Plan Review Details - Permit 12010161
Plan Review Stops For Permit 12010161
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2012-01-11 Cont ID  
Sent By jgomez Date 2012-01-11 Time 15:41 Rev Time 0.00
Received By jgomez Date 2012-01-11 Time 15:01 Sent To  
Notes
2012-01-11 15:43:07BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- ANY RETROFIT ROOF DRAINS OR DRAINAGE SYSTEM CHANGE
 NEED PLUMBING REVIEW APPROVAL.
  
 2- ANY ROOF EQUIPMENT REMOVAL REQUIRES SEPARATE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2012-01-10 Cont ID  
Sent By jgomez Date 2012-01-10 Time 09:06 Rev Time 0.00
Received By jgomez Date 2012-01-10 Time 09:01 Sent To  
Notes
2012-01-10 09:15:14RE-ROOF BUILDING REVIEW COMMENTS.
 2007 FBC WITH 2009 REVISIONS.
  
 1-THE WIND SPEED ADOPTED FOR THE CITY OF WEST PALM
 BEACH IS 140MPH. SEC. 117 CITY AMENDMENTS TO FBC.
 ENGINEER CALCULATIONS USES 135 MPH WIND SPEED. REVISE
 CALCULATIONS AS REQUIRED.
  
 2- ENGINEER CALCULATIONS SPECIFIED ROOF PRODUCT
 APPROVAL SYSTEM S-28 WITH DESIGN PRESSURES OF -52.5 PSF
 ON PAGE 14 OF FLORIDA PRODUCT APPROVAL FL5293-R3. THIS
 SYSTEM IS NO SHOWN ON PAGE 14. REVISE/CLARIFY AS
 REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-01-11 Cont ID  
Sent By jgomez Date 2012-01-11 Time 15:02 Rev Time 0.00
Received By jgomez Date 2012-01-11 Time 15:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-01-10 Cont ID  
Sent By jgomez Date 2012-01-10 Time 09:01 Rev Time 0.00
Received By jgomez Date 2012-01-10 Time 09:01 Sent To  
Notes
***NONE***