Plan Review Stops For Permit 12010160 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2012-01-12 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2012-01-12 |
Time |
14:00 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2012-01-12 |
Time |
14:00 |
Sent To |
|
|
Notes |
2012-01-12 14:05:30 | SERVICE IS ON ZERO LOT LINE OF BUILDING. | | | | NEED SURVEY AND PERMISSION FROM OWNER OF BUILDING AND | | OWNER OF PARKING LOT | | TO HAVE SERVICE ON THAT SIDE OF BUILDING. | | | | FAULT CURRENT SUPPLIED STATES 45,159 AMPERES AT FPL | | NEED 50,000 AIC RATED FUSES/CIRCUIT BREAKER AT MAIN. | | | | | | | | J. LEAHY 01/12/12 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2012-01-12 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2012-01-12 |
Time |
14:05 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2012-01-12 |
Time |
14:05 |
Sent To |
|
|
Notes |
2012-01-10 12:06:29 | TO ELECTRIC |
|
|
|