Plan Review Details - Permit 12010160
Plan Review Stops For Permit 12010160
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2012-01-12 Cont ID  
Sent By jleahy Date 2012-01-12 Time 14:00 Rev Time 0.00
Received By jleahy Date 2012-01-12 Time 14:00 Sent To  
Notes
2012-01-12 14:05:30SERVICE IS ON ZERO LOT LINE OF BUILDING.
  
 NEED SURVEY AND PERMISSION FROM OWNER OF BUILDING AND
 OWNER OF PARKING LOT
 TO HAVE SERVICE ON THAT SIDE OF BUILDING.
  
 FAULT CURRENT SUPPLIED STATES 45,159 AMPERES AT FPL
 NEED 50,000 AIC RATED FUSES/CIRCUIT BREAKER AT MAIN.
  
  
  
 J. LEAHY 01/12/12