Plan Review Details - Permit 12010646
Plan Review Stops For Permit 12010646
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-03-22 Cont ID  
Sent By jwitmer Date 2012-03-13 Time 09:51 Rev Time 0.00
Received By jwitmer Date 2012-03-13 Time 15:17 Sent To  
Notes
2012-03-13 15:33:06BUILDING PLAN REVIEW
 PERMIT: 12010646
 ADD: 315 S FLAGLER
 CONT: THE WHITING TURNER CO
 TEL: (954)776-0800
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
  
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SOILS REPORT IS REQUIRED BEFORE THE FOUNDATION
 INSPECTION CAN TAKE PLACE. SHEET S-1 STRUCTURAL NOTE #
 2 AS WELL AS FBC-B 1802.4-6 INVESTIGATION, SOIL BORING
 & SAMPLING AND REPORTS ARE REQUIRED TO DETERMINE THE
 SOILS MINIMUM SAFE BEARING VALUE.
  
 2) ) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. SHEET S-3
 EITHER PRODUCT TESTING REPORT OR SHOP DRAWINGS FOR THE
 SUSPENDED PARTITION RAIL BEAM SYSTEM TO BE REVIEWED BY
 THE DESIGNER OF RECORD. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
  
 3) THE FOLLOWING LIST OF PRODUCT TYPES REQUIRE PRODUCT
 APPROVALS:
 PLEASE PROVIDE 3 COPIES OF EACH REQUIRED (1) FOR THE
 THRESHOLD INSPECTOR)
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.EXTERIOR SWING, INTERIOR SWING &
 ELECTRONIC BY-PASS
 (B) WINDOWS/ MULLIONS IF NOT INCLUDED WITH IN THE
 REPORT
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 4) SHEET A3.12 DETAIL# 3 SHOP DRAWINGS TO BE SUBMITTED
 FOR THE CANOPY STRUCTURE AND WILL INCLUDE ENGINEERED
 DRAWINGS THAT WILL MEET THE WIND LOAD PRESSURES FOR A
 COASTAL EXPOSURE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-02-09 Cont ID  
Sent By jwitmer Date 2012-02-09 Time 09:25 Rev Time 0.00
Received By jwitmer Date 2012-02-09 Time 09:25 Sent To  
Notes
2012-02-09 09:53:58BUILDING PLAN REVIEW
 PERMIT: 12010646
 ADD: 315 S FLAGLER
 CONT: THE WHITING TURNER CO
 TEL: (954)776-0800
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) ONLY THE COVER SHEET OF THE A SHEETS ARE SEALED.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 2) THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN (WRITTEN) PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 3) THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 4) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 5) THREE SETS OF ALL DOCUMENTS ARCHITECTURAL &
 STRUCTURAL IN NATURE, THE THRD SET BEING FOR THE
 THRESHOLD INSPECTOR AND RECORDS.
  
 6) NOTE: 109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 7) A HOLD WILL BE PUT ON THIS PROJECT UNTIL THESE ITEMS
 ARE COMPLETED AS REQUESTED BY THE CHIEF BUILDING
 INSPECTOR KEN CONRAD:
  
 PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 7A) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONCRETE RESTORATION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 7B FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 8) SHEET S-1 STRUCTURAL NOTE # 2 AS WELL AS FBC-B
 1802.4-6 INVESTIGATION, SOIL BORING & SAMPLING AND
 REPORTS ARE REQUIRED TO DETERMINE THE SOILS MINIMUM
 SAFE BEARING VALUE.
 SHEET S-2 DOES INDICATE SOIL STABILIZATION AS WELL.
  
 9) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 10) THE FOLLOWING LIST OF PRODUCT TYPES REQUIRE PRODUCT
 APPROVALS:
 PLEASE PROVIDE 3 COPIES OF EACH REQUIRED (1) FOR THE
 THRESHOLD INSPECTOR)
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.EXTERIOR SWING, INTERIOR SWING &
 ELECTRONIC BY-PASS
 (B) WINDOWS/ MULLIONS IF NOT INCLUDED WITH IN THE
 REPORT
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 11) SHEET S-3 EITHER PRODUCT TESTING REPORT OR SHOP
 DRAWINGS FOR THE SUSPENDED PARTITION RAIL BEAM SYSTEM
 TO BE REVIEWED BY THE DESIGNER OF RECORD.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 12A) PLEASE REVIEW SHEET S-5 DETAIL # 1 ELEVATOR PIT/
 FOUNDATION DETAIL, BUILDING IS MAKING THIS COMMENT ONLY
 BECAUSE THE SUMP PIT IS INDICATED ON THE BUILDING
 (STRUCTURAL SHEETS). FBC-PLUMBING SECTION 712.3.2
 REQUIRES THE SUMP PIT TO BE NOT LESS THAN 18 INCHES
 WIDE AND 24 INCHES DEEP.
  
 12B) SHEET A2.2 DETAIL 3. THE OTHER CONCERN IS IF THIS
 ELEVATOR IS TO BE A HYDROLIC UNIT, HYDROLIC FLUID LEAKS
 AND OR FAILURES AND THE OILS BEING DELIVERED DIRECTLY
 INTO THE SANITARY SEWER. THE PLUMBING REVIEWER WILL
 ELABORATE FURTHER ON THIS ISSUE.
  
 13) SHEET A0.1 THE GROUND FLOOR INDICATES CORRIDOR #
 001 TO BE A 1-HOUR FIRE RATED CORRIDOR, SHEET A0.2 THE
 MAIN ENTRY COORIDOR # 102 COMMUNICATES WITH THE FIRST
 FLOOR WITH THE NEW OPENING-OPEN TO RECEPTION BELOW
 WHICH WOULD REQUIRE THE FIRST FLOOR CORRIDOR TO ALSO BE
 1 HOUR FIRE RATING. THE SECOND ISSUE WITH THIS SAME
 CORRIDOR IS THAT CORRIDOR # 102 ADJOINS WITH CORRIDOR #
 119 & 121WHICH ARE THE EXIT ACCESS CORRIODORS FOR THE
 CHAPEL AN A-3 OCCUPANCY WHICH WILL REQUIRE A 1 HOUR
 FIRE RATING PER FBC-B TABLE 1017.1 & OPENING
 PROTECTIVES PER FBC-B TABLE 715.4.
  
 14) SHEET A0.1 STAIRWELL # 1 OPENS INTO THE BUILDING,
 NOT EXITING TO THE EXTERIOR OF THE BUILDING, THIS IS
 PART OF THE REQUIRED MEANS OF EGRESS THAT WOULD NEED TO
 COMPLY WITH :
 FBC-B 707.2 SHAFT ENCLOSURES REQUIRED.
 FBC-B 1020.1 ENCLOSURES REQUIRED.
 FBC-B 1024.1 EXIT DISCHARGE
 THERE APPEARS TOO BE TWO ISSUES:
 14A) THE NEWLY CREATED HOLE THROUGHTHE FLOOR CREATING A
 2 STORY ATRUIM
  
 14B) STAIRWAY # 1 DUMPING INTO THE BUILDING AND NOT
 MEETING THE REQUIREMENTS OF EXIT DISCHARGE LISTED
 ABOVE.
  
  
 15) SHEET A0.1 BOTH OF THE CONTINUEING CORRIDORS 113 &
 122 WOULD NEED TO BE 1 HOUR FIRE RATED TO THE VERTICAL
 EXIT STAIR ENCLOSURE. FBC-B TABLE 1017.1 & OPENING
 PROTECTIVES PER FBC-B TABLE 715.4.
  
 16) SHEET A1.11 GENERAL STORAGE ROOM # 016 THE NEW RAMP
 INDICATES THE USE OF A NEW GUARD RAIL BUT PLANS DO NOT
 INDICATE THE USE OF A HANRAIL ON THE OPPOSITE SIDE.
 FBC-B 1012.1.
  
 17) SHEET A1.11 THE GENERAL STORAGE ROOM # 016 THE
 EXTERIOR DOOR # 016A IS MISSING THE 18" MANEUVERING
 CLEARENCES PULL SIDE OF DOOR. FBC-B 11-4.13.6.
  
 18) A1.11 DOOR # 021 DOES NOT APPEAR TO HAVE THE
 REQUIRED 18 INCHES ON THE LATCH SIDE OF THE DOORWAY,
 THE CORRIDOR IS ONLY 5 FEET WIDE. 11-4.13.6.
 MANEUVERING CLEARENCES.
  
 19) SHEET A1.11 DOOR # 026 TO THE MECHANICAL ROOM DOES
 NOT APPEAR TO HAVE THE REQUIRED 18 INCHES ON THE LATCH
 SIDE OF THE DOORWAY. 11-4.13.6. MANEUVERING CLEARENCES.
  
 20) SHEET A1.11 ROOM 043 THE ENVIROMENTAL SERVICES
 DIRECTOR ROOM, THE CORRIDOR IN FRONT OF THIS ROOM IS A
 RATED CORRIDOR, THE CORRIDOR TURNS INTO AN EXTERIOR
 WALL ON THE ONE SIDE BUT THE SIDE CLOSEST TO ROOM # 043
 IS NO LONGER INDICATED AS A RATED CORRIDOR.
  
 21) SHEET A1.12 COORIDOR # 111 IS NOT GIVEN A WIDTH
 DIMENSION, DOOR # 111 MAY NOT HAVE THE 18" ONTHE PULL
 SIDE OF THE DOOR. 11-4.13.6.
  
 22) SHEET A3.12 DETAIL# 3 PLEASE PROVIDE MANUFACTURERS
 SPEC ON SUN SCREEN CANOPY, DOES IT COMPLY WITH WIND
 DESIGNS FBC-B 3105.4.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-03-07 Cont ID  
Sent By rlecky Date 2012-03-07 Time 10:31 Rev Time 0.00
Received By rlecky Date 2012-03-06 Time 16:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-02-13 Cont ID  
Sent By rlecky Date 2012-02-13 Time 11:23 Rev Time 0.00
Received By rlecky Date 2012-02-13 Time 11:17 Sent To  
Notes
2012-02-13 11:25:0012010646
 315 S. FLAGLER DRIVE
 RENOVATION TO LOURDES-NOREEN MCKEAN RESIDENCE
  
 VERIFY NOTE 4: 2/0 AL LIMITED TO 135 AMPERES? NEC T.
 310.16
 VERIFY THE 150 KVA TRANSFORMER IS LOCATED WITHIN A
 FIRE-RESISTANT ROOM WITH A ONE HOUR FIRE RATING OR
 COMPLIES WITH THE NEC EXCEPTIONS. NEC 450.21 (B)
 VERIFY THE ELECTRICAL SERVICE MAINS ARE SIX OR LESS AND
 GROUPED IN ONE LOCATION. NEC 230
 EACH STRUCTURE OR BUILDING SHALL BE SUPPLIED BY ONLY
 ONE FEEDER. FEEDER TO PANEL GH1 APPEARS TO ORIGINATE
 FROM ANOTHER SERVICE IN ANOTHER BUILDING. NEC 225.25
 A GFCI PROTECTED RECEPTACLE IS REQUIRED IN THE ELEVATOR
 EQUIPMENT ROOM. NEC 620.23
 KITCHEN PANELS REQUIRE CLEAR UNOBSTRUCTED DEDICATED
 WORKING SPACE. NEC 110.26
 INDICATE THE FEEDER CONDUCTOR SIZES FOR THE KITCHEN
 PANELS. NEC T. 310.16
 INDICATE THE OVERCURRENT PROTECTION REQUIRED FOR THE
 TRANSFORMER FEEDER AT PANELBOARD EQH1. NEC 215.5
 VERIFY NUMBER 2 AL RATED AT 90 AMPERES IS ADEQUATE TO
 CARRY THE NEUTRAL LOAD AT PANEL BOARD KN1. NEC 220.61
 FEEDER CONDUCTORS TO THE 150 KVA TRANSFORMER APPEAR TO
 BE UNDER SIZED. NEC 215.2
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-04-02 Cont ID  
Sent By ddaniels Date 2012-04-02 Time 11:56 Rev Time 0.00
Received By ddaniels Date 2012-04-02 Time 11:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-02-13 Cont ID  
Sent By wjolin Date 2012-02-13 Time 15:25 Rev Time 0.00
Received By wjolin Date 2012-02-13 Time 11:47 Sent To  
Notes
2012-02-13 15:21:29315 SOUTH FLAGLER DRIVE
 PERMIT #12010646
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 **SHEET A0.0: PLAN STATES CERTAIN STAIRS WILL BE OUT OF
 SERVICE AND BUILDING OCCUPANTS WILL NEED TO
 "RE-DIRECTED" TO IN-SERVICE STAIRS DURING DIFFERENT
 PHASES OF CONSTRUCTION. SUBMIT ADDITIONAL INFORMATION
 AS TO HOW THE EXITING PLAN WILL BE EXECUTED AND MANAGED
 WITH REGARDS TO BUILDING EMERGENCY PLANS, EXISTING EXIT
 SIGN LOCATIONS, TEMPORARY SIGNAGE, STAFF, OCCUPANTS,
 VISITORS ETC.
  
 SHEET A1.11: PROVIDE NON-COMBUSTIBLE 18" DEEP DRAFT
 STOPS AROUND FLOOR OPENING. PROVIDE CLOSELY SPACED
 SPRINKLERS AROUND FLOOR OPENING.
  
 SHEET FP0.1: THE CONSTRUCTION DOCUMENTS SIGNED/SEALED
 BY THE ENGINEER, ESTABLISH R. DAVENPORT AS THE ENGINEER
 OF RECORD FOR THE FIRE PROTECTION DESIGN; THEREFORE,
 THE FIRE SPRINKLER SHOP DRAWINGS SHALL NOT BE SEALED.
  
 SHEET FP1.1: PROVIDE NON-COMBUSTIBLE 18" DEEP DRAFT
 STOPS AROUND FLOOR OPENING. PROVIDE CLOSELY SPACED
 SPRINKLERS AROUND FLOOR OPENING.
  
  
 GENERAL
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE
 HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE
 THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT
 TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE
 SURFACE.
  
  
 DEMOLITION/CONSTRUCTION
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY.
  
 SMOKING SHALL BE PROHIBITED THROUGHOUT THE DEMOLITION
 AREAS. "NO SMOKING" SIGNS SHALL BE POSTED THROUGHOUT.
  
 SMOKING SHALL BE PERMITTED ONLY IN DESIGNATED AREAS.
 WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES FOR
 SMOKING MATERIALS SHALL BE PROVIDED.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-04-12 Cont ID  
Sent By jwitmer Date 2012-04-12 Time 16:42 Rev Time 0.00
Received By jwitmer Date 2012-04-03 Time 08:27 Sent To  
Notes
2012-04-04 08:28:26INCOMING SENT TO C-26. JW

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-04-04 Cont ID  
Sent By jwitmer Date 2012-04-02 Time 08:26 Rev Time 0.00
Received By jwitmer Date 2012-03-05 Time 15:32 Sent To  
Notes
2012-03-05 15:33:24C--25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-03-05 Cont ID  
Sent By hmoser Date 2012-03-05 Time 13:10 Rev Time 0.00
Received By hmoser Date 2012-01-31 Time 14:05 Sent To  
Notes
2012-01-31 14:05:58C-25

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2012-03-05 Cont ID  
Sent By hmoser Date 2012-03-05 Time 13:04 Rev Time 0.00
Received By hmoser Date 2012-03-05 Time 09:31 Sent To  
Notes
2012-03-05 13:09:46PASS PROVISO
 SEPARATE PLANS AND PERMITS REQUIRED FOR HOODS,WALK IN
 COOLERS AND FREEZERS
 REFER TO SECTION 13-409.AB.3.3 SHUTOFF DAMPER CONTROLS.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2012-03-14 Cont ID  
Sent By lwagner Date 2012-03-14 Time 14:23 Rev Time 0.00
Received By lwagner Date 2012-03-13 Time 15:13 Sent To  
Notes
2012-03-14 13:39:10****PROVISO****
 PLUMBING 1003.4 APPROVED OIL ALARM SYSTEM REQUIRED FOR
 ELEVATOR SUMP PUMP.
  
 IRRIGATION IS NOT PART OF THIS PLAN REVIEW - SEPARATE
 PLAN, REVIEW, AND PERMIT REQUIRED.

Review Stop P PLUMBING
Rev No 2 Status F Date 2012-03-13 Cont ID  
Sent By lwagner Date 2012-03-13 Time 09:04 Rev Time 0.00
Received By lwagner Date 2012-03-07 Time 14:05 Sent To  
Notes
2012-03-07 14:35:06FBC PLUMBING 2007 REVIEW #2
 DENIED:
  
 ISSUES FROM REVIEW #1 THAT WERE NOT ADDRESSED BELOW:
  
 1. SHEETS P2.0, P2.1, P2.2 THE RESTROOM DRAWINGS ARE
 MISSING THE CURCUIT VENT.
 911.2 VENT CONNECTION. THE CIRCUIT VENT CONNECTION
 SHALL BE LOCATED BETWEEN THE TWO MOST UPSTREAM FIXTURE
 DRAINS. THE VENT SHALL CONNECT TO THE HORIZONTAL BRANCH
 AND SHALL BE INSTALLED IN ACCORDANCE WITH SECTION 905.
 THE CIRCUIT VENT PIPE SHALL NOT RECEIVE THE DISCHARGE
 OF ANY SOIL OR WASTE.
  
 2. SHEET P2.0 THE SANITARY BRANCH FOR THE ELEVATOR PUMP
 IS NOT VENTED.
  
 3. PROTECTION FROM OIL IN THE SANITARY SYSTEM WILL BE
 REQUIRED FOR THE ELEVATOR SUMP. AN APPROVED ELECTRONIC
 SENSOR SYSTEM WOULD BE OK.
  
 ***NOTE***
 IRRIGATION WILL NOT BE PART OF THIS REVIEW. SEPARATE
 APPLICATION, PLAN, FEES, PERMIT REQUIRED.
  
  
  
 -------------------------------------------------------
 ------------------------
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-02-10 Cont ID  
Sent By lwagner Date 2012-02-10 Time 14:40 Rev Time 0.00
Received By lwagner Date 2012-02-08 Time 10:37 Sent To  
Notes
2012-02-10 13:52:01FBC PLUMBING 2007 REVIEW #1
 DENIED:
  
 1. SHEETS P2.0, P2.1, P2.2 THE RESTROOM DRAWINGS ARE
 MISSING THE CURCUIT VENT.
 911.2 VENT CONNECTION. THE CIRCUIT VENT CONNECTION
 SHALL BE LOCATED BETWEEN THE TWO MOST UPSTREAM FIXTURE
 DRAINS. THE VENT SHALL CONNECT TO THE HORIZONTAL BRANCH
 AND SHALL BE INSTALLED IN ACCORDANCE WITH SECTION 905.
 THE CIRCUIT VENT PIPE SHALL NOT RECEIVE THE DISCHARGE
 OF ANY SOIL OR WASTE.
  
 2. SHEET P2.0 THE SANITARY BRANCH FOR THE ELEVATOR PUMP
 IS NOT VENTED.
  
 3. PROTECTION FROM OIL IN THE SANITARY SYSTEM WILL BE
 REQUIRED FOR THE ELEVATOR SUMP. AN APPROVED ELECTRONIC
 SENSOR SYSTEM WOULD BE OK.
  
 ***NOTE***
 IRRIGATION WILL NOT BE PART OF THIS REVIEW. SEPARATE
 APPLICATION, PLAN, FEES, PERMIT REQUIRED.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2012-04-12 Cont ID  
Sent By aaponte Date 2012-04-12 Time 11:58 Rev Time 0.00
Received By aaponte Date 2012-04-12 Time 11:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2012-03-14 Cont ID  
Sent By aaponte Date 2012-03-14 Time 15:02 Rev Time 0.00
Received By aaponte Date 2012-03-14 Time 15:02 Sent To  
Notes
2012-03-14 15:17:111. PLEASE INCLUDE A NOTE THAT CLEARLY STATES THAT THE
 MATERIAL ON THE ROW NEXT TO THE PROPOSED ENTRANCE SHALL
 BE CONCRETE SIDEWALK AS REQUIRED BY CITY STANDARDS.
 2. AN ADDITIONAL LIVE OAK TREE SHALL BE PLANTED AT THE
 SOUTH-EAST CORNER OF THE BUILDING, NEXT TO NEW C.U'S.
 3. THE NORTHERN MOST ROYAL PALM ALONG OLIVE AVENUE IS
 DEAD AND NEEDS TO BE REPLACED.
 4. THE EXISTING CONCRETE SIDEWALK ALONG OLIVE AVENUE
 SOUTH OF THE ALLEY IS VERY NARRROW (ONLY 2'8"). STAFF
 RECOMMENDS REDUCING THE PROPOSED LANDSCAPE AND WIDEN
 THE CONCRETE SIDEWALK TO AT LEAST 44" TO PROVIDE ADA
 ACCESSIBILITY COMPLIANCE.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 1 Status F Date 2012-02-13 Cont ID  
Sent By aaponte Date 2012-02-13 Time 11:42 Rev Time 0.00
Received By aaponte Date 2012-02-13 Time 11:42 Sent To  
Notes
2012-02-13 11:48:071. ALL SIDEWALKS OUTSIDE THE PROPERTY LINE SHALL BE
 CONCRETE. DECORATIVE SUFACES ARE NOT PERMITTED (NEW
 GUEST ENTRANCE) OUTSIDE THE PROPETY LINE.
 2. PROPOSED NEW C.U.S SHALL BE SCREENED WITH A WALL AND
 PLANTING ACCORDING TO SECTION 94-444(B).
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.