Plan Review Details - Permit 12010415
Plan Review Stops For Permit 12010415
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2012-07-13 Cont ID  
Sent By rmcdouga Date 2012-07-13 Time 08:46 Rev Time 0.00
Received By rmcdouga Date 2012-07-13 Time 08:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2012-07-13 Cont ID  
Sent By rmcdouga Date 2012-07-12 Time 16:54 Rev Time 0.00
Received By rmcdouga Date 2012-07-12 Time 13:20 Sent To  
Notes
2012-07-12 16:55:51ONE SET OF PLANS IS MISSING THE NEW STRUCTURAL PLAN
 SHEETS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2012-06-20 Cont ID  
Sent By rmcdouga Date 2012-06-20 Time 11:12 Rev Time 0.00
Received By rmcdouga Date 2012-06-20 Time 09:30 Sent To  
Notes
2012-06-20 11:11:562007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE CONCRETE BEAM (B-2) AT THE 10 FT WIDE GARAGE
 DOOR OPENING IS NOT LISTED IN THE BEAM & LINTEL DETAILS
 ON SHEET S1.2 AND THE BEAM SCHEDULE HAS BEEN REMOVED.
 PLEASE PROVIDE DETAIL FOR THIS BEAM. CITY AMENDMENTS
 107.2.1
  
 2) THE NOTE ON SHEET S1.3 SPECIFIES 8D SHANK NAILS FOR
 FASTENING THE ROOF SHEATHING . FBC R803.2.3.1 REQUIRES
 RING SHANK NAILS. PLEASE CORRECT.
  
 3) SPECIFY THE ROOF UPLIFT PRESSURES IN THE CHART ON
 SHEET S1.3. FBC R301.2.1
  
 4) THE PLANS APPEAR TO SHOW A NON-VENTED ATTIC AND THE
 ENERGY CALCULATIONS SPECIFY A VENTED ATTIC. PLEASE
 CORRECT. CITY AMENDMENTS 107.2.1
  
 5) SUBMIT TWO COPIES OF THE EVALUATION REPORT FOR THE
 SPRAY FOAM INSULATION THAT WILL BE USED IN THE
 NON-VENTED ATTIC. FBC R316.3
  
 6) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 7) SEVERAL OF THE PRODUCT APPROVALS HAVE BEEN
 SUPERSEDED OR ARE EXPIRED. PLEASE REVIEW ALL TO MAKE
 SURE THEY ARE CURRENT. DCA RULE 9N-3
  
 8) SPECIFY THE ROOF & FLOOR TRUSS DESIGN LIVE AND DEAD
 LOADS ON THE PLANS. FBC R301.1 NOTE: THE DESIGN LOADS
 OF THE TRUSSES WILL HAVE TO MATCH THE ROOF AND FLOOR
 LIVE AND DEAD LOADS SPECIFIED ON THE PLANS. FBC
 R802.10.1
  
 9) THE TRUSS LAYOUT FROM THE TRUSS COMPANY NEEDS TO BE
 SIGNED AND SEALED BY THE TRUSS ENGINEER AND REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD FOR THE
 STRUCTURE. FS 471 AND CITY AMENDMENTS 107.1 NOTE: TRUSS
 DRAWINGS FOR ONE AND TWO FAMILY DWELLINGS DO NOT HAVE
 TO BE SUBMITTED FOR PLAN REVIEW. THEY CAN BE PROVIDED
 TO THE FIELD INSPECTOR AT THE ROOF FRAMING INSPECTION.
  
 10) NOTE: IN ORDER TO SPEED REVIEW TIME, PLEASE PROVIDE
 A RESPONSE LETTER INDICATING HOW THE REVIEW COMMENTS
 WERE ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-05-14 Cont ID  
Sent By rmcdouga Date 2012-05-14 Time 12:08 Rev Time 0.00
Received By rmcdouga Date 2012-05-10 Time 13:32 Sent To  
Notes
2012-05-11 15:47:342010 FBC
  
 DENIED BY BUILDING
  
 1) PLANS REFERENCE THE 2010 FBC. THE PERMIT WAS APPLIED
 FOR ON 1/19/2O12 WHICH WAS PRIOR TO THE IMPLEMENTATION
 DATE OF THE 2010 FBC AND ASCE 7- 10 ON 3/15/20102. THE
 2007 FBC W2009 REVISIONS WAS THE CODE IN EFFECT AT THE
 TIME OF APPLICATION. BECAUSE THE PLANS WERE HELD UP IN
 ZONING AND NOT SENT TO BUILDING DEPT. UNTIL AFTER THE
 CODE CHANGE IF YOU CHOOSE TO DO SO THE APPLICATION DATE
 CAN BE CHANGED TO ALLOW DESIGN UNDER THE 2010 CODE PER
 ROBERT BROWN.
  
 2) BECAUSE THE PROPOSED STRUCTURE IS LOCATED WITHIN
 1500 FEET OF THE INTER-COASTAL WATERWAY THE EXPOSURE
 CATEGORY IS C AND THE WIND SPEED FOR WEST PALM BEACH IS
 170 MPH UNDER THE 2010 CODE AND 140 UNDER THE 2007
 CODE. PLEASE REVISE.
  
 3) THE COMPONENT AND CLADDING PRESSURES SPECIFIED ON
 THE PLANS ARE TOO LOW. FBC R301.2.1 PLEASE REVISE.
  
 4) THE FRONT AND REAR ELEVATIONS ON A2.1 DO NOT HAVE
 ALL OF THE WINDOWS AND DOORS TAGGED TO CORRESPOND WITH
 THE WINDLOAD SCHEDULE. R301.2.1
  
 5) THE BOTTOM OF ALL EXTERIOR FOOTERS ARE REQUIRED BY
 FBC R403.1.4 TO BE AT LEAST 12 INCHES BELOW THE GROUND
 SURFACE. THE SOIL REPORT SUBMITTED RECOMMENDS 16" TO
 24" BELOW THE FINISHED PAD OR MONOLITHIC SLAB.
  
 6) FBC R404.1.6 REQUIRES THE FOUNDATION TO EXTEND A
 MINIMUM OF 4 INCHES ABOVE THE FINISHED GRADE ADJACENT
 TO THE FOUNDATION.
  
 7) SHOW COMPLIANCE WITH FBC R310 FOR THE REQUIRED
 EMERGENCY ESCAPE AND RESCUE OPENINGS. THE SECOND FLOOR
 BEDROOMS DO NOT COMPLY. PLEASE CLARIFY "EH" TAG SHOWN
 AT THE WINDOWS ON THE FRONT AND REAR ELEVATIONS ON
 A2.1.
  
 8) SUBMIT TWO COPIES OF A SURFACE WATER DRAINAGE PLAN
 SHOWING COMPLIANCE WITH FBC R401.3.
  
 9) SPECIFY THE BOLTS FOR THE 2 X 4 AND 2 X 6
 ATTACHMENTS TO THE CONCRETE BEAM FOR THE LOWER ROOF
 SHOWN ON WALL SECTION 3 ON A4.2. FBC R301.1
  
 10) WALL SECTION 5 ON SHEET A4.2 IS MIS-LABELED. IT IS
 A SECTION AT THE PATIO NOT THE GARAGE. CITY AMENDMENTS
 107.2.1
  
 11) SHOW COMPLIANCE WITH FBC R502.1.2 FOR DRAFTSTOPPING
 AT THE FLOOR CEILING ASSEMBLY NOT TO EXCEED 1000 SQFT.
  
 12) THERE IS NO F1 FOOTER SHOWN IN THE SCHEDULE ON
 SHEET S1.1 FOR THE C1 COLUMN PAD SHOWN ON THE
 FOUNDATION PLAN. CITY AMENDMENTS 107.2.1
  
 13) PROVIDE A DETAIL FOR THE 2 X 4 AND 2 X 6 INTERIOR
 BEARING WALLS. FBC R301.1
  
 14) SPECIFY THE CONNECTORS THAT WILL BE USED AT THE TOP
 AND BOTTOM OF THE 6 X 6 WOOD COLUMNS. FBC R301.1
  
 15) PROVIDE A DETAIL FOR THE BUILT- UP (3) 2X 6 WOOD
 COLUMN. FBC R301.1
  
 16) PROVIDE THE MISSING STRUCTURAL DETAILS FOR COLUMN
 C-5 IN THE SCHEDULE ON SHEET S1.1. FBC R301.1
  
 17) PLEASE CLARIFY THE NOTE AT THE GARAGE ON SHEET S1.1
 FOR THE 16" X 16" STRIP FOOTING. A TE 2 18" X 12"
 FOOTING IS SHOWN. CITY AMENDMENTS 107.2.1
  
 18) ON SHEET S1.2 THE TAGS FOR THE BEAMS ON THE PLAN
 ARE B-1 AND B-2 AND IN THE SCHEDULE THEY ARE BM-1 AND
 BM-2. PLEASE CORRECT. CITY AMENDMENTS 107.2.1
  
 19) THE NOTE ON SHEET S1.3 SPECIFIES 8D COMMON NAILS
 FOR FASTENING THE ROOF SHEATHING . FBC R803.2.3.1
 REQUIRES RING SHANK NAILS. PLEASE CORRECT.
  
 2O) THE ROOF PRESSURE AND WALL PRESSURE CHARTS ON S1.3
 ARE MISSING THE PRESSURES. FBC R301.2.1
  
 21) THERE ARE NOT ANY WOOD TO WOOD CONNECTORS SPECIFIED
 IN THE SCHEDULE ON S1.3 FOR THE 6 X 12 WOOD BEAM TO
 RAFTERS AT THE PATIO. PLEASE CORRECT. FBC R301.1
  
 22) THE PLANS APPEAR TO SHOW A NON-VENTED ATTIC WITH
 R-20 INSULATION AND THE ENERGY CALCULATIONS SPECIFY A
 R-30 VENTED ATTIC. PLEASE CORRECT. CITY AMENDMENTS
 107.2.1
  
 23) SUBMIT TWO COPIES OF THE EVALUATION REPORT FOR THE
 SPRAY FOAM INSULATION THAT WILL BE USED IN THE
 NON-VENTED ATTIC. FBC R316.3
  
 24) THE FORM THAT WAS SUBMITTED 1100A-08 CAN NOT BE
 USED WITH THE 2010 FBC. SEE FBC ENERGY CONSERVATION
 SECTION 405.4.
  
 25) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 26) SEVERAL OF THE PRODUCT APPROVALS HAVE BEEN
 SUPERSEDED OR EXPIRED PRIOR TO THE IMPLEMENTATION OF
 THE 2010 FBC. PLEASE REVIEW ALL TO MAKE SURE THEY ARE
 CURRENT. DCA RULE 9N-3
  
 27) THE TRUSS DRAWING THAT WERE SUBMITTED SPECIFY THE
 2007 FBC AND ASCE 7-05 WITH A 140 MPH WIND SPEED. TO
 CORRESPOND WITH PLANS DESIGNED TO THE 2010 FBC, THE
 TRUSSES WILL NEED TO DESIGNED TO THE 2010 FBC AND ASCE
 7-10 WITH A 170 MPH WIND SPEED. PLEASE CORRECT. CITY
 AMENDMENTS 107.2.1
  
 28) SPECIFY THE ROOF & FLOOR TRUSS DESIGN LIVE AND DEAD
 LOADS ON THE PLANS. FBC R301.1
  
 29) THE TRUSS DESIGN LOADS OF THE TRUSSES WILL HAVE TO
 MATCH THE ROOF AND FLOOR LIVE AND DEAD LOADS SPECIFIED
 ON THE PLANS. FBC R802.10.1
  
 30) THE TRUSS LAYOUT FROM THE TRUSS COMPANY NEEDS TO BE
 SIGNED AND SEALED BY THE TRUSS ENGINEER AND REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD FOR THE
 STRUCTURE. FS 471 AND CITY AMENDMENTS 107.1
  
 31) NOTE: TRUSS DRAWINGS FOR ONE AND TWO FAMILY
 DWELLINGS DO NOT HAVE TO BE SUBMITTED FOR PLAN REVIEW.
 THEY CAN BE PROVIDED TO THE FIELD INSPECTOR AT THE ROOF
 FRAMING INSPECTION.
  
 32) NOTE: IN ORDER TO SPEED REVIEW TIME, PLEASE PROVIDE
 A RESPONSE LETTER INDICATING HOW THE REVIEW COMMENTS
 WERE ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-06-07 Cont ID  
Sent By rlecky Date 2012-06-07 Time 08:26 Rev Time 0.00
Received By rlecky Date 2012-06-06 Time 16:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-04-30 Cont ID  
Sent By rlecky Date 2012-04-30 Time 14:17 Rev Time 0.00
Received By rlecky Date 2012-04-30 Time 12:23 Sent To  
Notes
2012-04-30 14:17:2312010415
 419 33RD STREET
 NEW SFD
  
 PLEASE REDRAW THE ELECTRICAL RISER TO SHOW HOW EACH
 PANEL BOARD WILL BE FED. LOCATE THE ELECTRIC PANEL
 BOARDS ON THE PLAN. SHOW THE GROUNDING SYSTEM FOR EACH
 SUB PANEL. NEC 215.5
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. 2008 NEC 250.94
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
 INDICATE THAT ALL GENERAL PURPOSE BRANCH CIRCUITS MUST
 BE PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. 2008
 NEC 210.12
 THE BATHROOMS REQUIRE A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
 ADD A GFCI PROTECTED RECEPTACLE TO SERVE EACH BASIN IN
 THE SECOND FLOOR BATH. NEC 210.52 (D)
 SMOKE DETECTORS ARE REQUIRED TO BE INTERCONNECT AND
 LOCATED INSIDE AND OUTSIDE EACH SLEEPING AREA. FBC R
 313
  
 ROBERT LECKY, CBO
 ELECTRIC PLANS EXAMINER
 [email protected]
 561-805-6718
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2012-04-05 Cont ID  
Sent By spalmer Date 2012-04-05 Time 14:20 Rev Time 0.00
Received By spalmer Date 2012-04-05 Time 14:20 Sent To  
Notes
2012-04-05 14:21:31OKAY PER FRIEDERIKE MITTNER

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2012-01-20 Cont ID  
Sent By fmittner Date 2012-01-20 Time 14:05 Rev Time 0.00
Received By fmittner Date 2012-01-20 Time 14:05 Sent To  
Notes
2012-01-20 14:07:30NEW CONSTRUCTION PLANS REQUIRE HPB APPROVAL. FHM SPOKE
 TO ALONSO AND ASSOC 1-20-12, THEY WILL FILL OUT COA
 FORM AND SUBMIT NEXT WEEK FOR FEB HEARING. FAMILIAR
 WITH APPLICATION. QUESTIONS CONTACT 822-1457. PLACING
 PERMIT IN HISTORIC HOLD BIN.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2012-07-13 Cont ID  
Sent By rmcdouga Date 2012-07-13 Time 08:47 Rev Time 0.00
Received By rmcdouga Date 2012-07-09 Time 11:21 Sent To  
Notes
2012-07-09 11:21:30TO RM DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-06-20 Cont ID  
Sent By rmcdouga Date 2012-06-20 Time 11:12 Rev Time 0.00
Received By rmcdouga Date 2012-05-31 Time 11:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-05-14 Cont ID  
Sent By rmcdouga Date 2012-05-14 Time 12:08 Rev Time 0.00
Received By rmcdouga Date 2012-04-05 Time 16:13 Sent To  
Notes
2012-04-05 16:15:36R--2

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2012-07-13 Cont ID  
Sent By rmcdouga Date 2012-07-13 Time 08:46 Rev Time 0.00
Received By rmcdouga Date 2012-07-13 Time 08:46 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-05-10 Cont ID  
Sent By rmcdouga Date 2012-05-10 Time 09:09 Rev Time 0.00
Received By rmcdouga Date 2012-05-10 Time 09:09 Sent To  
Notes
2012-05-10 09:10:08PALM BEACH COUNTY IMPACT FEE REVIEW WILL BE REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-06-19 Cont ID  
Sent By rmcdouga Date 2012-06-19 Time 15:05 Rev Time 0.00
Received By hmoser Date 2012-06-19 Time 15:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-05-10 Cont ID  
Sent By rmcdouga Date 2012-05-10 Time 10:45 Rev Time 0.00
Received By rmcdouga Date 2012-05-10 Time 10:45 Sent To  
Notes
2012-05-10 10:50:262010 FBC
  
 DENIED BY MECHANICAL
  
 1) NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. A
 SEPARATE APPLICATION, PLANS AND REVIEW WILL BE
 REQUIRED. CITY AMENDMENTS 107.3.5.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2012-06-19 Cont ID  
Sent By rmcdouga Date 2012-06-19 Time 15:05 Rev Time 0.00
Received By rmcdouga Date 2012-06-19 Time 15:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2012-05-10 Cont ID  
Sent By rmcdouga Date 2012-05-10 Time 11:11 Rev Time 0.00
Received By rmcdouga Date 2012-05-10 Time 09:00 Sent To  
Notes
2012-05-10 13:32:082010 FBC
  
 DENIED BY PLUMBING
  
 1) THE FIRST FLOOR GUEST BATH ROOM IS NOT PROPERLY
 VENTED. FBC P3101.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2012-04-05 Cont ID  
Sent By fmittner Date 2012-04-05 Time 14:29 Rev Time 0.00
Received By fmittner Date 2012-04-05 Time 14:29 Sent To  
Notes
***NONE***