Plan Review Details - Permit 12010467
Plan Review Stops For Permit 12010467 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2012-01-27 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2012-01-27 |
Time |
16:29 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2012-01-27 |
Time |
16:22 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2012-02-15 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2012-02-15 |
Time |
10:57 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2012-02-15 |
Time |
10:28 |
Sent To |
|
|
Notes |
2012-02-15 10:53:14 | 701 NORTHPOINT PARKWAY - SUITE #500 | | PERMIT #12010467 | | MASTER #11110281 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | THE TWO EXISTING SPEAKER-STROBE APPLIANCES IN THE MAIN | | CORRIDOR DO NOT PROVIDE ADEQUATE VISUAL COVERAGE PER | | NFPA 72. | | | | PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL | | INITIATE A GENERAL FIRE ALARM CONDITION. | | | | A CERTIFICATE OF COMPLETION AND A THIRD PARTY | | MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL | | BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION. | | | | WESLEY JOLIN | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2012-01-27 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2012-01-27 |
Time |
13:08 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2012-01-27 |
Time |
12:44 |
Sent To |
E |
|
Notes |
2012-01-27 13:08:47 | 701 NORTHPOINT PARKWAY - SUITE #500 | | PERMIT #12010467 | | MASTER #11110281 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | INDICATE ROOM NAMES ON PLANS AND INDICATE THE LOCATION | | OF EXISTING FIRE ALARM DEVICES TO VERIFY SUFFICIENT | | COVERAGE EXISTS FOR THE ENTIRE FLOOR. | | | | THE QUALIFIED SYSTEM DESIGNER SHALL BE IDENTIFIED ON | | THE PLANS. | | | | INDICATE THE ADDRESS OF THE NEW DUCT SMOKE DETECTOR. | | | | PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL | | INITIATE A GENERAL FIRE ALARM CONDITION. | | | | A CERTIFICATE OF COMPLETION AND A THIRD PARTY | | MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL | | BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION. | | | | WESLEY JOLIN | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2012-02-15 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2012-02-15 |
Time |
11:04 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2012-02-07 |
Time |
13:30 |
Sent To |
|
|
Notes |
2012-02-07 13:30:27 | INCOMING SENT TO FIRE BOX. JW |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2012-01-27 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2012-01-27 |
Time |
16:29 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2012-01-23 |
Time |
15:35 |
Sent To |
|
|
Notes |
2012-01-23 15:35:26 | SENT TO FIRE BOX |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |