Plan Review Details - Permit 12020531
Plan Review Stops For Permit 12020531 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2012-03-28 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2012-03-28 |
Time |
15:11 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2012-03-28 |
Time |
10:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2012-03-19 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2012-03-19 |
Time |
16:42 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2012-03-19 |
Time |
16:08 |
Sent To |
G |
|
Notes |
2012-03-19 16:42:40 | #4 FEEDER CONDUCTORS FROM GENERATOR APPEAR TO BE | | UNDERSIZED. NEC 445.13 | | PROVIDE GENERATOR SPECIFICATIONS SHOWING THE REQUIRED | | CONSTRUCTION AND SAFETY CLEARANCES. NEC 110.26 | | | | | | | | ROBERT LECKY | | ELECTRIC PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
P |
Date |
2012-03-22 |
|
|
Cont ID |
|
Sent By |
lwagner |
Date |
2012-03-21 |
Time |
15:03 |
Rev Time |
0.00 |
Received By |
lwagner |
Date |
2012-03-21 |
Time |
13:44 |
Sent To |
|
|
Notes |
2012-03-21 15:03:02 | ***PROVISO*** | | IF ACTUAL LOCATION OF GENERATOR IS PER PLAN. SEE ZONING | | COMMENTS. | | | | GAS PLAN SHOWS 1/2 POUND GAS METER, BUT SHOWS 2 POUND | | SIZE TABLES 402.4(3) AND 402.4(21) | | PER CONTRACTOR: GAS SYSTEM IS 1/2 POUND - LESS THAN 10' | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2012-03-28 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2012-03-28 |
Time |
15:12 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2012-03-28 |
Time |
08:21 |
Sent To |
|
|
Notes |
2012-03-28 08:21:28 | TO ELEC |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2012-03-21 |
|
|
Cont ID |
|
Sent By |
lwagner |
Date |
2012-03-21 |
Time |
15:12 |
Rev Time |
0.00 |
Received By |
lwagner |
Date |
2012-02-23 |
Time |
10:17 |
Sent To |
|
|
Notes |
2012-02-23 10:17:36 | TO ZONING BIN |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2012-03-27 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2012-03-27 |
Time |
16:54 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2012-03-27 |
Time |
16:54 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2012-03-15 |
|
|
Cont ID |
|
Sent By |
ajones |
Date |
2012-03-15 |
Time |
08:54 |
Rev Time |
0.00 |
Received By |
ajones |
Date |
2012-03-15 |
Time |
08:54 |
Sent To |
E |
|
Notes |
2012-03-15 13:33:24 | 3/15/12- THE PROPOSED LOCATION OF THE GENERATOR DOES | | NOT MEET SETBACKS. CONTRACTOR WAS CALLED TO VERTIFY | | LOCATION. | | | | ANGELLA VANN, AICP | | PLANNING AND ZONING ADMINISTRATOR | | 561-822-1441 | | [email protected] |
|
|
|