Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-02-22 Cont ID  
Sent By rlecky Date 2012-02-22 Time 10:49 Rev Time 0.00
Received By rlecky Date 2012-02-22 Time 10:49 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-01-25 Cont ID  
Sent By rlecky Date 2012-01-25 Time 10:59 Rev Time 0.00
Received By rlecky Date 2012-01-25 Time 09:27 Sent To  
Notes
2012-01-25 10:59:5412010464
 508 NORTHWOOD RD.
 NEW SERVICE
  
 SUBMIT AN AVAILABLE FAULT CURRENT LETTER FROM FPL.
 INDICATE THE EQUIPMENT HAS A SUFFICIENT INTERRUPTING
 RATING. NEC 110.9
  
 PROVIDE A SUMMARY LOAD CALCULATION. NEC 230.31
  
 PROVIDE FOR ELECTRICAL SYSTEM GROUNDING. NEC 250.20
  
 PROVIDE AND GROUP ALL SERVICE DISCONNECTS IN ONE
 LOCATION. NEC 230.70, 230.2
  
 INDICATE THE HEIGHT OF THE MAST AND SERVICE LATERAL
 CONDUCTORS. NEC 230.24
  
 PROVIDE AN INTERSYSTEM BONDING TERMINAL. NEC 250.94
  
 THWN REQUIRED FOR WET LOCATIONS. NEC T. 310.13 (A)
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-02-22 Cont ID  
Sent By rlecky Date 2012-02-22 Time 10:49 Rev Time 0.00
Received By rlecky Date 2012-02-22 Time 09:24 Sent To  
Notes
2012-02-22 09:25:06TO ELECTRICAL
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-01-25 Cont ID  
Sent By rlecky Date 2012-01-25 Time 11:00 Rev Time 0.00
Received By rlecky Date 2012-01-23 Time 15:33 Sent To  
Notes
2012-01-23 15:34:39SENT TO ELECTRICAL UNDER $5,000 BOX