Plan Review Details - Permit 12020063
Plan Review Stops For Permit 12020063
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-03-20 Cont ID  
Sent By jgomez Date 2012-03-20 Time 11:08 Rev Time 0.00
Received By jgomez Date 2012-03-20 Time 11:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-02-24 Cont ID  
Sent By jgomez Date 2012-02-23 Time 17:56 Rev Time 0.00
Received By jgomez Date 2012-02-22 Time 13:33 Sent To  
Notes
2012-02-24 15:16:56RESIDENTIAL (R3) ALTERATION/RENOVATION BUILDING REVIEW
 COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROPERTY IS LOCATED ON FLOOD ZONE A5 WITH FLOOD BASE
 ELEVATION OF 7'. FINISH FLOOR ELEVATION NEEDS TO BE AT
 LEAST 7'-6" AS REQUIRED BY CITY ORDINANCE SEC.
 94-546(B)(1). PLEASE PROVIDE DOCUMENTATION SHOWING THE
 FINISH FLOOR.
  
 2- PLEASE PROVIDE PRODUCT APPROVAL (2 COPIES) AS
 REQUIRED BY DCA RULE 9N-3 FOR:
 A) SLIDING DOORS. (1) NOA 10-0120.03 SUBMITTED DOESN'T
 MEET THE DESIGN PRESSURES CALCULATED BY THE ARCHITECT
 ON SHEET S1.
 (2) NOA SUBMITTED WAS SUPERSEDED BY MIAMI-DADE. PLEASE
 VISIT MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA.
  
 B) OUTSWING WOOD DOOR. NOA 10-1222.03 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. PLEASE PROVIDE CURRENT ONE.
  
 C) CASEMENT WINDOW. NOA 09-1027.05 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. PLEASE SUBMIT CURRENT ONE.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC.
  
 4- SHEET S1: CLARIFY WIND DESIGN CRITERIA. TWO STORY
 COMPONENTS AND CLADDING DESIGN PRESSURES +/- 64 PSF
 (WORST CASE) DESIGN PRESSURES DON'T MATCH THE DESIGN
 PRESSURES SHOWN ON TWO STORY DIAGRAM. PLEASE REVISE AS
 REQUIRED TO MATCH. REVISE POSITIVE AND NEGATIVE
 PRESSURES TO MATCH.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-03-05 Cont ID  
Sent By rlecky Date 2012-03-05 Time 16:22 Rev Time 0.00
Received By rlecky Date 2012-03-05 Time 16:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2012-02-03 Cont ID  
Sent By rlecky Date 2012-02-03 Time 12:38 Rev Time 0.00
Received By rlecky Date 2012-02-03 Time 12:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-03-23 Cont ID  
Sent By lmartine Date 2012-03-23 Time 11:46 Rev Time 0.00
Received By lmartine Date 2012-03-05 Time 13:11 Sent To  
Notes
2012-03-05 13:11:48SENT TO R5 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-02-23 Cont ID  
Sent By jgomez Date 2012-02-23 Time 17:56 Rev Time 0.00
Received By jgomez Date 2012-02-02 Time 17:33 Sent To  
Notes
2012-02-02 17:34:17SENT TO R3 SHELF FOR REVIEW. JG.

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-03-20 Cont ID  
Sent By jgomez Date 2012-03-20 Time 16:20 Rev Time 0.00
Received By jgomez Date 2012-03-20 Time 16:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-02-23 Cont ID  
Sent By jgomez Date 2012-02-23 Time 17:21 Rev Time 0.00
Received By jgomez Date 2012-02-23 Time 17:21 Sent To  
Notes
2012-02-23 17:55:47RESIDENTIAL (R3) ALTERATION PLUMBING REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PLUMBING FIXTURES ARE NOT PROPERLY VENTED. SANITARY
 RISER DIAGRAM 2/E1 ON SHEET E1 SHOWS NO VENT FOR THE
 WATER CLOSET, TUB AND SHOWER. IN HORIZONTAL WET-VENT
 SYSTEMS, NOT MORE THAN ONE WET-VENTED FIXTURE DRAIN
 SHALL DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE
 DRAIN CONNECTION. SEE SEC. P3108.2.
  
 2- CLEARLY SPECIFY VENT SIZES AS REQUIRED BY SEC.
 P3108.3.
  
 3- REVISE SANITARY RISER DIAGRAM 2/E1. EACH FIXTURE
 DRAIN SHALL CONNECT HORIZONTALLY TO THE HORIZONTAL
 BRANCH BEING WET VENTED OR SHALL HAVE A DRY VENT. SEC.
 P3108.1.
 ALSO, INFORMATION SHOWN ON FLOOR PLAN 1/E1 DOESN'T
 MATCH INFORMATION SHOWN ON SANITARY RISER DIAGRAM 2/E1.
  
 ***NOTE: PLUMBING RISER DIAGRAM MAY BE DRAWN BY THE
 LICENSED PLUMBING CONTRACTOR DOING THE JOB. IF DOING
 SO, THEN PLUMBING CONTRACTOR TO WRITE NAME, LICENSE
 NUMBER AND SIGN THE DRAWING.
  
 4- SHEET E1: DETAIL 4/E1: TRAP GUARD ON FLOOR DRAIN IS
 NOT ALLOWED. TRAPS FOR FLOOR DRAINS SHALL BE FITTED
 WITH A TRAP PRIMER OR SHALL BE OF THE DEEP SEAL DESIGN
 AS REQUIRED BY SEC. P3201.2.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop Z ZONING
Rev No 2 Status P Date 2012-03-23 Cont ID  
Sent By jroach Date 2012-03-23 Time 08:24 Rev Time 0.00
Received By jroach Date 2012-03-22 Time 09:26 Sent To  
Notes
2012-03-23 08:24:23ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 03.23.2012
 PERMIT NO.: 12020063
 ADDRESS: 134 CORTEZ ROAD
 CONTRACTOR/CONTACT: SEAN COUNIHAN
 TELEPHONE NO.: 561.585.0084
 SCOPE OF REVIEW: INTERIOR RENOVATIONS TO EXISTING
 RESIDENCE.
 ___________________________________________
  
 REVIEW STATUS: PASSED WITH PROVISOS
 ___________________________________________
  
 THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING
 PROVISOS:
  
 1. PRIOR TO FINAL INSPECTION, A LANDSCAPE PERMIT
 APPLICATION SHALL BE OBTAINED TO BRING THE PROPERTY
 INTO COMPLIANCE WITH ARTICLE XIV OF THE CITY'S ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDRS).
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM

Review Stop Z ZONING
Rev No 1 Status F Date 2012-02-08 Cont ID  
Sent By jroach Date 2012-02-08 Time 15:16 Rev Time 0.00
Received By jroach Date 2012-02-08 Time 09:05 Sent To  
Notes
2012-02-08 15:17:21ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 02.08.2012
 PERMIT NO.: 12020063
 ADDRESS: 134 CORTEZ ROAD
 CONTRACTOR/CONTACT: SEAN COUNIHAN
 TELEPHONE NO.: 561.5850084
 SCOPE OF REVIEW: INTERIOR RENOVATION TO EXISTING
 RESIDENCE.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. AS THE VALUE OF THE PROPOSED IMPROVEMENTS EXCEEDS 50
 PERCENT OF THE ASSESSED VALUE OF THE STRUCTURE, THE
 PROPERTY SHALL BE BROUGHT IN COMPLIANCE WITH ARTICLE
 XIV (LANDSCAPING) OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS).
  
  A LANDSCAPE PERMIT APPLICATION SHALL BE SUBMITTED WITH
 TWO (2) COPIES OF A LANDSCAPE PLAN, AND A CERTIFIED
 COST ESTIMATE. THE LANDSCAPE PLAN SHALL INDICATE ALL
 EXISTING AND PROPOSED TREES/SHRUBS/GROUNDCOVER/ETC AND
 A TABULATION TABLE INDICATING COMPLIANCE WITH ARTICLE
 XIV.
  
  IF THE EXISTING LANDSCAPING CURRENTLY CONFORMS TO THE
 MINIMUM STANDARDS OF ARTICLE XIV AND NO ADDITIONAL WORK
 IS NEEDED, SIMPLY PROVIDE A PLAN INDICATING ALL OF THE
 EXISTING LANDSCAPING, ALONG WITH A TABULATION TABLE,
 INDICATING COMPLIANCE WITH SUCH.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, SENIOR PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3366
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1435
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.CITYOFWPB.COM
  