Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-02-08 Cont ID  
Sent By shill Date 2012-02-08 Time 09:54 Rev Time 0.00
Received By shill Date 2012-02-08 Time 09:54 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-02-01 Cont ID  
Sent By shill Date 2012-02-01 Time 10:00 Rev Time 0.00
Received By shill Date 2012-02-01 Time 10:00 Sent To  
Notes
2012-02-01 10:08:08****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. DESIGN PRESSURES ARE TOO LOW. THIS IS LOCATED IN
 EXPOSURE C, 140 MPH. DOOR PRODUCT APPROVAL SUBMITTED
 HAS AD DESIGN PRESSURE LIMITATION OF +35.7/-35.7.
 PRODUCT TO BE INSTALLED IS TO HAVE A MINIMUM DESIGN
 PRESSURE OF +39.99/-45.3 FOR A BUILDING WHICH IS 20' IN
 HEIGHT. CONTRACTOR TO PROVIDE BUILDING HEIGHT WHEN
 RESUBMITTING. IF BUILDING HEIGHT EXCEEDS 20', DESIGN
 PRESSURES WILL BE HIGHER. ENGINEERING MAY BE REQUIRED.
 FBC1609.1.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-02-08 Cont ID  
Sent By shill Date 2012-02-08 Time 09:54 Rev Time 0.00
Received By shill Date 2012-02-02 Time 16:40 Sent To  
Notes
2012-02-02 16:40:50SENT TO SAMANTHA'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-02-01 Cont ID  
Sent By shill Date 2012-02-01 Time 10:08 Rev Time 0.00
Received By shill Date 2012-01-31 Time 16:43 Sent To  
Notes
2012-01-31 16:44:10SH DESK