Plan Review Details - Permit 12010418
Plan Review Stops For Permit 12010418 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2012-02-07 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2012-02-07 |
Time |
12:29 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2012-02-07 |
Time |
12:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2012-01-24 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2012-01-24 |
Time |
17:29 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2012-01-24 |
Time |
17:29 |
Sent To |
|
|
Notes |
2012-01-24 17:30:34 | PERMIT: 12010419 | | ADDRESS: 3101 OKEECHOBEE BLVD | | CONT: DREAMWORKS ELECTRICAL SERVICES | | TEL: (772)341?9818 | | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS | | * WEST PALM BEACH AMENDMENTS | | 2007 EXISTING BUILDING CODE LEVEL II 701.3 | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | OF THE FLORIDA BUILDING CODE, BUILDING. | | 1ST REVIEW | | ACTION: DENIED | | 1) SHEET PV?8 STRUCTURAL SHEET INDICATES THIS TO BE IN | | A B EXPOSURE WHILE TO THE NORTH THERE IS A CLEAR PATH | | OVER 150 FEET WIDE AND 600 FEET LONG WHICH MAKES THIS A | | EXPOSURE C?TYPE WITH THE INCREASED PRESSURES. FBC?B | | 1609.4.3 EXPOSURE C/ AND ADJUSTMENT FACTOR OF 1.35 @ AN | | ELEVATION OF 25 FT. | | 2) PLEASE PROVIDE A ROOF PLAN WITH THE LOCATION OF THE | | SOLAR PHOTOVOLTAIC PANELS INDICATE WHICH PANELS ARE | | LOCATED IN ROOF ZONES 1, 2 & 3 WITH THE ASSOCIATED | | PRESSURES. | | 3) THE STRUCTURAL PLANS DO NOT PROVIDE THE TYPE OF | | ANCHORS OR SIZE OF ANCHOR TO BE USED IN THE INSTALATION | | TO THE ROOF DECK, NOR DOES THE PLAN INDICATE THE TYPE | | OF ROOF DECK | | THESE ANCHORS ARE BEING INSTALLED IN. THE PLANS | | INDICATE A PULL STRENGTH PER ANCHOR POINT BUT AGAIN | | WHAT TYPE OF MATERIAL IS THIS DESIGN ANCHORED TO? | | ADDITIONAL INFORMATION REQUIRED, MOMENT OF OVERTURNING, | | FBC?B 1609. | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561?805?6715 | | FAX: 561?805?6676 | | E?MAIL: [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2012-02-07 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2012-02-07 |
Time |
12:29 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2012-02-07 |
Time |
12:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2012-01-24 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2012-01-24 |
Time |
17:30 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2012-01-23 |
Time |
09:56 |
Sent To |
|
|
Notes |
2012-01-24 17:19:26 | 12010418 | | 3031 OKEECHOBEE BLVD | | SOLAR PHOTOVOLTAIC SYSTEM | | | | PROVIDE A FLOOR PLAN SHOWING THE RELATIVE LOCATION OF | | THE SYSTEM DEVICES AND OVERCURRENT DEVICES. | | PHOTOVOLTAIC DISCONNECTING MEANS SHALL BE INSTALLED AT | | A READILY ACCESSIBLE LOCATION NEAREST THE POINT OF | | ENTRANCE OF THE SYSTEM CONDUCTORS. NEC 690.14 | | | | INDICATE THE TYPE OF CONDUIT SYSTEM PROPOSED FOR ALL | | AREAS. NEC 690.31 (A) 690.31(E) | | | | VERIFY THE SELECTED EQUIPMENT ROOMS HAVE ADEQUATE | | SAFETY CLEARANCES FOR THE PHOTOVOLTAIC EQUIPMENT. NEC | | 110.26 | | | | SAFETY AND WARNING LABELS PREFERABLY RED IN COLOR ARE | | REQUIRED FOR THE VARIOUS PHOTOVOLTAIC SYSTEM | | COMPONENTS, RACEWAYS, JUNCTION BOXES, INVERTERS, | | COMBINER, SAFETY SWITCH, MDP, INCLUDING THE MAIN | | ELECTRICAL SERVICE AND METER. LABELS ARE TO BE | | PERMANENT. LABELS LOCATED OUTSIDE ARE TO BE SUNLIGHT | | AND WEATHER RESISTANT. NEC 690.53, 690.54, 690.56(B), | | 690.5(C), 690.35(F), 690.14, 690.17, 690.31(E) (3), | | 690.4(F) | | | | PROVIDE AN UPDATED VALUE FOR THE WORK WHICH INCLUDES | | ALL DEVICES AND EQUIPMENT. | | | | | | ROBERT LECKY | | COMMERCIAL COMBINATION PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2012-02-07 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2012-02-07 |
Time |
12:29 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2012-02-03 |
Time |
12:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2012-01-24 |
|
|
Cont ID |
|
Sent By |
rlecky |
Date |
2012-01-24 |
Time |
17:30 |
Rev Time |
0.00 |
Received By |
rlecky |
Date |
2012-01-19 |
Time |
11:01 |
Sent To |
|
|
Notes |
2012-01-20 11:03:57 | ****************EXPEDITED***************** | | GAVE TO LECKY |
|
|
|