Plan Review Details - Permit 12020531
Plan Review Stops For Permit 12020531
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-03-28 Cont ID  
Sent By rlecky Date 2012-03-28 Time 15:11 Rev Time 0.00
Received By rlecky Date 2012-03-28 Time 10:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-03-19 Cont ID  
Sent By rlecky Date 2012-03-19 Time 16:42 Rev Time 0.00
Received By rlecky Date 2012-03-19 Time 16:08 Sent To G
Notes
2012-03-19 16:42:40#4 FEEDER CONDUCTORS FROM GENERATOR APPEAR TO BE
 UNDERSIZED. NEC 445.13
 PROVIDE GENERATOR SPECIFICATIONS SHOWING THE REQUIRED
 CONSTRUCTION AND SAFETY CLEARANCES. NEC 110.26
  
  
  
 ROBERT LECKY
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2012-03-22 Cont ID  
Sent By lwagner Date 2012-03-21 Time 15:03 Rev Time 0.00
Received By lwagner Date 2012-03-21 Time 13:44 Sent To  
Notes
2012-03-21 15:03:02***PROVISO***
 IF ACTUAL LOCATION OF GENERATOR IS PER PLAN. SEE ZONING
 COMMENTS.
  
 GAS PLAN SHOWS 1/2 POUND GAS METER, BUT SHOWS 2 POUND
 SIZE TABLES 402.4(3) AND 402.4(21)
 PER CONTRACTOR: GAS SYSTEM IS 1/2 POUND - LESS THAN 10'
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-03-28 Cont ID  
Sent By rlecky Date 2012-03-28 Time 15:12 Rev Time 0.00
Received By rlecky Date 2012-03-28 Time 08:21 Sent To  
Notes
2012-03-28 08:21:28TO ELEC

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-03-21 Cont ID  
Sent By lwagner Date 2012-03-21 Time 15:12 Rev Time 0.00
Received By lwagner Date 2012-02-23 Time 10:17 Sent To  
Notes
2012-02-23 10:17:36TO ZONING BIN

Review Stop Z ZONING
Rev No 2 Status P Date 2012-03-27 Cont ID  
Sent By ajones Date 2012-03-27 Time 16:54 Rev Time 0.00
Received By ajones Date 2012-03-27 Time 16:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2012-03-15 Cont ID  
Sent By ajones Date 2012-03-15 Time 08:54 Rev Time 0.00
Received By ajones Date 2012-03-15 Time 08:54 Sent To E
Notes
2012-03-15 13:33:243/15/12- THE PROPOSED LOCATION OF THE GENERATOR DOES
 NOT MEET SETBACKS. CONTRACTOR WAS CALLED TO VERTIFY
 LOCATION.
  
 ANGELLA VANN, AICP
 PLANNING AND ZONING ADMINISTRATOR
 561-822-1441
 [email protected]