Plan Review Details - Permit 12010418
Plan Review Stops For Permit 12010418
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-02-07 Cont ID  
Sent By rlecky Date 2012-02-07 Time 12:29 Rev Time 0.00
Received By rlecky Date 2012-02-07 Time 12:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-01-24 Cont ID  
Sent By rlecky Date 2012-01-24 Time 17:29 Rev Time 0.00
Received By rlecky Date 2012-01-24 Time 17:29 Sent To  
Notes
2012-01-24 17:30:34PERMIT: 12010419
 ADDRESS: 3101 OKEECHOBEE BLVD
 CONT: DREAMWORKS ELECTRICAL SERVICES
 TEL: (772)341?9818
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 1ST REVIEW
 ACTION: DENIED
 1) SHEET PV?8 STRUCTURAL SHEET INDICATES THIS TO BE IN
 A B EXPOSURE WHILE TO THE NORTH THERE IS A CLEAR PATH
 OVER 150 FEET WIDE AND 600 FEET LONG WHICH MAKES THIS A
 EXPOSURE C?TYPE WITH THE INCREASED PRESSURES. FBC?B
 1609.4.3 EXPOSURE C/ AND ADJUSTMENT FACTOR OF 1.35 @ AN
 ELEVATION OF 25 FT.
 2) PLEASE PROVIDE A ROOF PLAN WITH THE LOCATION OF THE
 SOLAR PHOTOVOLTAIC PANELS INDICATE WHICH PANELS ARE
 LOCATED IN ROOF ZONES 1, 2 & 3 WITH THE ASSOCIATED
 PRESSURES.
 3) THE STRUCTURAL PLANS DO NOT PROVIDE THE TYPE OF
 ANCHORS OR SIZE OF ANCHOR TO BE USED IN THE INSTALATION
 TO THE ROOF DECK, NOR DOES THE PLAN INDICATE THE TYPE
 OF ROOF DECK
 THESE ANCHORS ARE BEING INSTALLED IN. THE PLANS
 INDICATE A PULL STRENGTH PER ANCHOR POINT BUT AGAIN
 WHAT TYPE OF MATERIAL IS THIS DESIGN ANCHORED TO?
 ADDITIONAL INFORMATION REQUIRED, MOMENT OF OVERTURNING,
 FBC?B 1609.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561?805?6715
 FAX: 561?805?6676
 E?MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-02-07 Cont ID  
Sent By rlecky Date 2012-02-07 Time 12:29 Rev Time 0.00
Received By rlecky Date 2012-02-07 Time 12:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-01-24 Cont ID  
Sent By rlecky Date 2012-01-24 Time 17:30 Rev Time 0.00
Received By rlecky Date 2012-01-23 Time 09:56 Sent To  
Notes
2012-01-24 17:19:2612010418
 3031 OKEECHOBEE BLVD
 SOLAR PHOTOVOLTAIC SYSTEM
  
 PROVIDE A FLOOR PLAN SHOWING THE RELATIVE LOCATION OF
 THE SYSTEM DEVICES AND OVERCURRENT DEVICES.
 PHOTOVOLTAIC DISCONNECTING MEANS SHALL BE INSTALLED AT
 A READILY ACCESSIBLE LOCATION NEAREST THE POINT OF
 ENTRANCE OF THE SYSTEM CONDUCTORS. NEC 690.14
  
 INDICATE THE TYPE OF CONDUIT SYSTEM PROPOSED FOR ALL
 AREAS. NEC 690.31 (A) 690.31(E)
  
 VERIFY THE SELECTED EQUIPMENT ROOMS HAVE ADEQUATE
 SAFETY CLEARANCES FOR THE PHOTOVOLTAIC EQUIPMENT. NEC
 110.26
  
 SAFETY AND WARNING LABELS PREFERABLY RED IN COLOR ARE
 REQUIRED FOR THE VARIOUS PHOTOVOLTAIC SYSTEM
 COMPONENTS, RACEWAYS, JUNCTION BOXES, INVERTERS,
 COMBINER, SAFETY SWITCH, MDP, INCLUDING THE MAIN
 ELECTRICAL SERVICE AND METER. LABELS ARE TO BE
 PERMANENT. LABELS LOCATED OUTSIDE ARE TO BE SUNLIGHT
 AND WEATHER RESISTANT. NEC 690.53, 690.54, 690.56(B),
 690.5(C), 690.35(F), 690.14, 690.17, 690.31(E) (3),
 690.4(F)
  
 PROVIDE AN UPDATED VALUE FOR THE WORK WHICH INCLUDES
 ALL DEVICES AND EQUIPMENT.
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-02-07 Cont ID  
Sent By rlecky Date 2012-02-07 Time 12:29 Rev Time 0.00
Received By rlecky Date 2012-02-03 Time 12:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-01-24 Cont ID  
Sent By rlecky Date 2012-01-24 Time 17:30 Rev Time 0.00
Received By rlecky Date 2012-01-19 Time 11:01 Sent To  
Notes
2012-01-20 11:03:57****************EXPEDITED*****************
 GAVE TO LECKY