Plan Review Details - Permit 12020630
Plan Review Stops For Permit 12020630
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2012-03-14 Cont ID  
Sent By rlecky Date 2012-03-14 Time 14:36 Rev Time 0.00
Received By rlecky Date 2012-03-14 Time 14:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2012-03-09 Cont ID  
Sent By rlecky Date 2012-03-09 Time 11:34 Rev Time 0.00
Received By rlecky Date 2012-03-09 Time 11:34 Sent To  
Notes
2012-03-09 11:34:44INCOMPLETE RESPONSE TO FIRE REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-02-28 Cont ID  
Sent By rlecky Date 2012-02-28 Time 17:27 Rev Time 0.00
Received By rlecky Date 2012-02-28 Time 17:23 Sent To  
Notes
2012-02-28 17:27:52SEE FIRE COMMENTS, QUALIFIED DESIGNER DID NOT SIGN THE
 PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2012-03-14 Time   Rev Time 0.00
Received By   Date 2012-03-14 Time   Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2012-03-08 Cont ID  
Sent By ddaniels Date 2012-03-08 Time 11:34 Rev Time 0.00
Received By ddaniels Date 2012-03-08 Time 11:24 Sent To E
Notes
2012-03-08 11:34:363/08/2012 PLANS REVIEWED BY FIRE **DENIED**
  
 COMMENTS NOT ADDRESSED
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-02-28 Cont ID  
Sent By wjolin Date 2012-02-28 Time 12:57 Rev Time 0.00
Received By wjolin Date 2012-02-28 Time 12:36 Sent To E
Notes
2012-02-28 12:57:351901 NORTH FLAGLER DRIVE
 PERMIT #12020630
 MASTER #11080026
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE QUALIFIED SYSTEM DESIGNER NEEDS TO PROVIDE A
 SIGNATURE ON THE PLANS.
  
 PROVIDE THE CANDELA INTENSITY FOR THE VISUAL
 NOTIFICATION APPLIANCES.
  
 PROVIDE ROOM NAMES/NUMBERS ON THE PLANS SO THE LOCATION
 OF THE FIRE ALARM DEVICES CAN BE IDENTIFIED.
  
 PROVIDE BATTERY CALCULATIONS AS DEVICES HAVE BEEN ADDED
 TO THE EXISTING NOTIFICATION APPLIANCE CIRCUIT.
  
 INDICATE WIRE GAGE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-03-14 Cont ID  
Sent By rlecky Date 2012-03-14 Time 14:36 Rev Time 0.00
Received By rlecky Date 2012-03-14 Time 14:36 Sent To  
Notes
2012-03-14 10:40:42TO ELECTRIC

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-03-09 Cont ID  
Sent By rlecky Date 2012-03-09 Time 11:33 Rev Time 0.00
Received By rlecky Date 2012-03-05 Time 13:39 Sent To  
Notes
2012-03-05 13:39:51SENT TO FIRE SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-02-28 Cont ID  
Sent By rlecky Date 2012-02-28 Time 17:27 Rev Time 0.00
Received By rlecky Date 2012-02-27 Time 16:03 Sent To  
Notes
2012-02-27 16:03:43SENT TO FIRE SHELF FOR REVIEW. JG.