Plan Review Details - Permit 12020002
Plan Review Stops For Permit 12020002 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2012-10-02 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2012-10-02 |
Time |
10:47 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2012-10-02 |
Time |
10:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2012-02-02 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2012-02-02 |
Time |
16:23 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2012-02-01 |
Time |
14:21 |
Sent To |
|
|
Notes |
2012-02-02 16:32:15 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. PROVIDE A PLAN SHOWING PROPOSED DOOR LOCATION, DOOR | | SWING, FIRE RESISTANCE REQUIRED, AND WHETHER OR NOT | | PANIC BARS ARE TO BE INCLUDED IN THE INSTALLATION. | | PROVIDE INFORMATION REGARDING THE METER ROOM TO SHOW | | WHETHER PANIC DEVICES ARE REQUIRED, SEE FBC1008.1.9. | | ALL INFORMATION REQUIRED TO SHOW CODE COMPLIANCE IS TO | | BE INCLUDED ON THE PLAN. THE CONTRACT DOES NOT SHOW | | THAT PANIC BARS ARE PROPOSED, PLEASE INCLUDE ENOUGH | | INFORMATION ON THE PLAN TO SHOW WHY THIS INSTALLATION | | IS EXEMPT. THE CONTRACT SHOWS A 90 MINUTE DOOR | | PROPOSED; PLEASE INCLUDE THIS INFORMATION ON THE PLAN. | | | | 2. IF THIS IS AN EXTERIOR DOOR, AN ENGINEER IS TO | | SPECIFY DESIGN PRESSURES, FBC1609. | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2012-09-20 |
|
|
Cont ID |
|
Sent By |
rferguso |
Date |
2012-09-20 |
Time |
16:00 |
Rev Time |
0.00 |
Received By |
rferguso |
Date |
2012-09-20 |
Time |
15:59 |
Sent To |
B |
|
Notes |
2012-09-20 16:37:31 | 3705 SOUTH FLAGLER DR. | | PERMIT #12020002 | | | | | | FIRE PLAN REVIEW COMMENTS | | | | * PLANS REVIEWED BY FIRE (APPROVED), (PROVISO) AS | | MENTIONED IN PREVIOUS NOTES, PLANS MUST INDICATE IF | | DOORS, CLOSERS, LOCKS/LATCHES ARE FIRE RATED. | | | | | | | | RONALD E. FERGUSON, ASSISTANT FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | PHONE #(561) 804-4756 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2012-02-03 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2012-02-03 |
Time |
10:54 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2012-02-03 |
Time |
10:51 |
Sent To |
|
|
Notes |
2012-02-03 10:54:37 | 3705 SOUTH FLAGLER DRIVE | | PERMIT #12020002 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | PROVIDE A FLOOR PLAN INDICATING THE LOCATION OF THE | | DOORS TO BE REPLACED. | | | | INDICATE IF THE DOORS WILL HAVE A FIRE RATING, DOOR | | CLOSER, LOCK/LATCH ETC. | | | | WESLEY JOLIN | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2012-09-21 |
|
|
Cont ID |
|
Sent By |
rferguso |
Date |
2012-09-21 |
Time |
16:21 |
Rev Time |
0.00 |
Received By |
rferguso |
Date |
2012-09-17 |
Time |
16:03 |
Sent To |
|
|
Notes |
2012-09-17 16:04:02 | SENT TO FIRE SHELF FOR REVIEW. JG. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2012-02-03 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2012-02-03 |
Time |
14:05 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2012-02-01 |
Time |
10:23 |
Sent To |
|
|
Notes |
2012-02-02 16:32:40 | 2/2 TO FIRE | 2012-02-01 10:23:26 | MISC 1 |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |