCT
 APPROVALS SHALL BE APPROVED IN WRITING BY THE DESIGN
 PROFESSIONAL (SHOP DRAWING REVIEW STAMP WILL SUFFICE).
  
 5. PROVIDE DRYER MANUFACTURER'S INSTALLATION
 INSTRUCTIONS SHOWING THE MAX ALLOWABLE LENGTH OF DRYER
 EXHAUST DUCT PER FBC-M 504.1 OR FBC-M 504.7 AS
 APPLICABLE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2012-07-24 Time   Rev Time 0.00
Received By lwagner Date 2012-07-24 Time 12:26 Sent To  
Notes
***NONE***

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status F Date 2012-04-10 Cont ID  
Sent By lwagner Date 2012-04-10 Time 14:16 Rev Time 0.00
Received By lwagner Date 2012-04-10 Time 10:01 Sent To  
Notes
2012-04-10 10:02:251. SHEETS 202 & 203 OXYGEN LINE APPEARS TO BE
 INTERCONNECTED WITH THE COLD WATER NEAR COLUMN LINE
 J-5.

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-07-24 Cont ID  
Sent By lwagner Date 2012-07-24 Time 12:44 Rev Time 0.00
Received By lwagner Date 2012-07-24 Time 10:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-04-10 Cont ID  
Sent By lwagner Date 2012-04-10 Time 10:01 Rev Time 0.00
Received By lwagner Date 2012-03-27 Time 09:45 Sent To  
Notes
2012-04-09 11:12:32FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEETS P101, P103, P104, P208 PER TABLE 1106.3
 HORIZONTAL STORM PIPING - 5" RAINFALL RATE THE
 HORIZONTAL PIPING ON THE FIRST AND OFFSETS TO ROOF
 WOULD BE REQUIRED TO HAVE 1/4" PER FOOT FALL.
  
 2. SHEETS 202 & 203 OXYGEN LINE APPEARS TO BE
 INTERCONNECTED WITH THE COLD WATER NEAR COLUMN LINE
 J-5.
  
 3. SHEET P301- THE S-4 SINKS ARE NOT SHOWN AS BEING
 VENTED. TRAPS SHOULD BE SHOWN FOR FS-1 FIXTURES. A VTR
 IS MISSING FOR SOILED UTILLITY
  
 4. SHEET P501 THE BOTTOM FED WATER HEATERS WILL REQUIRE
 ANSI Z21.22 VACUUM RELIEF. SECTION 504.2
  
 5. FUEL GAS IS NOT PART OF THIS REVIEW. SEPARATE PLAN,
 REVIEW, APPLICATION, AND PERMIT REQUIRED.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 3 Status P Date 2012-08-21 Cont ID  
Sent By eschneid Date 2012-08-21 Time 10:25 Rev Time 4.00
Received By eschneid Date 2012-08-21 Time 10:25 Sent To  
Notes
2012-08-21 10:26:11PROVISO - THE SECURITY MANAGEMENT PLAN SHALL BE
 MAINTAINED THROUGHOUT THE CONSTRUCTION PHASE OF THE
 PROJECT. NON-COMPLIANCE WITH THE APPROVED PLAN SHALL
 RESULT IN A STOP-WORK ORDER FOR THE ENTIRE PLANNED
 DEVELOPMENT.
  
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR LANDSCAPE,
 PARKING STRIPING, FENCING, SITE/LANDSCAPE LIGHTING AND
 SIGNAGE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2012-07-24 Cont ID  
Sent By eschneid Date 2012-07-24 Time 15:31 Rev Time 4.00
Received By eschneid Date 2012-07-24 Time 15:30 Sent To  
Notes
2012-07-23 17:07:42FAILED
  
 PLEASE PROVIDE RESPONSES IN WRITING:
  
 A) REPEAT COMMENT: THE FOLLOWING CONDITIONS OF THE SITE
 PLAN APPROVAL FOR THIS BUILDING HAVE NOT BEEN
 SATISFIED:
  
 1) PRIOR TO THE SUBMITTAL FOR A BUILDING PERMIT, THE
 APPLICANT SHALL PREPARE A CONSTRUCTION SITE SECURITY
 AND MANAGEMENT PLAN FOR APPROVAL BY THE CITY'S POLICE
 DEPARTMENT CRIME PREVENTION THROUGH ENVIRONMENTAL
 DESIGN ("CPTED") OFFICIAL.
  
 A) THE APPLICANT, AFTER SITE CLEARING AND PLACEMENT OF
 CONSTRUCTION TRAILERS, SHALL INSTITUTE SECURITY
 MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES FOR
 THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT TO BE
 LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL,
 VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS,
 REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE
 SUB-CONTRACTORS TO SECURE MACHINERY AND TOOLS AT END OF
 WORK DAY AND/OR ANY OTHER MEASURE DEEMED APPROPRIATE TO
 PROVIDE A SAFE AND SECURE WORKING ENVIRONMENT.
  
 B) THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED
 THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT.
 NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A
 STOP-WORK ORDER FOR THE ENTIRE PLANNED DEVELOPMENT.
  
 B) REPEAT COMMENT: PRIOR TO ZONING APPROVAL OF THIS
 PERMIT, A SEPARATE LANDSCAPE PERMIT AND SITE PERMIT, TO
 INCLUDE THE PARKING STRIPING, SHALL BE SUBMITTED TO THE
 BUILDING DIVISION.
  
 C) REPEAT COMMENT: THE CHANGES TO THE KARLAN BUILDING
 FOR THE SERVICE CANOPIES (SHEET SC101) AND OTHER MINOR
 SITE CHANGES REQUIRE THE APPROVAL OF A MINOR SITE PLAN
 AMENDMENT FOR THE CHANGES TO THE LAYOUT OF THE SITE. A
 REVISED LANDSCAPE PLAN, SHOWING THE RELOCATION OF THE
 TREES WITHIN THE LIMITS OF WORK IS ALSO REQUIRED AS
 PART OF THE MINOR AMENDMENT. UPDATE - A MINOR AMENDMET
 HAS BEEN SUBMITTED BUT IT IS NOT SUFFICIENT.
  
 D) SHEET L102 DOES NOT SHOW THE LATEST SITE DATA TABLES
 (SPECIFICALLY THE BUILDING DATA TABLE). IT APPEARS THAT
 IT IS BASED ON AN OLDER PLAN.
  
 E) THE PARKING DETAILS ON SHEET L 104 DO NOT MATCH THE
 PARKING SPACES SHOWN ON THE CIVIL DRAWINGS (BOTH
 DETAILS AND PLANS).
  
 F) REPEAT COMMENT SHOW THE ROOFTOP MECHANICAL EQUIPMENT
 ON THE ELEVATIONS TO SHOW HOW IT WILL BE SCREENED. THE
 A/C UNITS ON TOP OF THE CURBS APPEAR TO BE 5 FEET HIGH,
 WITH A LOWER PARAPET. THIS DOES NOT APPLY TO THE
 COOLING TOWERS, WHICH ARE SHOWN AS SCREENED.
  
 G) REPEAT COMMENT - THE APPROVED ELEVATIONS OF THE
 GENERATOR BUILDING DID NOT INCLUDE GRILLS FOR THE VENTS
 FACING MILITARY TRAIL. THE WALL AND LANDSCAPE DO NOT
 PROVIDE ADEQUATE BUFFER FOR THE PROPOSED ELEVATION.
  
 H) THE NECESSARY DOCUMENTS SHALL BE SUPPLIED TO THE
 PLANNING DIVISION TO SECURE AN APPROVED TREE ALTERATION
 PERMIT.
  
 I) SEPARATE PERMITS ARE REQUIRED FOR LANDSCAPE, PARKING
 STRIPING, FENCING, SITE/LANDSCAPE LIGHTING AND SIGNAGE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2012-03-27 Cont ID  
Sent By eschneid Date 2012-03-27 Time 17:56 Rev Time 4.25
Received By eschneid Date 2012-03-27 Time 17:56 Sent To  
Notes
2012-03-27 18:33:11FAILED
  
 PLEASE PROVIDE RESPONSES IN WRITING:
  
 A) THE FOLLOWING CONDITIONS OF THE SITE PLAN APPROVAL
 FOR THIS BUILDING HAVE NOT BEEN SATISFIED:
  
 1) PRIOR TO THE SUBMITTAL FOR A BUILDING PERMIT, THE
 APPLICANT SHALL:
  
 A. SECURE AN APPROVED TREE ALTERATION PERMIT FROM THE
 PLANNING DIVISION.
  
 B. PREPARE A CONSTRUCTION SITE SECURITY AND MANAGEMENT
 PLAN FOR APPROVAL BY THE CITY'S POLICE DEPARTMENT CRIME
 PREVENTION THROUGH ENVIRONMENTAL DESIGN ("CPTED")
 OFFICIAL.
  
 I) THE APPLICANT, AFTER SITE CLEARING AND PLACEMENT OF
 CONSTRUCTION TRAILERS, SHALL INSTITUTE SECURITY
 MEASURES TO REDUCE OR ELIMINATE OPPORTUNITIES FOR
 THEFT. THE MANAGEMENT PLAN SHALL INCLUDE, BUT NOT TO BE
 LIMITED TO, TEMPORARY LIGHTING, SECURITY PERSONNEL,
 VEHICLE BARRIERS, CONSTRUCTION/VISITOR PASS,
 REDUCE/MINIMIZE ENTRY/EXIT POINTS, ENCOURAGE
 SUB-CONTRACTORS TO SECURE MACHINERY AND TOOLS AT END OF
 WORK DAY AND/OR ANY OTHER MEASURE DEEMED APPROPRIATE TO
 PROVIDE A SAFE AND SECURE WORKING ENVIRONMENT.
  
 II) THE SECURITY MANAGEMENT PLAN SHALL BE MAINTAINED
 THROUGHOUT THE CONSTRUCTION PHASE OF THE PROJECT.
 NON-COMPLIANCE WITH THE APPROVED PLAN SHALL RESULT IN A
 STOP-WORK ORDER FOR THE ENTIRE PLANNED DEVELOPMENT.
  
 2) THE APPLICANT SHALL SUBMIT THE FOLLOWING ITEMS AT
 THE TIME OF BUILDING PERMIT APPLICATION:
  
 A. A COPY OF THE PERMIT MODIFICATION FROM THE SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT AND NORTHERN PALM
 BEACH COUNTY IMPROVEMENT DISTRICT AND SIGNED AND SEALED
 DRAINAGE CALCULATIONS TO THE ENGINEERING SERVICES
 DEPARTMENT.
  
 B) PRIOR TO ZONING APPROVAL OF THIS PERMIT, A SEPARATE
 LANDSCAPE PERMIT AND SITE PERMIT, TO INCLUDE THE
 PARKING STRIPING, SHALL BE SUBMITTED TO THE BUILDING
 DIVISION.
  
 C) THE CHANGES TO THE KAPLAN BUILDING FOR THE SERVICE
 CANOPIES (SHEET SC101) REQUIRE THE APPROVAL OF A MINOR
 SITE PLAN AMENDMENT FOR THE CHANGES TO THE LAYOUT OF
 THE SITE. A REVISED LANDSCAPE PLAN, SHOWING THE
 RELOCATION OF THE TREES WITHIN THE LIMITS OF WORK IS
 ALSO REQUIRED AS PART OF THE MINOR AMENDMENT.
  
 D) THE SURVEY PROVIDED DOES NOT COVER THE ENTIRE WORK
 AREA FOR THE KAPLAN BUILDING CANOPIES.
  
 E) THE PLANS HAVE BEEN CHANGED FROM THE APPROVED PLANS
 AS FOLLOWS AND REQUIRE THE APPROVAL OF A MINOR SITE
 PLAN AMENDMENT:
  
 A. THE ENTRY DRIVE HAS BEEN WIDENED BY 5 FEET,
 RESULTING IN A REDUCTION IN THE TERMINAL ISLAND SIZE.
  
 B. THE ENTRY MEDIAN INCREASED FROM 189 TO 195 FEET.
 PLEASE VERIFY THAT THE TURNING RADII STILL WORK INTO
 THE SITE.
  
 F) THE PLANS STATE THAT THE CIVIL PLANS ARE BEING USED
 FOR CONSTRUCTION; THEREFORE THE BICYCLE RACK DIMENSIONS
 SHALL BE SHOWN ON SHEET C-7 AND A BICYCLE RACK DETAIL
 SHALL BE PROVIDED (AS SHOWN ON SHEET L104).
  
 G) THE NEW PARKING AREAS AT THE SOUTH END OF THE SITE
 STATE THAT WHEEL STOPS WILL BE USED WITH THE 2 FOOT
 OVERHANG. THIS IS NOT PERMITTED, AS THEY WILL NOT STAY
 IN PLACE. A D-CURB IS REQUIRED. THE PARKING DETAIL
 SHOWS THIS CONDITION AS WELL AND SHALL BE AMENDED.
 NOTE: THE ADA SPACES OVERHANG PAVING AND THUS MAY
 REMAIN AS SHOWN ON THE DETAIL.
  
 H) SHOW THE MECHANICAL EQUIPMENT ON THE ELEVATIONS TO
 SHOW HOW IT WILL BE SCREENED. THE A/C UNITS ON TOP OF
 THE CURBS APPEAR TO BE 5 FEET HIGH, WITH A LOWER
 PARAPET. THIS DOES NOT APPLY TO THE COOLING TOWERS,
 WHICH ARE SHOWN AS SCREENED.
  
 I) THE APPROVED ELEVATIONS OF THE GENERATOR BUILDING
 DID NOT INCLUDE GRILLS FOR THE VENTS FACING MILITARY
 TRAIL. THE WALL AND LANDSCAPE DO NOT PROVIDE ADEQUATE
 BUFFER FOR THE PROPOSED ELEVATION.
  
 J) SEPARATE PERMITS ARE REQUIRED FOR FENCING,
 SITE/LANDSCAPE LIGHTING AND SIGNAGE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved