Plan Review Details - Permit 12010341
Plan Review Stops For Permit 12010341
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-03-01 Cont ID  
Sent By shill Date 2012-03-01 Time 11:29 Rev Time 0.00
Received By shill Date 2012-02-27 Time 07:44 Sent To  
Notes
2012-03-01 11:30:39PROVISO - SUBMIT PRODUCT APPROVALS FOR MULLIONS, ENTRY
 DOOR, AND SINGLE HUNG WINDOW AS A REVISION PRIOR TO
 INSTALLATION
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-02-02 Cont ID  
Sent By shill Date 2012-02-02 Time 10:19 Rev Time 0.00
Received By shill Date 2012-01-31 Time 12:01 Sent To  
Notes
2012-02-02 10:19:32****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. IMPACT FEE ASSESSMENT REQUIRED; CONTACT 561-233-5025
 FOR MORE INFORMATION.
  
 2. FIREPLACE SPECS REQUIRED, FBC R1005. THIS MAY BE
 SUBMITTED AT THIS TIME OR WILL BE PROVISO ITEM TO
 SUBMIT AS A REVISION.
  
 3. PROVIDE PRODUCT APPROVALS FOR THE ENTRY DOOR,
 MULLION, SINGLE HUNG WINDOW, FAC9N-3. THIS MAY BE
 SUBMITTED AT THIS TIME OR WILL BE A PROVISO ITEM TO
 SUBMIT AS A REVISION AFTER ISSUANCE.
  
 4. DESIGN PRESSURES ON ARCHITECTURAL SHEETS APPEAR TOO
 LOW (FOR EXAMPLE, SHEET A02) AND IN CONFLICT WITH
 STRUCTURAL SHEET S0, FBC R301. PLEASE REMOVE FROM
 AFFECTED SHEETS OR CORRELATE WITH STRUCTURAL SHEETS.
  
 5. SHEET A.08, STRUCTURAL CRITERIA, INCORRECTLY STATES
 100 MPH FASTEST MILE NON WIND BORNE DEBRIS REGION.
 OTHER AREAS OF PLAN CORRECTLY DECLARE WIND DESIGN
 CRITERIA AS 140MPH, EXPOSURE C. AS THIS APPEARS TO BE A
 TYPO, PLEASE REMOVE LANGUAGE FROM PLAN TO AVOID
 POSSIBLE CONFLICTS, FBC R301. IF THIS IS NOT A TYPO AND
 IS DESIGN INTENT, PLEASE CONTACT ME TO DISCUSS.
  
 6. M2, PROVIDE PRODUCT APPROVAL FOR THE MIAMI TECH CU
 TIE DOWNS, FAC9N 3. PLAN STATES THAT THESE ARE TO BE
 INSTALLED IN ACCORDANCE WITH MANUFACTURER?S
 INSTRUCTIONS, BUT I WAS UNABLE TO LOCATE THE PRODUCT
 WITH THIS DESCRIPTION ON THE INTERNET. PROVIDE SPEC
 SHEETS AND FASTENING PATTERN/CONFIGURATION TO SHOW HOW
 THE UNIT WILL RESIST WIND LOADS, FBC R301.
  
 7. PROVIDE ORIGINAL SOILS INVESTIGATION REPORT, FS471.
 DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS.
  
 8. ENERGY CALCS ARE INCOMPLETE. PLEASE PROVIDE CORRECT
 ENERGY CALCS, FBC 13 103.1.1.2. PREPARER AND
 OWNER/AGENT ARE TO READY ENERGY CALCS AND CERTIFY AS TO
 ACCURACY PRIOR TO SIGNING.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2012-02-22 Cont ID  
Sent By rlecky Date 2012-02-22 Time 16:45 Rev Time 0.00
Received By rlecky Date 2012-02-22 Time 16:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-01-23 Cont ID  
Sent By rlecky Date 2012-01-23 Time 09:10 Rev Time 0.00
Received By rlecky Date 2012-01-20 Time 12:22 Sent To  
Notes
2012-01-23 09:11:1412010341
 235 EDMOR RD.
 NEW CUSTOM HOME
  
 CARBON MONOXIDE DETECTORS ARE REQUIRED WITHIN 10 FEET
 OF ALL SLEEPING AREAS. FBC R313
 ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2
 FEET IN WIDTH HAVE A RECEPTACLE I.E. WET BAR, FRONT
 ENTRY, BEDROOM 3, UNDER STAIRCASE ETC. NEC 210.52
 PANEL BOARD FEEDERS APPEAR TO BE UNDERSIZED. MIN. 3/0
 REQUIRED FOR 200 AMPERE BREAKER. NEC T. 310.16
 PANEL ?C? EQUIPMENT GROUND SHOULD BE #6. NEC T. 250.122
 INDICATE LOCATION OF ALL PANEL BOARDS AND THE
 ELECTRICAL SERVICE. NEC 215.5
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-03-09 Cont ID  
Sent By shill Date 2012-03-08 Time 07:38 Rev Time 0.00
Received By shill Date 2012-02-16 Time 15:32 Sent To  
Notes
2012-02-16 15:32:53SENT TO R24 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-02-02 Cont ID  
Sent By rmcdouga Date 2012-02-02 Time 15:32 Rev Time 0.00
Received By rmcdouga Date 2012-01-18 Time 10:28 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2012-03-01 Cont ID  
Sent By shill Date 2012-03-01 Time 13:14 Rev Time 0.00
Received By shill Date 2012-03-01 Time 13:14 Sent To  
Notes
2012-03-01 13:15:06MU 2012 002569 0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2012-03-01 Cont ID  
Sent By shill Date 2012-03-01 Time 08:23 Rev Time 0.00
Received By shill Date 2012-03-01 Time 08:22 Sent To  
Notes
2012-03-01 08:24:28PROVIDE IMPACT FEE RECEIPT FOR 2012-2569
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2012-02-02 Cont ID  
Sent By shill Date 2012-02-02 Time 07:59 Rev Time 0.00
Received By shill Date 2012-02-02 Time 07:59 Sent To  
Notes
2012-02-02 08:08:11****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. IMPACT FEE ASSESSMENT REQUIRED. PLEASE CONTACT
 561-233-5025 FOR MORE INFORMATION. THE PLANS ARE TO BE
 STAMPED AND THE RECEIPT, IF APPLICABLE, IS TO BE
 PROVIDED.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-02-28 Cont ID  
Sent By rmcdouga Date 2012-02-28 Time 08:18 Rev Time 0.00
Received By rmcdouga Date 2012-02-28 Time 07:24 Sent To  
Notes
2012-02-28 16:50:57REVISED PLANS REQUIRED SHOWING RETURN DUCT SIZES FOR
 A/H #1 @ WET BAR AND A/H #2 @ MASTER BEDROOM.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-02-02 Cont ID  
Sent By rmcdouga Date 2012-02-02 Time 15:31 Rev Time 0.00
Received By rmcdouga Date 2012-01-31 Time 14:28 Sent To  
Notes
2012-02-02 15:48:512007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) THE ENERGY CALCULATIONS ARE NOT COMPLETE. IT APPEARS
 THAT THERE MAY HAVE BEEN AN ERROR WITH THE PRINTER.
 PLEASE SUBMIT TWO COMPLETE COPIES OF THE ENERGY
 CALCULATIONS AS REQUIRED BY N1100.2 OF THE 2007 FBC
 ENERGY GLITCH AMENDMENTS.
  
 2) THE HVAC SYSTEM HAS BEEN DESIGNED BY A DIFFERENT
 MECHANICAL CONTRACTOR THAN THE ONE THAT IS SIGNED ON
 THE PERMIT APPLICATION TO DO THE WORK. UNDER THE DESIGN
 AND BUILD EXEMPTION TO FLORIDA STATUTE 471.003(2)(H),
 THE MECHANICAL CONTRACTOR IS ALLOWED TO DESIGN THE
 SYSTEM ONLY IF IT IS INSTALLED BY HIM. SINCE THIS IS
 NOT THE CASE, THE MECHANICAL PLANS ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE DESIGN ENGINEER.
  
 3) ON SHEET M2 BOTH OF THE AIR HANDLERS FOR THE SECOND
 FLOOR ARE LABELED AHU #3. PLEASE CORRECT. CITY
 AMENDMENTS 106.1.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2012-01-26 Cont ID  
Sent By rmcdouga Date 2012-01-26 Time 08:21 Rev Time 0.00
Received By rmcdouga Date 2012-01-24 Time 14:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2012-03-08 Cont ID  
Sent By ajones Date 2012-03-08 Time 12:58 Rev Time 0.00
Received By ajones Date 2012-03-08 Time 12:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2012-02-01 Cont ID  
Sent By lfranco Date 2012-02-01 Time 15:07 Rev Time 0.00
Received By lfranco Date 2012-02-01 Time 15:04 Sent To  
Notes
2012-02-01 15:19:24PLANNING: **** FAILED ****
  
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. THE SURVEY AND THE SITE PLAN DIMENSIONS DO NOT
 MATCH. SURVEY SHOWS A DEPTH OF 96.7' AND SITE PLAN
 SHOWS 97'. REVISE ACCORDINGLY. SHOW UTILITY EASEMENT ON
 THE PLANS, PER SURVEY.
  
 3. A SEPARATE PERMIT FOR THE DRIVEWAY WILL BE REQUIRED
 THROUGH THE ENGINEERING DEPARTMENT, IF THE SCOPE OF
 WORK SHOW ON THE SITE PLAN ARE EXCLUDING THE WORK.
 HOWEVER, SHOW DIMENSIONS WIDTH OF THE DRIVEWAY ON THE
 SITE PLAN.
  
 4. WHAT ARE THE FOUR RECTANGULAR BOXES ON THE UPPER
 RIGHT HAND SIDE OF THE PLANS?
  
 5.SHOW A/C ON SITE PLAN AND INDICATE SETBACK DIMENSIONS
 FROM PROPOSED A/C EQUIPMENT TO ALL PROPERTY LINES.
 PURSUANT TO SECTION 94-305(B)(4) OF THE ZLDR:
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET
 INTO A REQUIRED SETBACK.
  
 NOTE: IF A PATIO OR PAVED AREA IS PROVIDED ADJACENT TO
 OR SURROUNDING A POOL, IT SHALL BE DESIGNED TO DRAIN
 AWAY FROM THE POOL, BUT NOT ONTO ADJACENT PROPERTIES.
  
 6. PROVIDE HEIGHT OF BUILDING TO THE TOP OF THE ROOF
 LINE. THE MAXIMUM BUILDING HEIGHT IS 30 FEET.
  
 7. SEPARATE LANDSCAPE AND IRRIGATION PERMITS ARE
 REQUIRED. TWO COPIES OF THE LANDSCAPE PLAN AND A
 CERTIFIED COST ESTIMATE THAT INCLUDES THE TOTAL COST OF
 ALL LANDSCAPE MATERIALS AND LABOR, BROKEN DOWN INTO
 UNIT COST SHALL BE SUBMITTED WITH THE LANDSCAPE PERMIT
 APPLICATION.
  
 8. SUBMIT TWO COPIES OF THE IRRIGATION PLAN WITH THE
 IRRIGATION PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO, AICP
 SENIOR PLANNER
 PLANNING DIVISION
 TEL: (561) 822-1443
 EMAIL: [email protected]
  