Plan Review Details - Permit 12010058
Plan Review Stops For Permit 12010058
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2012-02-09 Cont ID  
Sent By wjolin Date 2012-02-09 Time 13:31 Rev Time 0.00
Received By wjolin Date 2012-02-09 Time 13:14 Sent To M
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2012-01-12 Cont ID  
Sent By wjolin Date 2012-01-12 Time 13:52 Rev Time 0.00
Received By wjolin Date 2012-01-12 Time 12:07 Sent To M
Notes
2012-01-12 13:52:45901 45TH STREET - MAINTENANCE BUILDING
 PERMIT #12010058
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER FLORIDA STATUTES, FIRE SPRINKLER DRAWINGS AND
 HYDRAULIC CALCULATIONS ARE REQUIRED TO BE SIGNED AND
 SEALED BY A PROFESSIONAL ENGINEER FOR THE DESIGN OR
 ALTERATION OF 50 OR MORE AUTOMATIC FIRE SPRINKLERS.
  
 SPRINKLER DESIGN SHALL CONFORM TO THE REQUIREMENTS OF
 THE 2007 EDITION OF NFPA 13 AS OF JANUARY 1, 2012.
  
 SUBMIT HYDRAULIC CALCULATIONS FOR REVIEW AND PROVIDE
 HYDRAULIC DESIGN PLACARD ON RISER.
  
 PROVIDE WATER SUPPLY INFORMATION (FIRE PUMP TEST OR
 HYDRANT FLOW TEST, ETC.).
  
 INDICATE THE MAXIMUM SYSTEM WORKING PRESSURE FOR THIS
 FLOOR.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 PROVIDE PERMANENT WEATHERPROOF SIGN MARKING THE FIRE
 DEPARTMENT CONNECTION.
  
 THE 4-INCH STANDPIPE RISER ON THE EAST SIDE OF THE
 BUILDING APPEARS TO BE SUPPLYING THE SPRINKLER SYSTEM;
 HOWEVER, THERE ARE SPRINKLERS LOCATED BOTH UPSTREAM AND
 DOWNSTREAM OF THE FLOOR CONTROL ASSEMBLY. PLEASE
 EXPLAIN.
  
 TWO STORAGE ROOMS ON SHEET 2 DO NOT INDICATE THE
 FINISHED CEILING TO BE RUN TIGHT TO THE BOTTOM OF THE
 WOOD CEILING JOISTS. SPRINKLERS WILL BE REQUIRED IN THE
 COMBUSTIBLE CONCEALED SPACE IF THE CEILING IS LOCATED
 MORE THAN 6-INCHES BELOW THE JOISTS. VERIFY CEILING
 ELEVATION IN RELATION TO THE JOISTS.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2012-02-13 Cont ID  
Sent By hmoser Date 2012-02-13 Time 13:21 Rev Time 0.00
Received By hmoser Date 2012-02-02 Time 15:55 Sent To  
Notes
2012-02-02 15:55:59SENT TO FIRE SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2012-01-18 Cont ID  
Sent By hmoser Date 2012-01-18 Time 09:14 Rev Time 0.00
Received By hmoser Date 2012-01-06 Time 11:26 Sent To  
Notes
2012-01-06 11:27:04TO FIRE
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2012-02-13 Cont ID  
Sent By hmoser Date 2012-02-13 Time 13:21 Rev Time 0.00
Received By hmoser Date 2012-02-13 Time 13:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2012-01-18 Cont ID  
Sent By hmoser Date 2012-01-18 Time 09:01 Rev Time 0.00
Received By hmoser Date 2012-01-18 Time 09:01 Sent To  
Notes
2012-01-18 09:13:36PLANS DENIED REFER TO FIRE COMMENTS.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]