Plan Review Details - Permit 12010347
Plan Review Stops For Permit 12010347
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-02-03 Cont ID  
Sent By rlecky Date 2012-02-03 Time 17:02 Rev Time 0.00
Received By rlecky Date 2012-02-03 Time 16:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-01-26 Cont ID  
Sent By rlecky Date 2012-01-26 Time 14:19 Rev Time 0.00
Received By rlecky Date 2012-01-26 Time 14:05 Sent To  
Notes
2012-01-26 14:20:25PLEASE RESPOND TO THE FIRE COMMENTS. RL

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-02-03 Cont ID  
Sent By wjolin Date 2012-02-03 Time 12:44 Rev Time 0.00
Received By wjolin Date 2012-02-03 Time 11:50 Sent To E
Notes
2012-02-03 12:05:19324 DATURA STREET - SUITE #209
 PERMIT #12010347
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NOTE: THESE REQUIREMENTS ARE DIFFERENT THAN THE
 REQUIREMENTS OF FOR MAGNETIC LOCKS WHEREBY AN OCCUPANT
 SENSOR AND PUSH TO EXIT BUTTON ARE NEEDED IN ON THE
 EGRESS SIDE.
  
 SECTION 7.2.1.5.5 OF NFPA 101 FLORIDA EDITION 2009
 ALLOWS ELECTRICALLY CONTROLLED EGRESS DOOR ASSEMBLIES
 IF EQUIPPED WITH APPROVED LISTED HARDWARE THAT
 INCORPORATES A BUILT-IN SWITCH AND THE FOLLOWING FIVE
 CRITERIA ARE MET:
 1. THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO THE DOOR LEAF.
 2. THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION THAT
 IS READILY OPERATED IN THE DIRECTION OF EGRESS.
 3. THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND IN THE DIRECTION OF EGRESS.
 4. OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE
 DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 5. LOSS OF POWER TO THE HARDWARE AUTOMATICALLY UNLOCKS
 THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-01-23 Cont ID  
Sent By wjolin Date 2012-01-23 Time 15:08 Rev Time 0.00
Received By wjolin Date 2012-01-23 Time 14:56 Sent To E
Notes
2012-01-23 15:08:17324 DATURA STREET - SUITE #209
 PERMIT #12010347
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE TOTAL JOB VALUE SHALL INCLUDE ALL MATERIALS IN
 ADDITION TO LABOR.
  
 INDICATE THE OCCUPANCY OR BUSINESS TYPE ASSOCIATED WITH
 THIS SUITE.
  
 INDICATE HOW THE DOORS/SECURITY SYSTEM ARE RELEASED IN
 THE DIRECTION OF EGRESS.
  
 ONE CARD READER LOCATION APPEARS TO BE LOCATED ON THE
 EGRESS SIDE OF THE DOOR. IS THIS ACCURATE?
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-02-03 Cont ID  
Sent By rlecky Date 2012-02-03 Time 17:02 Rev Time 0.00
Received By rlecky Date 2012-01-31 Time 13:15 Sent To  
Notes
2012-01-31 13:15:52INCOMING SENT TO FIRE BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-01-26 Cont ID  
Sent By rlecky Date 2012-01-26 Time 14:46 Rev Time 0.00
Received By rlecky Date 2012-01-18 Time 13:44 Sent To  
Notes
2012-01-18 13:44:24TO FIRE BOX