Plan Review Details - Permit 12010178
Plan Review Stops For Permit 12010178
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2012-01-11 Cont ID  
Sent By wjolin Date 2012-01-11 Time 10:30 Rev Time 0.00
Received By wjolin Date 2012-01-11 Time 10:21 Sent To  
Notes
2012-01-11 10:23:21400 NORTH FLAGLER DRIVE
 PERMIT #12010178
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY.
  
 TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES.
  
 POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  